Heater actuators - Series 

HMG 4
HME 4  

The heater actuators for the 

series

are as follows:

BMG 4

(4-chanel basic module) and 

HME 4

(4-channel upgrademodule)

for controlling the heating valves via silent triac outputs.

The heater actuators are suitable for use with the European Installation -
Bus 

EIB  

in combination with the 

t

product database. ETS

(EIB Tool Software) enables application programs to be selected, and spe-
cific parameters and addresses to be assigned and transferred to the
device.

A type BCU 2.1 bus coupling is integrated into the basic modules. A basic
module can be expanded simply by adding up to 2 upgrade modules.
Any combination of       -series modules is possible, e.g.

HMG 4 + HME 4 + HME 4

(12 x heating)

HMG 4 S + RME 4 S + RME 4 S

(4 x h 8 x 
switching)

RMG 4 C-Last + DME 2 + HME 2

(4 x C-load + 2 x dimming 
+ 4 x heating)

etc.

1.0  Designated use

The bus line must be routed, connected and installed in accordance with
the valid regulations to DIN-VDE and also the EIB Handbook and ZVEI/
ZVEH. The work may be carried out only by trained electricians qualified
to EIB.

Compliance with the national regulations and valid safety requirementsis
required. Tampering with or making modifications to the 
device will invalidate the warranty.

Please note:

• It is permitted to connect different phases in one device.

• It is possible to connect contactable protective low voltage, if all 4 

channels of a module switch protective low voltage.

• Switching protectors can be activated for controlling electric heaters,

for example.

3.0. Electrical connection

2.0  Description

309 321

1

2

6

3

4

5

HMG 4

Basic device

The device controls thermal actuators via silent and 
non-wearing triac outputs.

The heating output can be continuously adjusted 
as and when required. This is achieved by converting a continuous 
control variable into a PWM (pulse width modulation) output signal.

Example:

HME 4

Upgrade module

Manual selector switch permanently - ON / OFF – Bus 
operation

Manual switch in position:

The status of the triac is determined by the bus 
messages.

The triac is permanently 

switched on.

The triac is permanently 

switched off.

Please note: Manual switching can also be used in the event
of a bus voltage failure.

Connection for actuators HMG 4 and HME 4

7

1

4

7

3

6

8

2

5

L3

L2

L1

H1

H2

H3

H4

N

L

M

L1

N

N

HMG 4
1

LEDs

on = channels

H1 ... H4 

switched on

2

Programming key and LED for physical address

3

Bus connection: Ensure correct polarity!

4

Manual selector switch: e.g. Permanently On / Off or Bus

HME 4
5

Plug as connection between upgrade module and basic device

6

LEDs

on = channels

H1 ... H4 

switched on

7

Manual selector switch: e.g. Permanently On / Off or Bus

Aus

Ein

10 %

1 min.

10 min.

10 min.

5 min.

50 %

ON

OFF 