Parameter
Meaning
DISTRIBUTION
CIRCUIT 1 - 2
Indicates if the distribution circuit must be controlled by a heat curve or by a constant temperature.
Factory setting:
HEAT CURVE, range:
HEAT CURVE – CONSTANT TEMP - OPEN CIRCUIT. At the selection OPEN CIRCUIT, the shunt outputs are not ac-
tive, but the temperature for the distribution circuit is displayed in the OP.DATA menu.
Open circuit cannot be used in connection with CONFIGURATION = TANK CONTROL or if external auxiliary heat-
er is configured.
The option (OFF) deactivates the distribution circuit function fully. The menu only appears if distribution cir-
cuit sensor is connected
SHUNT TIME DC1 - 2 Indicates shortest permitted time between control signals to the shunt.
Factory setting: 30s, range: 10s – 99s
DISTR. 1-2 P. COOL Indicates whether the circulation pump for distribution circuit must be used for cooling.
Factory setting: ON, range:
– ON
HEAT STOP DEPEN. Indicates if heating the buffer tank is to be influenced by HEAT STOP.
A condition is that CONFIGURATION = TANK CONTROL.
Factory setting: YES, range: NO – YES
POOL CIRCUIT
Used to indicate where the reversing valve for pool is located. The system supply circuit cannot be used if exter-
nal auxiliary heater is configured.
Factory setting: SYSTEM SUPPLY, range: SYSTEM SUPPLY - DISTRIBUTION CIRCUIT 1 - DISTRIBUTION CIRCUIT 2
MAX TIME POOL determines the longest permitted pool heating time at non-integral controlled circuit.
Factory setting: 40M, range 1M – 210M
MAX TANK TEMP
Maximum permitted temperature in the buffer tank. Fixed value 55°C is used if no external auxiliary heater is
configured. With an external auxiliary heater the temperature can be set between 55°C – 80°C.
Factory setting: 55°C, range: 55°C – 80°C
8.11
OUTD. UNIT INFO
Parameter
Meaning
TEMP SET POINT
The temperature set point, sent from the indoor unit to the outdoor unit.
CONF. SET POINT
The confirmed temperature set point, sent from the outdoor unit back to the indoor unit.
COMPR.(HZ)
The current frequency value of the compressor, in Hz.
COMPR.(%)
The current workload of the compressor, in %.
CURRENT
The electric current of the outdoor unit, in A.
FAN 1 RPM
The current speed of FAN 1, in RPM.
FAN 1(%)
The current workload of FAN 1, in %.
FAN 2 RPM
The current speed of FAN 2, in RPM. For 16kW only.
FAN 2(%)
The current workload of FAN 2, in %. For 16kW only.
EXP.V.STEPS
The current step for the expansion valve. Range: 0-2000.
EXP.V.(%)
The current workload of the expansion valve, in %.
Commissioning
iTec
VIJSR102
Thermia Värmepumpar
40