Tesco 6330 Скачать руководство пользователя страница 1

 

 

 

 

 

 

 

 

  
 
 
 
 
 
 
 
 

METER SITE 

ANALYZER 

PRODUCT: 

CATALOG NO. 6330

OPERATIONS 

MANUAL 

 

Содержание 6330

Страница 1: ...METER SITE ANALYZER PRODUCT CATALOG NO 6330 OPERATIONS MANUAL ...

Страница 2: ...ESCO The Eastern Specialty Company All Rights Reserved Specifications are subject to change without prior notice Revision 1 0 TESCO The Eastern Specialty Company 925 Canal Street Bristol PA 19007 Phone 215 228 0500 support tescometering com www tescometering com ...

Страница 3: ...nd the purchaser s sole remedy under this Warranty is limited to repair or replacement at TESCO s option free of charge F O B TESCO s factory at Bristol PA of any workmanship and or part which in TESCO s sole judgment displays evidence of defect On site Warranty repairs will be made when in TESCO s judgment the PRODUCT cannot practically be shipped to TESCO s factory Any modifications additions or...

Страница 4: ... 5 The defective PRODUCT or part is returned in the original packing or packing approved by TESCO TESCO is not responsible for drayage charges damages or labor costs incurred in conjunction with failure removal or reinstallation of any PRODUCT all of which shall be at the purchaser s expense TESCO is not responsible for special incidental or consequential damages whether resulting from breach of w...

Страница 5: ... 5 Optional Accessories 5 1 6 General Specifications 5 1 6 1 Input Characteristics 5 1 6 2 Dimensions 5 1 6 3 Accuracy 5 1 7 About this Operations Manual 6 2 0 SETUP 6 2 1 Introduction 7 2 2 Unpacking and Inspection 7 2 3 Setup Airflow and Cooling Considerations 7 2 3 1 Setup and Placement 7 2 4 Main Power Supply 7 3 0 FUNCTIONALITIES 8 3 1 Introduction 10 3 2 Panel Features 10 3 2 1 Front Panel S...

Страница 6: ...st Results 31 3 3 2 3f Data Library 31 3 3 2 3g Test Sequences 32 3 3 2 4 Preferences 33 3 3 2 4a Network Security Options 34 3 3 2 4b Colors Beepers Options 34 3 3 2 4c General Options 35 3 3 2 4d Testing Options 35 3 3 2 5 System Information 36 3 3 2 5a User 36 3 3 2 5b Temperature 37 3 3 2 5c Configuration 37 3 3 2 5d Serial Numbers 38 3 3 2 5e Software Versions 38 3 3 3 Fast Access Functions 1...

Страница 7: ...cometering com 1 215 228 0500 support tescometering com v TABLE OF CONTENTS 5 0 MAINTENANCE 40 5 1 Introduction 41 5 2 Cleaning the Instrument External Surface 41 5 3 Repair Parts Replacement Recalibration 41 ...

Страница 8: ...General Safety Summary 3 1 4 Description of Safety related Icons 3 1 5 Product Features 4 1 5 1 Key Features 4 1 5 2 Standard Features 4 1 5 3 Standard Unit 4 1 5 4 Additional Items 4 1 5 5 Optional Accessories 5 1 6 General Specifications 5 1 6 1 Input Characteristics 5 1 6 2 Dimensions 5 1 6 3 Accuracy 5 1 7 About this Operations Manual 6 ...

Страница 9: ...e and complete tool for testing the entire functionality of transformer rated metering installation in a convenient portable and lightweight kit It can perform CT Testing Ratio Burden Only Admittance Demagnetization Demand Testing Customer Load or Phantom Load Testing 5 amp Current Load Box and more It has a database for storing test results that you can export to your PC Since 1904 customers have...

Страница 10: ...d actions that may damage the Site Analyzer or the test equipment WARNING To avoid electrical shock personal injury or fire hazard The device must not be switched ON if it is damaged or suspected to be faulty Do not operate the device in wet condensing dusty or explosive gas conditions If the equipment is used in a manner not specified in this manual the protection provided by the Site Analyzer ma...

