37

ENGLISH

 

 

Pump controller

The pump is configured in the factory for a maximum head of 

7 metres.

When necessary, the user interface provides access to:

- Functioning (performance display) mode. Pump perfor-

mance is displayed during functioning as a % of current 

draw with respect to rated load. Alarm conditions can 

be seen from the colour of LED.

- Setting Mode: Press button (1) to enter setting mode 

and select the type of pump curve.

USER INTERFACE

The user interface consists of a push-button (1), a red/green 

LED (2) and four yellow LEDs (3).

1

2

3

LED 1 LED 2 LED 3 LED 4 LED 5

FUNCTIONING MODE

Performance display

When the pump is running, LED 1 is green. The four yellow 

LEDs indicate the pump's instantaneous electrical power con-

sumption as shown in the table.

Nr. displayed

Meaning

% power

LED 1 flashing green

Standby

0

LED 1 green and LED 2 yel-

low, both lit

Low load

0-25

LED 1 green and LEDs 2, 3 

yellow, all lit

Low-medium 

load

25-50

LED 1 green, LEDs 2, 3, 4 

yellow, all lit

Medium-high 

load

50-75

LED 1 green, LEDs 2, 3, 4, 5 

yellow, all lit

High load

75-100

The pump functions at fixed speed.

Alarm display

If the pump detects one or more alarm conditions, LED 1 

changes from green to red. When an alarm is active, the LEDs 

indicate the type of alarm as shown in the following table. If 

more than one alarm is active at the same time, the LEDs only 

show the alarm condition with the highest priority. Alarm priori-

ty follows the order of the table.

When no alarm is active, the user interface automatically dis-

plays pump performance.

Nr. displayed

Meaning

Function

Action

LED 1 red and 

LED 5 yellow, 

both lit

The pump 

rotor is 

blocked

The pump 

automatically 

attempts to 

start every 1.5 

seconds

Wait or 

check that 

the pump 

rotor is free 

to rotate

LED 1 red and 

LED 4 yellow, 

both lit

Supply 

voltage too 

low

Indication only. 

The pump 

continues to 

function

Check the 

voltage of 

the power 

supply

LED 1 red and 

LED 3 yellow, 

both lit

Electronic 

controller 

error

The pump has 

stopped be-

cause supply 

voltage is too 

low or because 

an error has 

occurred in the 

internal elec-

tronic controller

Check the 

voltage of 

the power 

supply or 

replace the 

pump

Содержание 20109806

Страница 1: ...ACQUAHOME 32 B 32 BS INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...lowing di rectives Directive 92 42 EEC on efficiency requirements Electromagnetic Compatibility Directive 2014 30 EU Low Voltage Directive 2014 35 EU Ecodesign Directive 2009 125 CE for energy related...

Страница 3: ...ections 18 Boiler water circuit 18 Typical water system schematics 19 Fuel connections 19 Flue gas vent and comburent air intake 21 Technical specifications of stack 22 Connection to the stack 22 Syst...

Страница 4: ...d must ALWAYS ac company the boiler even if it is sold to another Owner or User or transferred to another plant If it is damaged or lost request another copy from your local Technical As sistance Cent...

Страница 5: ...gram and sends a lockout signal to the control panel in the event of an error b The intervention of a safety device indicates a potentially dangerous malfunction in the system Contact the manu facture...

Страница 6: ...Storage cylinder fill cock 10 Fuel oil drip tray 11 Storage cylinder inspection flange 12 Storage cylinder flange insulation 13 Central heating circuit pump 14 Non return valve 15 Boiler circulator 16...

Страница 7: ...l cock 10 Fuel oil drip tray 11 Storage cylinder inspection flange 12 Storage cylinder flange insulation 13 Central heating circuit pump 14 Non return valve 15 Boiler circulator 16 Boiler body 17 Flam...

Страница 8: ...urent air inlet ACQUAHOME 32 B 7 Oil pump pressure adjuster screw 8 Pressure gauge fitting 9 Photoresistor 10 Combustion head 11 Motor 12 Comburent air inlet ACQUAHOME 32 BS OIL PUMP 7 6 5 4 3 2 1 8 1...

Страница 9: ...al energy consumption QHE 104 8 104 8 GJ Daily electrical energy consumption Qelec 0 1 0 1 kWh Annual electrical energy consumption AEC 29 29 kWh Daily fuel consumption Qfuel 26 3 26 3 kWh Annual fuel...

Страница 10: ...ith storage cylinder at 60 C 190 l Specific flow rate EN 13203 20 l min Replenishment time T 35 C 14 min Maximum operating pressure of storage cylinder 6 bar Volume of expansion vessel DHW 3 l Prechar...

