Overcurrent in Discharge Protection
23
SLUUBD3D – September 2015 – Revised September 2018
Copyright © 2015–2018, Texas Instruments Incorporated
Protections
Class
Subclass
Name
Type
Min
Max
Default
Unit
Description
Protections
OCC
Threshold
I2
–32768
32767
6000
mA
Overcurrent in Charge trip
threshold
Protections
OCC
Delay
U1
0
255
6
s
Overcurrent in Charge trip
delay
Protections
OCC
Recovery
Threshold
I2
–32768
32767
–200
mA
Overcurrent in Charge
recovery threshold
Protections
OCC
Recovery
Delay
U1
0
255
5
s
Overcurrent in Charge
recovery delay
3.5
Overcurrent in Discharge Protection
The device has two independent overcurrent in discharge protections that can be set to different current
and delay thresholds to accommodate different load behaviors. See
for additional FET
action options.
Status
Condition
Action
Normal
Current()
>
OCD:Threshold
SafetyAlert()[OCDL]
= 0, if OCDL counter = 0
Alert
OCDL counter > 0
SafetyAlert()[OCDL]
= 1, Decrement OCDL counter by
one after each
OCD:Counter Dec Delay
period
Trip
Current()
continuous
≤
OCD:Threshold
for
OCD:Delay
duration
SafetyAlert()[OCD]
= 0
SafetyStatus()[OCD]
= 1
OperationStatus()[XDSG]
= 1
DSG FET is disabled.
Increment OCDL counter.
Latch
OCDL counter
≥
OCD:Latch Limit
SafetyAlert()[OCDL]
= 0
SafetyStatus()[OCDL]
= 1
OperationStatus()[XDSG]
= 1
DSG FET is disabled.
Recovery
[SafetyStatus()[OCD]
= 1 AND
Protection
Configuration:VAUXR
= 0
Current()
continuous
≥
OCD:Recovery Threshold
for OCD:Recovery Delay
time
SafetyStatus()[OCD]
= 0
OperationStatus()[XDSG]
= 0
Discharging is allowed.
Recovery
[SafetyStatus()[OCD]
= 1 AND
Protection
Configuration:VAUXR
= 1
Current()
continuous
≥
OCD:Recovery Threshold
for
OCD:Recovery Delay
time OR
VAUXVoltage()
≥
Power:Charger Present Threshold
SafetyStatus()[OCD]
= 0
OperationStatus()[XDSG]
= 0
Discharging is allowed.
Latch Reset
SafetyStatus()[OCDL]
= 1 for OCD: Reset Time
SafetyStatus()[OCDL]
= 0
Reset OCDL counter
OperationStatus()[XDSG]
= 0
DSG FET returns to normal if
SafetyStatus()[OCD]
= 0.
Class
Subclass
Name
Type
Min
Max
Default
Unit
Description
Protections
OCD
Threshold
I2
–32768
32767
–6000
mA
Overcurrent in Discharge trip threshold
Protections
OCD
Delay
U1
0
255
6
s
Overcurrent in Discharge trip delay
Protections
OCD
Recovery
Threshold
I2
–32768
32767
200
mA
Overcurrent in Discharge recovery threshold
Protections
OCD
Recovery
Delay
U1
0
255
5
s
Overcurrent in Discharge recovery delay
Protections
OCDL
Latch Limit
U1
0
255
0
counts
Overcurrent in Discharge latch limit
Protections
OCDL
Counter Dec
Delay
U1
0
255
10
s
Overcurrent in Discharge counter decrement
delay
Protections
OCDL
Reset
U1
0
255
15
s
Overcurrent in Discharge latch reset delay