Страница 11: ...able on direct sunlight ETHERNET CONNECTIVITY 100 BaseT with support for Web Services Remote Control Database Access 7 RJ45 standard blue and crossover red cables are provided INTEGRATED CONTROL KEYPAD The keypad is embedded in the front panel LOAD BOX True three phase with current of 0 5A with full harmonics 1 5 3 Standard Unit These are the standard items included in the package 6330 TESCO Meter...

Страница 12: ... Supply Frequency 50 60Hz Power Supply Adaptor Output 19VDC 4 74A Power 90W Max 1 6 2 Dimensions PARAMETERS DATA Height Lid closed 6 7 17 01 cm Width 13 9 35 30 cm Depth 18 2 46 22 cm Weight 17 8 lbs 8 07 kg 1 6 3 Accuracy PARAMETERS DATA Voltage Measurement Accuracy 0 02 Current Measurement Accuracy 0 02 Phase 0 005 degrees Power Measurements Accuracy Watts VA VAR 0 04 0 02 typical Energy Measure...

Страница 13: ...ut this Operations Manual This manual provides complete information for setting up and operating the Site Analyzer This document instructs the user on the following operations of the CAT 6330 Setup Front Panel Features Graphical User Interface GUI How to perform tests Instrument Maintenance ...

Страница 14: ...1 215 228 0500 www tescometering com support tescometering com 2 0 SETUP 2 1 Introduction 7 2 2 Unpacking and Inspection 7 2 3 Setup Airflow and Cooling Considerations 7 2 3 1 Setup and Placement 7 2 4 Main Power Supply 7 ...

Страница 15: ...d portable unit that you can easily adapt to your surroundings on a site or inside the shop The long cords allow for the placement for a Site Analyzer to be as close or as far from the site as possible Make sure to lay the Site Analyzer flat when using and make sure there is proper ventilation for the fans on the side 2 4 Main Power Supply The Site Analyzer is fully battery powered and the battery...

Страница 16: ...e 16 3 3 2 1a Meter Test 17 3 3 3 1b CT Testing 20 3 3 3 1c Pulse Alignment Check 24 3 3 2 2 Sequence Testing 25 3 3 2 3 Database 26 3 3 2 3a New Edit Site 27 3 3 2 3b New Edit Meter 28 3 3 2 3c New Edit CT 29 3 3 2 3d New Edit Customer 30 3 3 2 3e Test Results 31 3 3 2 3f Data Library 31 3 3 2 3g Test Sequences 32 3 3 2 4 Preferences 33 3 3 2 4a Network Security Options 34 3 3 2 4b Colors Beepers...

Страница 17: ...00 support tescometering com 9 FUNCTIONALITY 3 3 2 5c Configuration 37 3 3 2 5d Serial Numbers 38 3 3 2 5e Software Versions 38 3 3 3 Fast Access Functions 13 3 3 3a Metrology 13 3 3 3b Phasors 14 3 3 3c Waveforms 14 3 3 3d Harmonics 15 ...

Страница 18: ...d this information before operating the Site Analyzer Front panel operating instructions for the Site Analyzer are provided in this chapter 3 2 Panel Features Front panel features controls displays indicators and side panel sections terminals are shown in Figure 3 2 1 and Figure 3 2 2 respectively 3 2 1 Front Panel NUMBER DESCRIPTION 1 LCD screen 2 Function keys 3 Keypad 4 Fast access keys 5 Power...

Страница 19: ...s the focus from one section of the screen to another Displays many of the metrology values in tabular form Displays a phasor diagram for the active phases Diagram is continuously updated Displays live waveforms Displays harmonic analysis up to the 50th Deletes the previous character NUMBER DESCRIPTION 1 Rogowski Current Probe Terminals 2 Fused Voltage Lead Terminals 3 Current Cable Terminal 4 Bat...

Страница 20: ... field or button that is grayed out cannot be changed or accessed by the user STATUS BAR ICONS These icons are located at the status bar of the screen They are indicators of different network connections and temperature levels of the device ICON NAME DESCRIPTION Wired Connection LAN Ethernet connection is enabled The number represents the number of users remotely connected to the device Extremely ...