Страница 11: ...0 0 1 0 2 0 3 0 4 0 5 0 Q l s 10 20 30 40 50 W P1 Residual head Flow rate 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Q m h 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 The curves refer to a water dens...

Страница 12: ...12 ENGLISH Location of sensors ACQUAHOME 32 B 32 BS TS 3 1 2 TS Safety thermostat sensor 1 Boiler sensor 2 Storage cylinder sensor 3 Boiler temperature gauge socket...

Страница 13: ...5 Indicator showing a burner lockout for a tripped safety thermostat red Lights to show that the safety thermostat has tripped 6 Burner lockout indicator red Lights to show that the burner locked out...

Страница 14: ...arranty certificate Located inside the front panel Fuel oil drip tray Positioning of labels A A Packing label b The instruction manual is an integral part of the boiler Once located read it thoroughly...

Страница 15: ...Pull out the staples B and remove the front of the cage first in order to slide it off to the rear B 1 Remove the polystyrene edge protectors 2 Pull off the protective bag 3 2 3 a Do not dispose of p...

Страница 16: ...er the burner To move the boiler manually proceed as follows Unscrew the screws 1 securing the boiler to the pallet 1 1 Lift the boiler by inserting two 1 diameter pipes 2 through the lifting holes 3...

Страница 17: ...ME 32 B boiler Installation in older systems and systems requiring modernisation When installing these boilers in older systems or systems re quiring modernisation always perform the following checks...

Страница 18: ...B 32 BS A 80 mm B 120 mm C 210 mm D 460 mm E 1020 mm F 1080 mm G 45 mm MI CH flow 1 M RI CH return 1 M UACS domestic hot water outlet 1 2 M RC recirculation 1 2 M SC drain 10 mm EAFS domestic cold wa...

Страница 19: ...o the fitting 2 Make sure that these connections are oil tight 640 675 2 1 Description ACQUAHOME 32 B ACQUAHOME 32 BS Fittings 2x3 8 M If the oil feed system is in negative pressure the return line mu...

Страница 20: ...tion cy cle again up to the ignition of the flame max 4 m H H Automatic shut off device if fitted For details of the electrical connections see the Automatic shut off de vice DAI section on page 25 H...

Страница 21: ...the flue A Models ACQUAHOME 32 B i 120 280 128 ACQUAHOME 32 B boilers derive their comburent air from the room in which they are installed Suitable air vents must therefore be provided in compliance w...

Страница 22: ...tem at the bottom b The diameter of the stack must never be smaller than that of the flue pipe from the boiler b In configuration B23 the stack must guarantee the min imum draught specified by applica...

Страница 23: ...value specified in the table it is mandatory to install a water softening system b Excessive water softening leading to a total hardness 15 F can cause corrosion in metal parts pipes and boiler compo...

Страница 24: ...urn the control panel function selector to 0 Close the water supply shut off cocks To empty the boiler connect a rubber hose int 12mm to the hose union on the boiler drain cock 1 or storage cylinder d...

Страница 25: ...lue HEAT REQUEST BURNER CONTROLLER RESET 4 D AE Power supply COM G 3 position function selector TS Safety thermostat 100 C 0 6 TA Room thermostat LV Mains power indicator LR1 Burner lockout indicator...

Страница 26: ...e all removed components in the opposite order Refer to the manual provided with the storage cylinder electri cal interface kit for details of the storage cylinder s electrical connections see the Cat...

Страница 27: ...setting key T2 Boiler parameter selection setting key T3 Value increase button T4 Value decrease button S1 Storage cylinder temperature setpoint indicator yellow S2 Boiler temperature setpoint indica...

Страница 28: ...d changing storage cylinder settings Displaying and changing boiler settings Displaying hours remaining to the next service Enter pass word Changing boiler pa rameters P0 P1 PA PD Changing s t o r a g...

Страница 29: ...ove pro ceed as follows to start up the boiler for the first time turn the boiler s mains power switch ON Set the room thermostat to the required temperature 20 C or if the system has a timer or timer...

Страница 30: ...to the ignition of the flame If boiler temperature becomes too high the manual reset safe ty thermostat trips b If the safety thermostat trips T 100 C the warning light on the control panel comes on P...

Страница 31: ...ores the boiler tem perature display CHANGING THE FUNCTIONING MODE You can only change the boiler s functioning mode when the display is reading out either boiler or storage cylinder temper ature Pres...

Страница 32: ...is shown on the three digit display The default value is 50 C Pressing the or key once more changes the value Press the key to confirm the setpoint and return to the stor age cylinder temperature dis...

Страница 33: ...hundreds of hours The combination of the decimal point on the right and that in the middle represents a value in tens of thousands of hours to be summed to the previous value 0 39999 x100 h P7 This de...

