8
3.
Press the Off button to clear the password. The
display shows the following.
Example of password deleted, no password entered
C
.
4.
Press the On button to start the unit. The set
point temperature can occur without the need
for a password.
Pump Status Indicator
There are two indicating lights in the Pump icon.
When the pump is on the upper LED will be green.
When the pump overloads the lower LED will be
yellow.
Heating Status Indicator
There are two indicating lights in the Heating icon.
When Heater 1 is on the upper LED will be green.
When Heater 2 is on the lower LED will be green.
Cooling Status Indicator
When the cooling valve is open, the LED in the
Cooling icon will be green.
Low Level Alarm Indicator
The LED in the Low Level icon will be yellow when
the oil level in the reservoir is too low.
Deviation Alarm Indicator
The LED in the Deviation Alarm icon will be green
when the Deviation Alarm is active. The LED will not
be on if the Deviation Alarm has been turned off.
Automatic Timer Status Indicator
The LED in the Timer icon will be green when the
Automatic Start/Stop Timer is active. The LED will not
be on if the Automatic Start/Stop Timer is not active.
Automatic Cool-Down Prior to Stop
The unit features an automatic cool-down function
that ensures the unit and the fluid cools down to a
safe temperature prior to stopping the unit for
maintenance or repair. This function will cool the unit
to 122°F before stopping the pump. To activate this
function press the Temperature Adjust button,
release, and then press the C button. When activated
the tank temperature displays with a C in front of it
indicating the automatic cooling sequence is active.
This sequence will stop at any time if the Stop
button is pressed.
Controller Control Fault Logic
Alarm
Condition
Indication
Tank Low Level Low Level Alarm indicator light on
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Deviation
Temperature Deviation Alarm indicating light on
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Sensor Short
Circuit
Temperature display flashing
Alarm horn on and X1 output powered
Temperature
Sensor
Disconnected
Temperature display flashing
Alarm horn on and X1 output powered
Vacuum Option Cool-Down
(Vac units only)
With this option, the unit includes an internal
venture and bypass line and a modified version of
the automatic cool down function. This works
similarly; however, instead of turning the unit off
after the cool down is complete it will sound the
alarm horn to indicate the unit is ready to be put
into the vacuum mode and the pump remains on. To
initiate a vacuum cool-down, press the Temperature
Adjust button and release and then pressure the On
button. When activated the tank temperature
displays with a C in front of it indicating the
automatic cooling sequence is active. This sequence
will stop at any time if the Stop button is pressed.
Example of vacuum option automatic cooling, tank at 400°F
E
4 0 0
Содержание Oiltherm RO
Страница 1: ......
Страница 2: ......
Страница 18: ...14 Drawings Charts Figure 1 Pump Curve 60 Hz ...
Страница 19: ...15 Figure 2 Cooling Capacity ...
Страница 20: ...16 Figure 3 High Voltage Wiring Diagram ...
Страница 21: ...17 Figure 4 Low Voltage Wiring Diagram ...
Страница 22: ...18 Figure 5 Control Board Details ...
Страница 23: ...19 Figure 6 Heating Element Details ...
Страница 26: ...Notes ...
Страница 27: ......