Страница 21: ... of the metrology values in tabular form If no test is in progress then the TREND PLOT and RECORD functions are available The SEL column is used to select which parameters are used in a TREND PLOT or WAVEFORM RECORDING Use the arrow keys to navigate through each of the parameter and press ENTER to select deselect NOTE The phase colors were changed in 3 3 2 4b Colors Beepers Options FUNCTION KEYS S...

Страница 22: ...ary reading Freeze the data acquisition Change to showing live data 3 3 2c Waveforms SCREEN DESCRIPTION Displays live waveforms with recording functionality NOTE The phase colors were changed in 3 3 2 4b Colors Beepers Options KEYPAD FUNCTION KEYS Hide or show the voltage waveforms Hide or show the current waveforms Select the number of cycles to be displayed 1 2 4 8 Shift between ALL Phase A Phas...

Страница 23: ... The phase colors were changed in 3 3 2 4b Colors Beepers Options KEYPAD FUNCTION KEYS Change Y axis from linear to log scale Show the 1st harmonic fundamental so that the display can auto scale to show more vertical detail Hide the 1st harmonic fundamental Change from a Columns display to a Points display Change from a Points display to a Columns display Column mode Shift between Va Vb Vc Ia Ib I...

Страница 24: ...ration FORM Meter form will be loaded automatically if site is selected SERVICE Services wiring configurations available for selected meter form This will be loaded automatically if a site is selected 3 3 3 1 Manual Mode SCREEN DESCRIPTION Manual Mode allows testing without specifying a site or test sequence If a site was selected on the MAIN MENU then the information on this screen will automatic...

Страница 25: ...signal and the current signals from both the potential and the current transformers 2 FL TA Load box provided current of TA at PF 1 0 is used 3 LL 10 TA Load box provided current of 10 TA at PF 1 0 is used 4 PF TA 0 5PF LAG Load box provided current of TA at PF 0 5 lagging is used TEST TYPE PARAMETERS A ACCURACY TEST Perform this test to determine a meter s accuracy under one or more load conditio...

Страница 26: ...r s registration using the difference of the two values Note Use caution that the accuracy of the test is not limited by the resolution of the meter readout PARAMETERS TEST DURATION Set the test duration ITERATIONS Number of times the test will be repeated TOLERANCE Tolerance used for pass fail criteria WARM UP TIME Time for meter to stabilize prior to test execution D DEMAND TEST The demand inter...

Страница 27: ... METER TEST SETUP when performing MANUAL TEST TEST SEQUENCE SETUP when performing SEQUENCE TEST Return to the MANUAL METER TEST screen TEST PARAMETERS TAG Alias or brief description of the test ITERATION Number of test iteration TEST STATUS Indicates test type PULSES Preset Pre defined number of pulses Actual Counted pulses during test Remaining Remaining pulses during and after test TEST RESULTS ...

Страница 28: ...e error This test does require a current probe such as a Rogowski coil connected to the primary of the transformer ADMITTANCE An admittance test injects a 1575 Hz signal into the secondary of a CT and measures the response to determine the admittance of the CT The value you measure depends somewhat on the primary wiring and circuit characteristics However these effects do not generally change over...

Страница 29: ...y Secondary current is below the minimum current for the accuracy class Accuracy is not specified in this region Pass Fail will be determined using the lowest accuracy for the class Measured current is in the high accuracy portion of the specification Measured current is in the low accuracy portion of the specification Typically twice the uncertainty of the high accuracy region CT BURDEN ONLY Test...

Страница 30: ...curacy class KEYPAD FUNCTION KEYS Shift between different display modes Either one CT at a time or multiple CTs Only the available CTs are shown Allows the user to override the values of Accuracy Class and Burden Class provided in the setup screen Return to CT Test Setup CT RATIO WITH BURDEN This test is performed just like the burden only test except the ratio of primary to secondary current time...

