Refrigeration Maintenance
84
Evacuating and Charging
Smart Reefer Multi-Temp
Systems
Set-up Unit
The Smart Reefer Multi-Temp µP-IV
microprocessor must be placed in the Evacuation
Mode to evacuate and charge the unit. When the
microprocessor is in the Evacuation mode it opens
all the solenoid valves in the refrigeration system.
This allows the refrigeration system to be
evacuated properly. Refer to the appropriate
Diagnosis Manual for complete information about
the microprocessor. Use the following procedure
to set-up the unit and the place the microprocessor
in the Evacuation mode:
1. Connect a battery charger to the unit battery.
The battery charge must have an output of at
least 15 amperes. This will maintain the
charge level of the battery during the time
required to evacuate and the charge the unit.
The microprocessor's Service Test mode is
used to open unit valves as required for
evacuation. Failure to connect a battery
charger may result in the battery voltage
falling too low to reliably operate the
microprocessor and valves.
2. Use the CYCLE-SENTRY Selection screen to
select Continuous Run operation if
Continuous Run operation is not already
selected.
3. Place the Zone 1/Host On/Off switch in the
Off position.
4. Place the Zone 1/Host, Zone 2, and Zone 3
On/Off switches in the On position.
5. Clear any alarm codes using the
C
ODE
and
C
LEAR
keys.
6. With the standard screen on the display and
before the engine starts, press the
TK
key and
hold it down (for 3 to 5 seconds) until [PrE]
[TRIP] appears on the display.
7. Press the
S
ELECT
key. If [OFF] and [PRNT]
appear on the display, press the
S
ELECT
key
again. The letters [REV] should appear in the
lower display and the revision number should
appear in the upper display.
8. With the revision screen on the display, press
both the
TK
key and the
C
LEAR
key and hold
them down (for 3 to 5 seconds) until [TEST]
and [VAC] appears on the display.
9. Press the
E
NTER
key to load the Evacuation
mode [VAC]. All normally closed valves will
be energized.
The display should show [TEST] and [VAC].
If the display shows [SET] and [VAC], a
higher rate of battery charge is required.
Alarm Code 109 will be generated. This is
normal.
10. The microprocessor is now in the Evacuation
mode. The refrigeration system is set-up for
evacuation and charging.
Evacuating the System
1. Be sure all refrigerant has been recovered
from the unit.
2. Connect a vacuum pump and gauge manifold
for 3 point evacuation to the suction service
valve, discharge service valve, and receiver
tank outlet valve.
NOTE: The use of the Thermo King
Evacuation Station P/N 204-725 or 204-744
is recommended.
3. Verify proper operation of the Evacuation
Station as shown in the Evacuation Station
Operation Manual TK 40612.
4. Start the evacuation pump and mid-seat the
suction service valve, discharge service valve,
and receiver tank outlet valves.
5. Install service valve stem caps with seals and
tighten them. The valve stems should remain
capped while evacuating the unit.
6. Evacuate the unit to 500 microns.
7. Continue to evacuate the unit for one
additional hour after reaching 500 microns.
This insures complete evacuation of the
remote evaporators and lines.
8. Close the Evacuation Station valve nearest the
vacuum pump (V1) to isolate the vacuum
pump from the system. Turn the vacuum
pump off.
Содержание 002008
Страница 4: ...4 ...
Страница 25: ...Unit Description 25 Figure 3 Zone 1 Cool Zone 2 Cool and Zone 3 Cool Zone 3 Zone 2 Zone 1 AGA168 ...
Страница 27: ...Unit Description 27 Figure 4 Zone 1 Cool Zone 2 Cool and Zone 3 Heat Zone 3 Zone 2 Zone 1 AGA169 ...
Страница 30: ...Unit Description 30 Figure 9 Front View AJA920 ...
Страница 31: ...Unit Description 31 1 Access Panels 2 Defrost Damper Figure 10 Back View 1 2 ARA104 ...
Страница 114: ...Mechanical Diagnosis 114 ...
Страница 116: ...Electric Standby Diagnosis 116 ...
Страница 120: ...Remote Evaporator Specifications 120 ...
Страница 122: ...Remote Evaporator Maintenance Inspection Schedule 122 ...
Страница 128: ...Remote Evaporator Electrical Maintenance 128 ...
Страница 132: ...Remote Evaporator Refrigeration Service Operations 132 ...
Страница 134: ...Remote Evaporator Structural Maintenance 134 ...
Страница 136: ...Remote Evaporator System Diagnosis 136 ...
Страница 140: ...Index 140 ...
Страница 142: ......
Страница 143: ...143 Model 30 Schematic Diagram Page 1 of 2 ...
Страница 144: ...144 Model 30 Schematic Diagram Page 2 of 2 ...
Страница 145: ...145 Model 30 Wiring Diagram Page 1 of 4 ...
Страница 146: ...146 Model 30 Wiring Diagram Page 2 of 4 ...
Страница 147: ...147 Model 30 Wiring Diagram Page 3 of 4 ...
Страница 148: ...148 Model 30 Wiring Diagram Page 4 of 4 ...
Страница 149: ...149 Model 50 Schematic Diagram Page 1 of 2 ...
Страница 150: ...150 Model 50 Schematic Diagram Page 2 of 2 ...
Страница 151: ...151 Model 50 Wiring Diagram Page 1 of 5 ...
Страница 152: ...152 Model 50 Wiring Diagram Page 2 of 5 ...
Страница 153: ...153 Model 50 Wiring Diagram Page 3 of 5 ...
Страница 154: ...154 Model 50 Wiring Diagram Page 4 of 5 ...
Страница 155: ...155 Model 50 Wiring Diagram Page 5 of 5 ...