Servicing The Unit
Taking Care of the Structure
Inspecting the Unit
Inspect the unit during unit pretrip inspection and
every 1,000 operating hours for loose or broken
wires or hardware, compressor oil leaks, or other
physical damage which can affect unit
performance and require repair or replacement of
parts.
Checking the Mounting Bolts
Check and tighten all unit, compressor, and fan
motor mounting bolts during pretrip inspections
and every 1,000 operating hours. Unit mounting
bolts should be tightened to a torque value of
204 N•m (150 ft-lb). Compressor and fan motor
mounting bolts should be tightened to a torque
value of 20 to 21 N•m (15 to 20 ft-lb).
Cleaning the Condenser Coil
Clean the condenser coil by blowing low pressure
compressed air or a medium pressure warm water
spray from the inside of the coil outward (opposite
direction of normal airflow). Inspect coil and fins
for damage and repair if necessary.
If a build up of salt or debris is present on the
condenser coil, the coil should be cleaned using a
mild alkaline cleaner with a pH of 9.5 to 10.5. For
example, a 2-3 percent solution of SIMPLE
GREEN
®
would make a suitable cleaning
solution. Apply the solution using a pressure
spray/wash type apparatus. Spray the condenser
coil thoroughly from both the inside and outside
of the coil. Always thoroughly rinse the coil with
a fresh water spray.
Also inspect the directional airflow condenser
grille for damage. This grille directs the condenser
airflow out and away from the unit to increase the
efficiency of the condenser coil by preventing the
recirculation (short cycling) of warm air through
the coil. Abnormally high head pressures may
result if this special condenser grille is damaged
or missing.
Cleaning the Evaporator Coil
Clean the evaporator coil by blowing low pressure
compressed air from the bottom side of the coil
upward (opposite direction of normal airflow).
Inspect coil and fins for damage and repair if
necessary.
Cleaning the Defrost Drains
Clean the defrost drains every 1,000 operating
hours to be sure the lines remain open.
1.
Tighten Unit Mounting Bolts
2.
Tighten Compressor, Condenser Fan and
Evaporator Fan Mounting Bolts
Figure 99: Mounting Bolts
1
2
AMA306
CAUTION: Air pressure or water spray
must not be high enough to damage coil
fins
CAUTION: Air pressure must not be high
enough to damage coil fins
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...