PlanoSpot 360 DALI-2 S DE manual
18
7.2
Settings via the DALI bus
All of the parameters* and control commands described above can also be set by the multi-
master application controller via the DALI bus. They are stored in the memory bank.
* Exceptions: "Brightness measurement value Int/2, Inn/3, Mid/4, Win/5" and "LED display – no short
address" parameters. These parameters cannot be transferred via the DALI bus (see table in section 7.1.1).
7.3
Status messages via the DALI bus
The "QUERY INPUT DEVICE ERROR" command can be used to query the error status of the
PlanoSpot 360 DALI-2 S (no response means no error):
Bit Name
Value
Measures
0 Checksum_Error_Info
1 = Yes
Return the PlanoSpot 360 DALI-2 S for repair
1 Reserve
1 = Yes
2 Checksum_Error_Parameter 1 = Yes Reset to factory settings
3 Kein_HTS_Code
1 = Yes
Return the PlanoSpot 360 DALI-2 S for repair
4 EEPROM_Error
1 = Yes
Return the PlanoSpot 360 DALI-2 S for repair
5 Checksum_Error_DALI
1 = Yes
Reset to DALI default values
6 Reserve
1 = Yes
7 instanceError
1 = Yes
Further queries are required, see below
In the event of instanceError, the "QUERY INSTANCE ERROR" command must be executed for
the "Occupancy sensor", "Light sensor" and "Button instance" instances:
-
If the "Occupancy sensor" instance returns an error notification: Return the PlanoSpot 360
DALI-2 S for repair.
-
If the "Light sensor" instance returns an error notification: Return the PlanoSpot 360 DALI-2
S for repair.
-
If the button instance returns an error notification: Check the remote control, push buttons.