1
Getting started
1.1
Getting started
Installation
The accumulator tank should stand on a solid surface and be leveled with assistance from the setscrews underneath the tank (not fitted
on all models). The tank models that come without setscrews can be leveled with assistance of a shim. This must be done before the
tank is connected to the pipes and filled with water. See picture below for adjusting the setscrews. Connections not in use must be
plugged appropriately. During water filling, condensed water may emerge on the outside of the tank. This will result in water under-
neath the tank, on the floor. This will cease when the tank is heated. There must be a floor drain in the same room.
To temporarily remove the insulation, for instance if there is a narrow passage to fit the tank through, see the below instructions (not
applicable to all models). All the screws holding the insulation in place is of Torx 10 type.
1
2
3
2
1
1. Start by removing the screws that holds the locks in
place. At the top and bottom.
2. Flip the locks.
3. Remove the screws all the way down. The side is also fit-
ted with a velcro on the inside.
4. Put the insulation back in the reversed order.
Adjust the setscrews according to the measures below.
1
2
3
1. Foot length is 14mm.
2. Maximum length between floor and tank is 39mm, in-
cluding foot.
3. Maximum screw length is 25mm, excluding foot.
Commissioning
Start by filling the tank, then pressurize it. Continue to fill the radiator system (the enclosed water). The working pressure may not ex-
ceed the test pressure (4,3 or 8,6 bars, gauge). A safety valve with releasing pressure of that of the test pressure must always be installed.
Maintenance
Check the safety valve annually by manually opening and closing the valve handle and making sure that water is released. Check annu-
ally all connections for eventual leakage (also peripheral installations, i.e. a heat pump, etc).
Electric installation
▪
The electrical installation must be performed by an authorised installer and follow applicable norms and regulations.
▪
When selecting electrical equipment, it must be selected with approved materials and enclosure class.
Disassembling the product
When disassembling the product, applicable laws and regulations must be observed. Contact your installer for more information.
Installation Guide
WT-C Accumulator tanks
VIBND502
Thermia AB