3
L
The walking test can also be activated with theSenda P
and SendoPro 868-A remote controls, see chapter 7.
3 sec
6. Setting
The presence detector has 2 potentiometers for setting time
delay (TIME) and brightness switching value (LUX).
Setting the brightness switching value (LUX)
You can set different brightness values with the potentiome-
ter for the brightness switching value (LUX).
If you want to change the preset brightness
¾
Set the potentiometer to the desired brightness
(5 – 1000 lux = ).
or want a specific brightness value to be learned using the
teach-in function
¾
At the desired brightness, set the potentiometer to . The
LED flashes for 20 s, afterwards the measured brightness
value is accepted as the new brightness switching value.
¾
Leave the potentiometer at position .
Brightness measurement
The presence detector measures the surrounding brightness
below the detector. The installation location is the reference
point for the lighting level. If the brightness measurement is
deactivated by using the remote control, the switch contact
light only switches depending on presence (with SendoPro
868-A: brightness switching value set to «measurement off»
via the remote control; with theSenda P: button „Lux On“
activated).
L
The brightness measurement value is influenced by the
installation location, incidence of light, position of the
sun, weather conditions, the reflection properties of the
room, and the furniture. Therefore, the lux values are guide
values.
Setting the time delay (TIME)
If the presence detector detects no further movement, it swit-
ches off after the set time delay.
If you want to change the preset time
¾
Set the potentiometer to the desired time (30 s – 30 min).
If you want to use the pulse function (e.g. for a staircase light
timer switch)
¾
Set the potentiometer to . Presence detector for „stair-
case light timer switch“ operation is on for 0.5 s and off for
10 s
7. Settings with remote control
You can also make the settings with remote controls the-
Senda S, theSenda P, and Sendo Pro 868-A.
30
1
6
5
8
9
10
11
12
13
14
15
23
22
21
20
19
18
17
16
26
27
25
2
3
2
Off
On
L
If the command sent from the presence detector is accep-
ted, the red LED flashes briefly twice. If the command is
rejected, the red LED flashes briefly once.