20
LUNA 2T | MACHINE FEA
TURES
5
Technical specifications
s
izes
lUna 2T
6
8
10
12
14
16
Heat output
(@A7/W35)
100% kW
6.16
8.41
9.94
12.08 13.18 15.05
66% kW
4.21
5.23
7.26
7.56
8.51
10.48
33% kW
2.75
2.45
3.33
3.67
4.08
4.92
Compressor power
input
100% kW
1.18
1.63
2.16
2.51
2.74
3.20
Total power input
100% kW
1.34
1.82
2.35
2.75
3.02
3.50
COP
4.59
4.62
4.22
4.39
4.36
4.30
System side
Water flow rate
(system)
m3/h
1.06
1.45
1.71
2.08
2.27
2.59
Useful head
mca
5.20
4.80
5.50
3.00
5.00
4.20
Pump power input
kW
0.06
0.06
0.06
0.06
0.09
0.09
s
izes
lUna 2T
6
8
10
12
14
16
Heat output
(@A7/W45)
100% kW
5.99
8.19
9.76
11.68 12.74 14.52
66% kW
4.08
5.07
7.06
7.28
8.20
10.13
33% kW
2.66
2.37
3.22
3.52
3.92
4.73
Compressor power
input
100% kW
1.50
2.04
2.75
3.06
3.35
3.90
Total power input
100% kW
1.65
2.23
2.95
3.30
3.62
4.20
COP
3.62
3.67
3.31
3.54
3.52
3.46
System side
Water flow rate
(system)
m3/h
1.03
1.41
1.68
2.01
2.19
2.50
Useful head
mca
6.50
4.70
4.50
3.40
4.90
3.80
s
izes
lUna 2T
6
8
10
12
14
16
Cooling Capacity
(@A35/W18)
100% kW
8.05
10.65 12.59 15.48 16.83 19.27
66% kW
5.58
6.54
9.44
9.77
10.92 13.44
33% kW
3.70
3.12
4.45
4.78
5.29
6.38
Compressor power input
100% kW
1.36
1.88
2.56
2.67
3.04
3.76
Total power input
100% kW
1.52
2.07
2.76
2.91
3.32
4.06
EER
5.29
5.15
4.57
5.32
5.07
4.75
System side
Water flow rate (system)
m3/h
1.39
1.83
2.17
2.66
2.90
3.31
Useful head
mca
5.60
4.00
3.40
1.90
3.60
2.70