Страница 31: ...e of accuracy class ADMITTANCE TEST An admittance test injects a signal into the secondary of a CT and measures the response to determine the admittance of the CT The user can manually PASS FAIL a CT based on the user s standard KEYPAD FUNCTION KEYS Shift between different display modes Either one CT at a time or multiple CTs Only the available CTs are shown Show numerical actual data Manually PAS...

Страница 32: ...ent display modes Either one CT at a time or multiple CTs Only the available CTs are shown Show numerical actual data Return to previous screen 3 3 3 1c Pulse Alignment Check SCREEN DESCRIPTION This will apply voltage and current to the meter so that the optical probe can be aligned with the meter s pulse output Before performing a pulse alignment check make sure that the optical pickup 1037 SA is...

Страница 33: ...xes on this form are read only except SEQUENCE and the ENA fields SEQUENCE NAME Sequences available for selected meter form and service TOLERANCE Tolerance for the pass or fail criteria TA Test amps RMS of a full load test SERVICE Services wiring configurations available for selected meter form ENA Toggle to select or deselect a test TAG Alias or brief description of the test TEST DESCRIPTION Type...

Страница 34: ...ustomer Edit information of a site meter CT and customer This will be enabled once a site is selected View test results on meter CT and PT tests This will be enabled once a site is selected View Create Edit information on meter CT and PT Press to return to the previous screen DATA SEARCH SITE Enter characters to search for a site SITE ID ID of site SITE NAME Name of site DESCRIPTION Description ab...

Страница 35: ...Site Analyzer Save site information Press to return to the previous screen DATA SITE ID ID of site SITE NAME Name of site DESCRIPTION Description about site CUSTOMER Choose customer ADDRESS 1 Location of site ADDRESS 2 Location of site CITY City where site is located STATE PROVINCE State Province where site is located ZIPCODE Zip code of the local address COUNTRY Country where site is located GPS ...

Страница 36: ...rial number of communication device if applicable FORM Form number of the meter auto populates the default Kh in the Kh field BASE Meter base S K A etc CLASS Meter class determines maximum current and auto populates the default test amps in TA field TA Test Amps RMS of a full load test Kh Meter Constant Watt hours per revolution of disk Kt Meter Test Constant Watt hours per pulse Kt Kh Pulses per ...

Страница 37: ...NFO screen to create or edit a site Copy information except serial number from CT 1 to other CTs Press to return to the previous screen DATA SERIAL NO Serial number of the meter MANUFACTURER Manufacturer s name MODEL Model number of the meter NAMEPLATE RATIO Ratio of primary to secondary current RATING FACTOR Rating factor of the CT ACCURACY CLASS Accuracy class of the CT MAX TEST BURDEN Maximum a...

Страница 38: ...FUNCTION KEYS Open the NEW SITE INFO screen Edit existing customer information Information that are grayed out will be enabled for editing Cancel editing the existing customer s information Delete existing customer s information This will be enabled once a customer is selected Save changes made to existing or new customer s information Press to return to the previous screen DATA CUSTOMER NAME Name...

Страница 39: ...ay modes Either show all test results or filter by meter or CT tests View details of selected test result Return to the SITE INFORMATION DATABASE screen Press to return to the previous screen 3 3 3 3f Data Library SCREEN DESCRIPTION TBA KEYPAD FUNCTION KEYS Shift between displaying Meter CT and PT data library Add a data library Edit a data library item This will be enabled if a data item is selec...

Страница 40: ...ww tescometering com support tescometering com SCREEN DESCRIPTION Create a new meter library KEYPAD FUNCTION KEYS Save new meter library Return to the METER LIBRARY screen Press to return to the previous screen SAVE BACK ADD METER LIBRARY ...

Страница 41: ...DESCRIPTION Change or update the options and settings for the device KEYPAD FUNCTION KEYS Select method of assigning IP address Change phase color assignments Adjust screen brightness options Set global testing options Press to return to the previous screen TO BE REPLACED NETWORK COLORS BEEPER GENERAL TESTING PREFERENCES NETWORK SECURITY OPTIONS COLORS BEEPER OPTIONS GENERAL OPTIONS TESTING OPTION...

