52
Table 18 – ModBUS RTU Option Parameters (Integral Values) - continued
Reg
Description
Read/Write Notes
4011 LOW ALARM DELAY
R
4012 HI ALARM DELAY
R
4013 DISPLAY UNITS
R
0 = Deg F, 1 = Deg C
4014 CONTROLLER TYPE
R
0 = TCU, 1 = Chiller
4015 BROWNOUT ENABLED
R
0 = DISABLED, 1 = ENABLED
4016 AUTOTUNE ENABLED
R
0 = DISABLED, 1 = ENABLED
4017 SEAL SAVER ENABLED
R
0 = DISABLED, 1 = ENABLED
4018 REM HEAT COOL ENABLED
R
0 = DISABLED, 1 = ENABLED
4019 PURGE ENABLED
R
0 = DISABLED, 1 = ENABLED
4020 CRASH COOL ENABLED
R
0 = DISABLED, 1 = ENABLED
4021 FLOW ENABLED
R
0 = DISABLED, 1 = ENABLED
4022 NOT USED
X
4023 NOT USED
X
4024 REM SETPOINT ENABLED
R
0 = DISABLED, 1 = ENABLED
4025 AUTOSTART ENABLED
R
0 = DISABLED, 1 = ENABLED
4026 NOT USED
X
4027 COMM BAUD RATE
R/W
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600
4028 MODBUS ID
R/W
4029 CURRENTLY CONTROLLING
R
0 = NO, 1 = YES
4030 SPI ADDR
R/W
4031 MODICON FLOAT FORMAT
R
0 = NO, 1 = YES
4032 COMM TYPE
R/W
0 = NONE, 1 = MODBUS, 2 = SPI, 3 = PV REXMIT,4 = HAND HELD
DISPLAY
4033 COMP 2 ENABLED
R
0 = DISABLED, 1 = ENABLED
4034 HEAT COOL SWITCH DELAY
R
4035 DAC OUTPUT SPI0
R
16 bit value being sent to DAC card
4036 DAC OUTPUT SPI1
R
16 bit value being sent to DAC card
4037 DAC OUTPUT COMM
R
16 bit value being sent to DAC card
4038 PID OUT
R
-100 to 100 PID algorithm output
4039 MODBUS COMMAND
R/W
0 = Do Nothing, 1 = Start, 2 = Stop
4040 EXTENDED RANGE ENABLED
R
0 = DISABLED, 1 = ENABLED
ModBus Parity = None, Stop Bits = 1
Table 19 – ModBus RTU Option Parameters (Floating Point Values)
Reg
Description
Read/Write
Notes
8000 FREEZESTAT TEMPERATURE READING (°C)
R
Error Hi = 9.9E05, Error Low = -9.9E05
8002 SUPPLY WATER TEMPERATURE (°C)
R
Error Hi = 9.9E05, Error Low = -9.9E05
8004 RETURN WATER TEMPERATURE (°C)
R
Error Hi = 9.9E05, Error Low = -9.9E05
8006 N/A
R
Error Hi = 9.9E05, Error Low = -9.9E05
8008 N/A
R
8010 LOW DEVIATION (°C)
R/W
8012 HI DEVIATION (°C)
R/W
8014 LOW SETPOINT LIMIT (°C)
R
8016 HI SETPOINT LIMIT (°C)
R
8018 REXMIT RANGE LOW (°C)
R
8020 REXMIT RANGE HI (°C)
R
8022 LOW SAFETY TEMP USER (°C)
R/W
8024 HI SAFETY TEMP USER (°C)
R/W
8026 PROPORTIONAL BAND (°C)
R/W
Note: All temperatures are in °C regardless of unit display configuration.