Watercool
Watercool is turned ON when the unit is equipped with the optional water cooled condenser.
When Watercool is turned OFF the condenser fan runs as required.
When Watercool is turned ON the condenser fan does not run unless no cooling water is available, then
the unit will trip off on HPCO and the condenser fan will run as required.
Figure 49: Watercool
Humidity Control
During Chill mode operation, a dehumidification function is available to reduce the relative humidity in
the container to the desired humidity setpoint.
HUMIDITY SENSOR mounted must be selected under the CONFIGURATION/OPTIONS/HUMIDITY
SENSOR for HUMIDITY CONTROL to be active or visible. See complete description of HUMIDITY
CONTROL under Operating Theory section of this manual
Figure 50: Humidity Control