Start
PLLSTS[MCLKSTS]
= 1?
Yes
No
Device is operating in limp
mode. Take appropriate
action for your system.
Do not write to PLLCR.
Set PLL[MCLKOFF] = 0
to enable failed oscillator
detect logic.
If required,
PLLSTS [DIVSEL]
can now be changed.
Set new PLLCR value
Is
PLLSTS[PLLLOCKS]
= 1?
Continue to wait for PLL
to lock. This is important
for time-critical software.
Set PLLSTS[MCLKOFF] = 1
to disable failed oscillator
detect logic
No
Yes
PLLSTS[DIVSEL]
= 2 or 3?
No
Set PLLSTS[DIVSEL] = 0
Yes
Figure 1-24. PLLCR Change Procedure Flow Chart
System Control and Interrupts
SPRUH18I – JANUARY 2011 – REVISED JUNE 2022
TMS320x2806x Microcontrollers
77
Copyright © 2022 Texas Instruments Incorporated