Страница 34: ...not enter a password or enter the wrong password the access procedure is automatically cancelled Enter the correct password then press the Mode selec tion key to confirm it You can now view and modif...

Страница 35: ...ses excess heat only to the storage cylinder 0 1 0 1 digit P5 This determines whether domestic hot water production has priority over the central heating or not If this parameter is set to 1 when dome...

Страница 36: ...r from position to and back The room thermostat or timer setting is changed Make sure that all the pumps in the system are free and rotate in the right direction Turn the mains power switch OFF and ma...

Страница 37: ...t Medium high load 50 75 LED 1 green LEDs 2 3 4 5 yellow all lit High load 75 100 The pump functions at fixed speed Alarm display If the pump detects one or more alarm conditions LED 1 changes from gr...

Страница 38: ...EDs except the red LED flash for one second to indicate that the button lock function has been activated deactivated Setting mode To modify settings press the button 1 for between 2 and 10 seconds Use...

Страница 39: ...or extraneous light or false flame signal during t2 the burner controller waits for time t2 then enters lockout the motor does not start t2p Maximum fuel oil pre heating time the burner controller wai...

Страница 40: ...ctrode V Fuel oil valve F Flame detector LED Colour of button LED Lockout caused by extraneous light during pre purging t2 t1 P M t3l ts HT FM F V LED ID Lockout Red Flashing orange POWER ON Flashing...

Страница 41: ...lt ORANGE GREEN alternate flashing Slow 0 5 0 5 Fault diagnosis lockouts Description of lockout Lockout time Presence of extraneous light during standby After 25 seconds Presence of extraneous light d...

Страница 42: ...y time if a heat request is cancelled during normal functioning NOTE If extraneous light or a false flame signal is detected during post purging the burner locks out after 25 seconds If a new heat req...

Страница 43: ...Programming allowed in OPERATING mode and in STANDBY Press button for 5 sec t 10 sec RED led Blinking 2 times 0 2s ON 0 2s OFF Release the button The burner shuts down and restarts The burner shuts d...

Страница 44: ...extended for another 10 seconds by pressing the reset button again while the lockout type is being displayed Always wait 1 second between every press and release of the button to ensure correct interp...

Страница 45: ...lockouts on page 41 PRE AND POST IGNITION During pre ignition the ignition electrode switches on 2 sec onds before the fuel oil valve opens During post ignition the ignition electrode switches off 3 s...

Страница 46: ...is appears CHECKING THE ELECTRONIC CIRCUIT CONTROLLING THE OIL VALVE The control box detects the presence of a fault inside the elec tronic circuit controlling the oil valve the fault is indicated by...

Страница 47: ...the pumps if there is a risk of freezing Preparing for extended periods of disuse If the boiler is not going to be used for an extended period of time proceed as follows to prepare it for shut down O...

Страница 48: ...ainte nance or cleaning Turn the mains power switch OFF and turn the control panel function selector to OFF close all external fuel shut off cocks Annual cleaning Cleaning and maintaining the burner P...

Страница 49: ...follows to remove the blast tube Remove the screws 1 and remove the blast tube 1 b With the blast tube removed check its front edge to make sure that it is smooth free from deposits burns and dents R...

Страница 50: ...G THE BURNER CONTROLLER The burner cover has to be removed first in order to remove the controller Proceed as follows Loosen the screw 1 open the cover 2 and remove all the components inside Remove th...

Страница 51: ...remove the turbulators 6 and check them for wear and fin angle replace as necessary use a flue brush 7 or other suitable tool 7 6 remove any displaced soot through the combustion chamber hole Proceed...

Страница 52: ...linder The storage cylinder should be serviced once a year to check the condition of the internal parts and the magnesium anode Perform the following operations before beginning any clean ing Remove t...

Страница 53: ...ction sensor failure or short circuit The indicator shows steady light SEr Service threshold near warning When the burner reaches 90 of the operating hours set in boiler parameter P7 see Programming P...

Страница 54: ...capacity insufficient Check and adjust the burner Problem with boiler control card Check correct functioning Check the temperature setting View functioning parameters The generator triggers a thermal...

Страница 55: ...Supply pressure too high Fit a pressure reducer Flow rate too high Fit a flow reducer Limescale and or sludge in storage cylinder Check and clean Check the functioning of the DHW cir cuit pump Check t...

Страница 56: ...s light Eliminate cause of light or false flame signal The burner performs pre purging and ignition correctly but locks out after about 5 seconds RED Flame detector dirty Clean the flame detector The...

Страница 57: ...57 ENGLISH...

Страница 58: ...58 ENGLISH...

Страница 59: ...59 ENGLISH...

Страница 60: ...Tel 0499323911 Fax 0499323972 www thermital it email info thermital it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment a...

Отзывы: