Pagina 31 di 35
AD1100TE-STD.EN-00 - Subject to change without notice
TFT DryAir
Alarm menu
To access the alarms folder to see the type of alarm, press SET, with the UP and DW look for the word "AL", press SET to
display the initials of errors occurred, with the UP and DW you can scroll and see all alarms (if present). To return to the
initial display back by repeatedly pressing the ESC key.
ALARMS TABLE
CODE
Description
Action
Rearmament
tPF
Overload alarm of process fan
Deactivation unit
Manual
trF
Thermal alarm of reactivation and/or gear motor
Deactivation unit
Manual
tHF
Thermal alarm of reactivation and/or gear motor
Deactivation unit
Manual
rtSt
Alarm rotor is stationary
Deactivation unit
Manual
E01
Reactivation temperature probe error, failure or disconnection
Deactivation
reactivation
Manual
E02
Error temperature sensor pre-treatment, failure or disconnection
Deactivation pre-
treatment
Manual
E03
Error temperature probe post-treatment, failure or disconnection
Deactivation pre-
treatment
Manual
E04
Probe error relative / absolute humidity, dewpoint, failure or disconnection
Deactivation
reactivation
Manual
A01
Alarm configuration:
You have enabled the after-treatment without enabling the corresponding probe
(CF04> 0 and CF05 = 0).
No action
Automatic
A02
Alarm configuration:
You have enabled the display of the value of moisture without enabling the
corresponding probe (CF01=3 and
CF08 = 0).
No action
Automatic
A03
Alarm configuration:
You have enabled the display of the value of post-treatment without enabling the
corresponding probe (CF01 and CF05 = 7 = 0).
No action
Automatic
A04
Alarm configuration:
You have enabled the display of the value of pre-treatment without enabling the
corresponding probe (CF01=6 and CF03 = 0).
Nessuna azione
Automatico
A05
Alarm configuration:
You have enabled the display of the value of absolute humidity or dewpoint calculated
without enabling probes corresponding relative humidity and post-treatment (CF01 = 4
or 5 and CF05=0 and CF08 ≠ 1).
No action
Automatic
A06
Alarm configuration:
You have enabled the display of the value of absolute humidity or dewpoint calculated
without enabling probes corresponding relative humidity and post-treatment
(CF13 ≠ 0
e CF05 = 0 e CF08 ≠ 1).
No action
Automatic
A07
Alarm configuration:
It has been enabled in the control of reactivation mixed Steam/Water + Electrical and
control of Post-cooled / Reheating simultaneously. Condition impermissible (CF02> 7
and CF03 and CF14 ≠ 0 = OFF).
No action
Automatic
Software Version 1.5.0 (FW 412.20)