46
. Heating Boiler Piping Diagrams
(continued)
Figure 17: Multiple Boiler, Primary/Secondary with Common Header Piping
NOTICE
NOTICE
1. These are suggested piping configurations. It is the installer's responsibility to
conform to local codes and ordinances for additional requirements.
2. Pressure relief valve rating shall not exceed pressure rating of any component
in the system.
3. Some piping components cannot be supported by the pipping. Refer to the
manufactures' installation instructions.
4. Circulation pump must be sized to overcome the pressure drop across the entire
loop.
!
A
B
From System
To System
Purge Valve
System Circulator
Air Vent
Expansion Tank
Pressure Reducing Valve
Check Valve
Factory Supplied Manifold
Boiler Circulator
Check Valve
Y-Strainer
Isolation Valve
Make Up Water
No more than 12 inches or 4 pipe diameters
A.
At least 18" of straight pipe for convetional
B.
air scoop
Thermal Solutions Products LLC
Notes:
1. This is a suggested piping configuration. It is the
installer's responsibility to to conform to local codes
and ordinances for additional requirements.
2. Pressure relief valve shall not exceed the pressure
rating of any components in the system.
3. The boiler pump shall be sized to overcome the
pressure drop across the entire boiler loop.
8/30/2019
Multiple AMP Pipng with Common Header