1.  Safety 

Assembly and installation should only be carried 

out by a qualified electrician, somebody who has 

completed appropriate professional training and 

has the knowledge and experience necessary to be 

able to recognise and avoid the potential dangers 

posed by electricity.

Before assembly/dismounting, disconnect the 

power supply and ensure that the parts are no 

longer live.

Prior to commissioning and using the product, read 

and observe all the operating instructions.

 

Corresponds

 to type 1 BSTU in accordance with IEC/

 

EN 60730-2-7

 

Power reserve (6 years) is reduced when Bluetooth 

 

OBELISK top3 is connected (in battery mode)

2.  Proper use

 

Digital time switch with weekly program and 3 special 

programs

 

Interface for Bluetooth OBELISK top3 

 

Programming by app possible

 

The time switch is intended for time-controlled and 
manual switching of lights, fans etc.

 

Only for use in closed, dry rooms 

 

The time switch is designed for wall mounting (flush-
mounting) in an interior switch range

3.  Installation and connection

Flush-mounted installation

 

L

With a standard flush-mounting box (see illustration).

 

L

Observe the recommended installation height of  
0.8 m–1.2 m!

 

†

Disconnect power source.

 

†

Connect the time switch according to the wiring diagram.

 

†

Screw down the time switch in the flush-mounted box 

.

 

†

Position the bezel frame on the time switch 

1

2

Ø 60 mm

≥ 40 mm

N

L1

L

L

L1‘

L1

N

 

!

Secure device with an upstream type B or type C circuit 

breaker (EN 60898-1) with a maximum of 10.

Connecting the cable

45°

Spring plug-in 
terminal opener

 

†

Strip cable to 8 mm (max. 9).

 

†

Insert cable in the open DuoFix plug-in terminal at 

45°.

 

L

2 cables per terminal position possible.

 

†

To open the DuoFix plug-in terminal, press screwdriver 

downwards.

Disconnecting the cable

 

†

Use the screwdriver to push the spring plug-in terminal 

downwards.

4.  Device description

4 buttons to select the 

functions

Bluetooth OBELISK top3 

(9070130)

Bezel frame

Display

Right/left buttons (configured as pre-selection)

Содержание TR 030 top3 UP

Страница 1: ...ghts fans etc Only for use in closed dry rooms The time switch is designed for wall mounting flush mounting in an interior switch range 3 Installation and connection Flush mounted installation LWith a...

Страница 2: ...witch the light on and off or to control a fan etc Pressing the right left buttons changes the relay state in question and the pro gram performs the next switching operation Overview of navigation men...

Страница 3: ...e with until SAVE is displayed Confirm with OK Repeat all steps for the turn off time however instead of selecting ON with select OFF and enter 12 00 for hour and minute Changing switching times MENU...

Страница 4: ...urn off times switching time and short time pulses pulse cycle times cycle can also be programmed The pulse duration pulse pause is limited to 17 hrs 59 min 59 sec LCycle times are cyclically repetiti...

Страница 5: ...SPECIAL 1 u NEW DATE CHECK MODIFY DATE DELETE END Press MENU Select PROGRAM confirm with OK Select SPECIAL 1 confirm with OK ON 1 for turn on time is displayed Set required turn on time confirm with...

Страница 6: ...y card accessory 9070130 Copying OBELISK TIME SWITCH This copies the switching program and optionally all time switch settings e g time format etc from the memory card to the time switch Copying TIME...

Страница 7: ...5 C Power reserve 6 years at 20 C without Blue tooth OBELISK top3 Time accuracy typical 0 25 s day 25 C Rated impulse voltage 4 kV Pollution degree 2 Contact NO contact Incandescent lamp halogen lamp...

Отзывы: