background image

1

thePrema S360-100 E UP WH

2070600

thePrema S360-100 E UP GR 

2070601

307184

1103087901

Presence detector

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Square detection area 360° (up to 64 m

2

) for reliable and 

easy planning

 

Automatic presence- and brightness-dependent control for 

lighting and HVAC

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs 

 

Channel A light: relay, 230 V

 

Fully or semi-automatic operation, switchable

 

Brightness switching value configurable, teach-in function

 

Self-learning time delay

 

Reduction of time delay when present briefly (short-term 

presence)

 

Connection option for push buttons or switches for manual 

switching with automatic detection of «push button/

switch»

 

Pulse function for staircase light timer switch

 

Ready for immediate use due to factory presetting

 

Exceptionally easy configuration of the energy-saving res-

ponse with the new «eco plus» function

 

Test mode for checking function and detection area

 

Extension of detection area via master/slave or master/

master switching, a maximum of 10 detectors can be swit-

ched in parallel with each other

 

Ceiling installation in flush-mounted box

 

Surface mounting on ceilings possible with back box 

(option)

 

User remote control «theSenda S» (option)

 

Management remote control «SendoPro» (option)

 

Installation remote control «theSenda P» (option)

2.  Safety

Danger of death through electric shock or fire!

 

Installation should only be carried out by a quali-

fied electrician!

WARNING

 

Work on electrical systems may only be carried out by 
qualified electricians or by instructed persons under the 
guidance and supervision of a qualified electrician in 
accordance with the technical regulations applying to 
electricity! 

 

Comply with the country-specific safety regulations for 
work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated with any object, the guarantee lapses.

3.  Proper use

The presence detector is intended for interior installation. The 

presence detector is exclusively intended for the use as cont-

ractually agreed between the manufacturer and the user. Any 

other use is considered to be unacceptable. The manufacturer 

does not accept liability for any resulting damages.

4.  Operation

The presence detector is primarily used in offices and schools, 

as well as in homes, for easy and energy-efficient control 

of lighting and shading. The switch contact "light" switches 

lighting on with presence and insufficient brightness, and off 

with absence or sufficient brightness. The light can also be 

switched on/off manually using buttons or switches.

Function description

 Mixed light measurement 

 Presence detection

 Artificial light

 Push button for manual lighting control

 Incident daylight

Содержание 2070600

Страница 1: ...ement remote control SendoPro option Installation remote control theSenda P option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a quali fied electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with th...

Страница 2: ...hting switches on and off auto matically in fully automatic mode In semi automatic the lighting must always be switched on manually The lighting is switched off automatically Staircase light function The staircase light function can be set to room or corridor using the DIP switch or the SendoPro management remote control Lighting can be switched on and off manually at any time in the room position...

Страница 3: ...brightness switching value set to on via potentiometer or set to measurement off via the remote control Fenster Innen 2m Suitable lamps The presence detector is designed for the operation of fluore scent lamps compact fluorescent lamps halogen incande scent lamps and LEDs The maximum number of switchable lights is restricted due to the high inrush current levels of the EBs and LED drivers The use ...

Страница 4: ...n the master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePrema S360 100 E Slave thePrema P360 Slave E thePrema S360 Slave E Master master parallel switching for several lighting groups Several masters can be used in parallel switching setup Each master controls its lighting group according to its own bright ness measurements Delay times and b...

Страница 5: ... potentiometer values and DIP switch settings from a distance Settings of switch contact light channel A Potentiometer brightness switching value lux The required brightness switching value can be set via the lux potentiometer The setting range is around 10 to 1000 lux The factory pre setting is 300 lux Brightness switching values from 5 to 3000 lux can be set via the management remote control Acc...

Страница 6: ...A Can be changed SendoPro 868 A Can be changed theSenda P Short presence A Short term presence On Off x Energy saving mode Selection eco eco plus x x Configuration type Selection auto man x x x Staircase light function Selection Off On x Control input S Auto switch push button S push button O x Detection sensitivity Detection Sensitivity PIR value range in Increments x x Monitoring sensitivity red...

Страница 7: ...hanges are only sensible in strongly deviating situations Time delay A Value range Adjustable values with SendoPro 868 A manage ment remote control In the theSenda P installation remote control the following values are available 10 s 60 min 10 s 30 s 60 s 2 min 10 min 20 min 60 min Control for staircase light timer switch 0 5 s on 10 s off SendoPro 868 A theSenda P Pulse Button 1 Short term presen...

Страница 8: ...rightness value is accepted as brightness switching value A Values outside the permitted range will automatically be set to the appropriate limit value The control command teach in can be adopted with the SendoPro 868 A management remote control or with the theSenda P installation remote control via the button Factory settings The presence detector thePrema S360 100 E is supplied with the followin...

Страница 9: ...erated Detector stays permanently in the test phase Note Do not use a torch to switch the presence detec tor The adaptive light switching thresholds will be distorted Setting the light test mode via remote control The detector goes directly into test mode without the start up phase when setting the test mode with the remote control Test mode ends automatically after 10 min The detector performs a ...

Страница 10: ...from the power supply for 5 mins thermal fuse Error flashing 4 x per second Error in self test Device not properly functional Guarantee ThebenHTS presence detectors are manufactured with the utmost care and using state of the art technology and are quality tested ThebenHTS AG therefore guarantees perfect operation when used correctly Should a fault occur however ThebenHTS AG will fulfil the guaran...

Страница 11: ...oPro 868 A Item No 9070675 Details www theben de theSenda S Item No 9070911 Details www theben de theSenda P Item No 9070910 Details www theben de ThebenHTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch Addresses telephone numbers etc www theben hts ch ...