Страница 42: ...rn to the previous screen DATA IP ADDRESS DHCP Select for IP address assigned by the network STATIC Select for IP address specified by the user 3 3 3 4b Colors Beepers Options SCREEN DESCRIPTION Choose colors for displaying each phase s data in the system All phase color coding and plots are affected KEYPAD FUNCTION KEYS Save the changes made on the colors beeper settings Press to return to the pr...

Страница 43: ...el will be disabled 3 3 3 4d Testing Options SCREEN DESCRIPTION Set an option whether to define a delay between tests in a sequence wait until a user presses continue or have no delay at all and have the succeeding test execute immediately The user can also set the default defined limits for CT testing KEYPAD FUNCTION KEYS Save the changes made on the testing options This will be enabled once ther...

Страница 44: ...3 5a User SCREEN DESCRIPTION This contains the user information date and time where the user can change these settings when necessary KEYPAD FUNCTION KEYS Edit user information and time and date settings Lock all information from editing This is enabled when the EDIT button is pressed Save changes made on the user information and date and time settings Press to return to the previous screen DATA U...

Страница 45: ... C Default temperature is in Fahrenheit F Press to return to the previous screen 3 3 3 5c Configuration SCREEN DESCRIPTION This contains the information on the standard and load box DATA LOAD BOX INFO MAX CURRENT Maximum current for the load box MIN CURRENT Minimum current for the load box MAX FREQ Maximum frequency for the load box MIN FREQ Minimum frequency for the load box THERMAL CUTOFF Therma...

Страница 46: ...en 3 3 3 5e Software Versions SCREEN DESCRIPTION This contains the information on the Linux operating system DATA FIRMWARE VERSION Firmware version of the software LINUX KERNEL VERSION Linux kernel version of the software MAIN BOARD FPGA SW VERSION Software version of the FPGA main board CT BOARD FPGA SW VERSION Software version of the FPGA CT board DB SCHEMA VERSION Database version HW VERSION Ha...

Страница 47: ...www tescometering com 1 215 228 0500 support tescometering com 39 FUNCTIONALITY 4 0 CONFIGURATIONS 4 1 Meter Test 40 4 2 CT Test 40 4 3 Sequence Test 42 ...

Страница 48: ...reen 3 Once everything is set press START to start the test 4 Depending on the test type a pop up will appear to ask the user to enter a certain value For example in the Demand Test a user will be asked to enter the meter s demand register kW to continue with the test 5 The test will end with the test results shown 4 1 1 Demand Test SCREEN DESCRIPTION HOW TO PERFORM DEMAND METER TEST 1 Press START...

Страница 49: ... information If all CTs have the same information press COPY 1 TO ALL to copy the information except serial number from CT 1 to the other CTs 3 If a site was selected the fields will be automatically filled in 4 Optional Demagnetize the CTs by pressing DEMAG This will perform Demag Test to return the CT accuracy to its normal state 5 Once everything is set press START to start the CT Test 6 Live r...

Страница 50: ...configure This is only available for meter tests 6 When everything is set press RUN to start the sequence test This will show the live reading of the results for the first test in the sequence which in this case is Site Scan 7 Once the test is completed press CONTINUE to proceed to the next test in the sequence Note This setting can be changed refer to section 3 3 3 4d Testing Options where the se...

Страница 51: ...IONS MANUAL 40 1 215 228 0500 www tescometering com support tescometering com 5 0 MAINTENANCE 5 1 Introduction 41 5 2 Cleaning the Instrument External Surface 41 5 3 Repair Parts Replacement Recalibration 41 ...

Страница 52: ...ter or a non abrasive mild cleaning solution that is not harmful to plastics CAUTION Do not use hydrocarbons or chlorinated solvents for cleaning They can damage the plastic materials used in the Site Analyzer 5 3 Repair Parts Replacement Recalibration For the Site Analyzer s repair parts replacement and recalibration directly contact TESCO through phone or email See section 1 2 Contacting TESCO f...