Operating Instructions
65
Configuration Menu
The Configuration menu displays a list of
functions that identifies unit operating features
and current settings. The following functions are
available: Container ID, Control Type, In-range,
Controller Type, Contrast, Language, Economy
Max, Economy Min., Reefer Type, Supply LH,
AFAM Options, Evaporator Fans, AFAM Setup,
Auto Configuration and Serial Number.
NOTE: When a spare parts controller is installed
and powered up for the first time, an automatic
configuration feature detects the unit options
installed on a unit. After the initial unit power
up, the controller turns the Auto Configuration
feature off. See “Replacing the Controller” in
this chapter for more information.
A complete listing of the controller operating
menu is located on an 11” x 17” fold out on the
last page in this manual.
Viewing or Setting Functions
With the
U
NIT
O
N
/O
FF
switch
O
N
and the LCD
display showing the standard display (setpoint):
1. Press the
F2
or
F3
key to enter the Main
menu.
2. Press the
F2
or
F3
key to scroll through Main
menu until [CONFIGURATIONS] appears in
LCD display.
3. Press the
F4
key to access the Configurations
screen. Configurations screen appears with
cursor in the [CONTAINER-ID] menu line.
4. Press the
F2
or
F3
key to scroll cursor to view
or reset the desired function:
Container ID:
Sets the container identification
number. Enter up to 11 characters (numbers or
letters).
Control Type:
Unit type based on serial plate.
In-Range:
Sets the temperature value for the
controller’s In-range LED and datalogger
functions (factory default = 1.5 C [2.7 F]). Enter a
value from 0.5 to 5.0 C (0.9 to 8.9 F).
Figure 37: Configuration Menu
Economy Max:
Sets the Economy mode maximum
temperature limit (factory default = 0.2 C). Enter
a value from 0 to 5.0 C (0 to 8.9 F).
Economy Min:
Sets the Economy mode minimum
temperature limit (factory default = 2.0 C). Enter
a value from 0 to 5.0 C (0 to 8.9 F).
24 Hr Defrost:
Sets the defrost interval to 24 hrs if
the return temperature is with in 5 degree C from
Set point. Next defrosts will be
30-36-42-48-48-48.
DATA
CONFIGURATION
Configuration
Menu
- Cont ID
- Ctrl Type
- In Range
- Economy Max
- Economy Min
- 24 Hr. Defrost
- Unit Type
- Zero Curr.
- PRS. Sensor
- Supply LH
- AFAM Opt.
- Gas Analyzer
-
AFAM Units
-
AFAM Type
- Evap. Type
- Cond. Type
- Chart R.
- Auto Config.
- Unit #
- Unit ID
MAIN MENU
DATALOGGER
MISC. FUNCTIONS
COMMANDS
NOTE: All screens are NOT
present on all units. The
screens that display on the
controller are determined by
the Controller Software
settings and the options
installed on the unit.
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...