Menu selection
Meaning
Factory setting
CURVE 0
Local increase or reduction of CURVE at an outdoor temperature of 0°C. Shown in the
graph for CURVE.
0°C(range: -5°C /
5°C)
CURVE -5
Local increase or reduction of CURVE at an outdoor temperature of -5°C. Shown in the
graph for CURVE.
0°C(range: -5°C /
5°C)
HEAT STOP
Maximum outdoor temperature when heat production is permitted.
If HEAT STOP applies, the outdoor temperature must drop 3°C below the setting before
HEAT STOP stops.
17°C(range:
,
0°C / 40°C)
REDUCTION
Only appears if the tariff control function has been activated. Lowering set room temper-
ature. Active at 10 kΩ connection at EVU input.
2°C(range: 1°C /
10°C)
TANK TEMP
Displayed if buffer tank is active. Charges the buffer tank to the set temperature. AUTO
setting charges the tank to the supply line setpoint value.
AUTO(range:
AUTO, 30°C /
55°C)
OVERCHARGE
Displayed if the buffer tank is active and TANK TEMP is set to AUTO. Charges the buffer
tank to supply line setpoint value + the value of OVERCHARGE.
0°C(range: 0°C /
5°C)
ROOM FACTOR
Only displayed if an accessory Room temperature sensor is installed.
Determines how great an impact the room temperature is to have when calculating the
supply temperature. For under floor heating it is recommended that ROOM FACTOR is set
to 1, 2 or 3. For radiator heating it is recommended that ROOM FACTOR is set to 2, 3 or 4.
(0 = no impact, 4 = very large impact).
2(range: 0 / 4)
POOL (Expansion card)
Only appears if POOL is selected. The temperature in the pool is controlled by a separate
sensor regardless of the heating and hot water system.
20°C(range:
,
5°C /40°C)
POOL HYSTERESIS (Ex-
pansion card)
Only appears if POOL is selected. The difference between the desired charge value (ad-
justable) and actual value to the pool sensor. Pool hysteresis does not affect the integral
value.
2°C(range: 1°C /
10°C)
8.3
Sub-menu HEAT CURVE 2
Only appears if shunt group sensor is connected and activated in menu SERVICE -> INSTALLATION - SYSTEM -> SHUNT GROUP.
Menu selection
Meaning
Factory setting
CURVE 2
Calculated shunt group temperature at 0°C outdoor temperature. Shown as a graphic
curve. The curve will be limited by the set values of MIN and MAX.
40°C(range:
22°C / 56°C)
MIN
Minimum permitted shunt group temperature, if the temperature for heat stop has not
been reached.
10°C(range:
10°C / 50°C)
MAX
Maximum permitted shunt group temperature.
55°C(range:
15°C / 70°C)
8.4
Sub-menu TEMPERATURE
The history of different temperature measurements can be viewed by pressing the right arrow key. The graph shows the last 60 meas-
urement points for the set time interval (SERVICE -> INSTALLATION -> LOG TIME). In the event of an alarm, history stops being logged
until the alarm is reset by changing the operating mode to OFF.
Menu selection
Meaning
Factory setting
OUTDOOR
Shows the actual outdoor temperature.
-
ROOM
Shows the actual set temperature.
-
SYSTEM SUPPLY
Displays system supply temperature at the buffer tank system.
-
SUPPLY LINE
Shows the actual supply temperature. The calculated supply temperature to the heating
system group is within brackets.
During hot water production in operating mode AUX. HEATER the value for HOT WATER
STOP + 10° is shown within brackets.
-
Installation Guide
Domestic heat pumps
VMGFP202
Thermia Värmepumpar
48
Содержание Atria Optimum
Страница 15: ...1 Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 15 ...
Страница 72: ...Installation Guide Domestic heat pumps VMGFP202 Thermia Värmepumpar 72 ...
Страница 73: ...Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 73 ...
Страница 74: ...Installation Guide Domestic heat pumps VMGFP202 Thermia Värmepumpar 74 ...
Страница 75: ...Installation Guide Domestic heat pumps Thermia Värmepumpar VMGFP202 75 ...