8
SERVICE menu
8.1
Menu overview
N
To be able to chose a specific function, the sensor for that function
must be connected.
▪
HOT WATER
▪
HEATING
▪
COOLING
▪
AUX. HEATER
▪
MANUAL TEST
▪
INSTALLATION
▪
SYSTEM
▪
HEAT SOURCE/AIR/DIRECT EVAP./NO SIZE
▪
POOL
▪
DISTR. CIRCUIT 1
▪
DISTR. CIRCUIT 2
▪
BUFFER TANK
▪
OPTIMUM
▪
CURRENT LIMITER
▪
HEAT / PRESSURE ERR.
▪
SERVICE TIME
▪
FACTORY SET
▪
RESET OPER. TIME
▪
SENSOR CALIBRATION
▪
VERSION
▪
LOG TIME
▪
DEFROST
▪
OPTIMUM
▪
BUFFER TANK
▪
OUTD. UNIT INFO
8.2
HOT WATER
Parameter
Meaning
START
Start temperature for hot water production. Shows the actual weighted hot water temperature and the value
within brackets indicates the start temperature. (
= no hot water production)
Factory setting: 40°C, range:
, 30°C – 55°C
STOP
The weighted hot water temperature for stopping hot water production during operation with only compres-
sor.
Factory setting: 55, range: START + 1K – 65°C
HOT WATER TIME
Time for hot water production during combined hot water demand and heating or cooling demand, in minutes.
Factory setting: 30M, range: 5M – 40M
TOPH. INTERVAL
Time interval between peak heating chargings (anti-legionella function) in days. Operating mode that permits
auxiliary heater must be selected.
Factory setting: 7D, (range:
, 1D – 90D
Commissioning
iTec
Thermia Värmepumpar
VIJSR102
33