The heating actuator of type 

HMG 8 

is suitable for use with the European

Installation bus-

in connection with the 

t

-product database. It is

fitted with the BCU 2 for the bus communication.

Basic device HMG 8

•  8 heating outputs, each capable of handling up to 10 thermal actuators

Expansion units

•  

HME 8

8 additional heating outputs

• 

HMx 4

4 additional heating outputs

•  

RME 8

8 switching outputs

•  

RMX 4

4 switching outputs

•  

FME 8

8 window contact inputs with safety extra low voltage (SELV)

1.0  Use in accordance with the intended application

Both routing and connecting up the bus cable as well as installation work must be
carried out in accordance with the applicable regulations and guidelines of DIN-
VDE, as well as with the EIB Handbook from ZVEI/ZVEH. The work may only be
carried out by qualified electricians with appropriate EIB training. National norms
and the applicable safety regulations shall be observed. Any changes made to the
device will invalidate the guarantee.

2.0  Electrical connection

2.2  Thermal actuators HMG 8, HME 8

2.4 Switching outputs RME 8, RMX 4

2.1  Network connection

The heating module 

HMG 8

can be expanded by using max. 1 expansion module.

No new EIB programming is required when replacing a defective device.

Remove the strip of insulation of the right-hand side of the 

HMG 8 

device (fig. 1).
Keep the strip of insulation for further use by attaching underneath the  
opening for the plug-in contact.
Snap the modules 

HMG 8 

and the expansion module onto the multi-

terminal rail (fig. 2).
Push the module 

HMG 8

and the expansion module completely 

together (fig. 3).

Connection

Connect up the switch actuator in accordance with the circuit diagram 
shown in chapter 2.2.

Removal instructions

When moving the expansion module, always protect the opening of the
remaining actuator 

HMG 8

by covering with a strip of insulating tape!

2.6  Bus connection

4.0  Expansion modules

310 498

Klick

1.

2.

3.

JMG 4

RME 8

Behaviour without ETS programming

The connected expansion modules are detected and actuated.
•  

HME 8 and HMX 4

- Actuator behavior: when switched on, it is in heating mode.

- The output value is 50 %.

- Can be manually operated for testing purposes.

•  

RME 8 and RMX 4

- Relays stays off.

- Can be manually operated (manual ON/OFF)

•  

FME 8

- LED status display

•  

see also section 6.0

3.0  Behaviour during a power or an operational failure

Note concerning power failure

All relays - irrespective of their assigned parameters - drop during a power failure.
This means that the electric circuit is opened.

Note concerning a bus failure only

Provided power is still being supplied the relays can be switched from the device´s
keypad in the event the bus fails.

Operating Instructions for Heating Actuator

-

Heating actuator HMG 8 and expansion units
Heating modules HME 8 and HMX 4
Switching modules RME 8 and RMX 4
Window contact module FME 8

Each module must be connected to a standard main power source.

Connecting the expansion module

Be sure to use the same phase and fused circuit as used for the base module
supply voltage to the logic system (L-, N connections).

• Uin is for a commun voltage supply 

to the actuators (230 V~, same 
phase as for the actuators).

• It is galvanically isolated from the 

standard main power source so that
24 V~ thermal actuators can also 
be used.

6

7

4

5

~J

M

~J

M

Please note:

• Switching differently -phased external

conductors in one device is generally 
allowed.

refer to the product manual for:

=> Using contactors or relays when 

actuating in order to achieve 
higher switching capacities

=> Switching of savety extra low

voltage

L

N

3

1

2

2.5 Window contacts FME 8

• The COM ports provide an SELV 

for the window contacts.

• All COM ports are internally 

connected to each other.

4

2

3

COM

E2

E1

e.g. channel 1

Lighting connection

2.3 Thermal actuator HMX 4

• Uin 1 and Uin 2 are galvanically 

isolated from each other and the 
standard mains power source so 
that 24 V~ thermal actuators can 
also be used.

3

1

2

J

M

J

M

e.g. channel 1

Uin

24-250 V AC/DC

24-250 V AC/DC