Specifications
17
Electrical System Specifications
Compressor Motor:
Type
460/380V, 60/50 Hz, 3 Phase
Kilowatts
4.48 kW @ 460V, 60 Hz
Horsepower
6.0 hp @ 460V, 60 Hz
RPM
3550 RPM @ 460V, 60 Hz
Locked Rotor Amps
70 amps @ 460V, 60 Hz
Condenser Fan Motor:
Type
460/380V, 60/50 Hz, 3 Phase
Kilowatts
0.55 kW @ 460V, 60 Hz
Horsepower
0.75 hp @ 460V, 60 Hz
Number: All Models
1
Motor:
RPM
1725 RPM @ 460V, 60 Hz
Full Load Amps
1.0 amps @ 460V, 60 Hz; 1.0 amps @ 380V, 50 Hz
Locked Rotor Amps
3.9 amps @ 460V, 60 Hz; 3.7 amps @ 380V, 50 Hz
Evaporator Fan Motors:
Type
460/380V, 60/50 Hz, 3 Phase
Kilowatts
0.75 kW @ 460V, 60 Hz
Horsepower
1.0 hp @ 460V, 60 Hz
Motor:
RPM (Each): High Speed
3450 RPM @ 460V, 60 Hz
Low Speed
1725 RPM @ 460V, 60 Hz
Full Load Amps (Each): High Speed
1.6 amps @ 460V, 60 Hz
Low Speed
0.8 amps @ 460V, 60 Hz
Locked Rotor Amps: High Speed
10.5 amps @ 460V, 60 Hz
Low Speed
9.0 amps @ 460V, 60 Hz
Electrical Resistance Heater Rods:
Type
460/380V, 60/50 Hz, 3 Phase
Number:
Normal Capacity
Normal Capacity
Extended Capacity
6 (18 ga wire)
3 (18 ga wire)
3 (16 ga wire)
Watts (Each):
Normal Capacity
Normal Capacity
Extended Capacity
680 Watts @ 460V, 60 Hz
1360 Watts @ 460V, 60 Hz
2000 Watts @ 460V, 60 Hz
Current Draw (Amps):
Normal Capacity
Extended Capacity
5 amps total @ 460V across each phase at heater contractor
4.5 amps total @ 460V across each phase at heater contractor
Control Circuit Voltage:
29 Vac @ 60 Hz
Содержание 098203
Страница 2: ......
Страница 3: ...MAGNUM TK 60275 4 MM Rev 3 08 15 Copyright 2012 Ingersoll Rand EMEIA Printed in Ireland...
Страница 193: ...Refrigeration Maintenance 191 Figure 163 Filter Drier...
Страница 200: ...Refrigeration Maintenance 198 Figure 169 Receiver Tank Figure 170 Water Cooled Condenser Tank...
Страница 257: ...255 Schematic Diagram RELEASED 19 Sep 2013...
Страница 258: ...256 Wiring Diagram Page 1 of 2 RELEASED 19 Sep 2013...
Страница 259: ...257 Wiring Diagram Page 2 of 2 RELEASED 19 Sep 2013...
Страница 263: ......