Terra Universal Smart WhisperFlow Скачать руководство пользователя страница 1

 

 

ECM

 

Fan/Filter Unit

       

Installation and Operation Manual    

Doc. 1788-14

 

© 

Copyright 2018 Terra Universal Inc.   

All rights reserved 

Revised November 2019 

 

 

Terra Universal, Inc.  •  TerraUniversal.com  •  800 S. Raymond Ave.  •  Fullerton, CA  92831  •  TEL: (714) 578-6000  •  FAX: (714) 578-6020 

1

 

IMPORTANT SAFETY INSTRUCTIONS 

 

READ AND SAVE THESE INSTRUCTIONS 

Proprietary Notice

 

This manual pertains to proprietary 

devices manufactured by Terra 

Universal, Inc. Neither this 

document nor any portion of it may 

be reproduced in any way without 

prior written permission from Terra 

Universal.

 

Safety Notice

 

A thorough familiarity with all operating guidelines is 

essential to safe operation of the product.  Failure to 

observe safety precautions could result in poor 

performance, damage to the system or other 

property, or serious bodily injury or death. The 

following symbols are intended to call your attention 

to two levels of hazard involved in operation.

 

Terra Universal makes no 

warranties applying to information 

contained in this manual or its 

suitability for any implied or inferred 

purpose.  Terra Universal shall not 

be held liable for any errors this 

manual contains or for any 

damages that result from its use. 

 

CAUTION

 

Cautions are used when failure 

to observe instructions could 

result in significant damage to 

equipment.

 

 

WARNING

 

Warnings are used when failure 

to observe instructions or 

precautions could result in 

injury or death.

 

The information presented here is subject to change without notice.

 

 

1.0

 

Introduction 

 

This manual documents the operational guidelines for 

Terra Universal’s Smart  

WhisperFlow™ EC (Electronically Commutated) Motor Fan/Filter Unit

.  

 

The Smart  WhisperFlow™ ECM FFU provides uniform, laminar flow HEPA-filtered air 

to the area below the mounted unit.  This unit incorporates Whisperflow™ advanced 

baffling technology to reduce noise and ensure uniform airflow. 

 

The Smart  WhisperFlow™ ECM Fan/Filter Unit uses an integrated control module 

referred to in this manual as the EC Motor Control Card.  The Control Card features can 

be accessed at the EC Motor Control panel located on the motor housing, above the 

HEPA filter housing. 

 

1.1  Fan/Filter Unit Specifications 

 

FFU Specifications 

Size Options 

Standard FFUs: 2’x4’, 2’x3’, 2’x2’ 

Narrow FFUs: 1.3’x4’, 1.3’x3’, 1.3’x2’ 

Housing 

White powder-coated cold-rolled steel or 304 stainless steel 

HEPA Filter 

99.99% efficient on removal of particles 0.3 microns and larger 

Pre-Filter 

20” x 20” x 1” – 30% efficient ASHRAE rated 

Impeller 

Forward-curved centrifugal type factory balanced. Entire 

motor/blower assembly is removable from top of housing for service 

Face Grille 

Perforated anodized aluminum or 304 stainless steel 

Velocity 

90 FPM or higher 

Noise Level 

50 dBA (measured at 30” from filter face) 

Weight 

76 lbs. shipping weight 

Power Options 

1/3 HP motor; 120V/1/60Hz, 4.2 Amps 

220V/1/60Hz or 240V/1/50Hz, 2.7 Amps 

 

Specification Notes: 

•         All FFU data is based on a standalone unit using 1” prefilter and clean filters.  

•         Data will vary depending on filter media and configurations with other 

products/systems, such as ductwork or hoods. 

 

2.0

 

Operation 

 

The unit consists of a 1/3-HP electronically commutative motor driving a forward-curved 

centrifugal impeller.  Air is drawn into the unit through a pleated pre-filter and in turn to 

an insulated chamber where it is then directed to an exit HEPA filter with a built-in 

diffuser. 

 

The unit can also be equipped with a 3/8”-diameter challenge port, which can be used to 

take differential pressure measurements to monitor filter performance or insert aerosols 

for leak-test certification.  Port is capped when not in use. 

 

3.0

 

Installation 

 

The Fan/Filter Unit is designed to fit on top of a Terra standard 2’ x 4’ clean room ceiling 

grid. It includes a threaded fixture at each corner to accommodate four eye-bolts (not 

provided) that can be used to assist in positioning the unit. 

 

WARNING: To reduce the risk of fire, electric shock, or injury to persons, 

observe the following: 

 

A)

 

Use this unit only in the manner intended by the manufacturer. If you have 

questions, contact the manufacturer. 

B)

 

Before servicing or cleaning unit, or replacing a filter, switch power OFF at the 

service panel and lock the service disconnecting means to prevent power from 

being accidentally switched on. When the service disconnecting means cannot be 

locked, securely fasten a prominent warning device, such as a tag, to the service 

panel. 

C)

 

When the removal/disconnection of either filter is required due to service or 

component replacement, the replacements are to be remounted as previously 

installed. 

D)

 

Installation work and electrical wiring must be done by qualified person(s) in 

accordance with all applicable codes and standards, including fire-rated 

construction. All metal components must be properly grounded. 

E)

 

When cutting or drilling into a wall or ceiling, do not damage electrical wiring and 

other hidden utilities. 

 

4.0

 

Initial Start-up 

 

WARNING: Keep unit disconnected from power supply during inspection. 

 

Prior to providing power to the unit, check that no damage has occurred during shipping. 

This can be accomplished via a visual check to make sure there are no visible dents or 

penetrations. If the unit is intact, remove the pre-filter and fan guard screen. 

 

Manually rotate the fan wheel to make sure it is not in contact with any stationary parts 

and that there are no visible loose screws or bolts obstructing the wheel’s rotation.  

After installation, with power applied, the fan will rotate and filtered air will exit the HEPA 

filter. 

 

5.0

 

Cleaning and Maintenance 

 

WARNING: Disconnect from power supply before servicing unit or replacing 

filters. When servicing or replacing either filter, the new filter is to be 

installed in the same manner as the filter it replaces. 

 

The scheduled maintenance of the unit depends on the installed location and consists of 

cleaning or changing the pre-filter and the HEPA filter. It is recommended that the pre-

filter be inspected and cleaned every three months or sooner depending on the 

cleanliness of the external environment. The HEPA filter cannot be cleaned and must be 

replaced when the air velocity falls below 70 feet/min. 

 

Changing the HEPA filter requires removal of the unit from the ceiling grid. Place the 

unit on a flat work surface and remove the 10 sheet metal screws that hold the HEPA 

filter to the case.  Replace the filter with a new one and secure it to the case with the 

same screws before placing it back onto the ceiling grid. 

Содержание Smart WhisperFlow

Страница 1: ...mutative motor driving a forward curved centrifugal impeller Air is drawn into the unit through a pleated pre filter and in turn to an insulated chamber where it is then directed to an exit HEPA filter with a built in diffuser The unit can also be equipped with a 3 8 diameter challenge port which can be used to take differential pressure measurements to monitor filter performance or insert aerosol...

Страница 2: ...sure air flow and particle counts The EC Motor Control panel provides access to LED diagnostics manual speed adjustment test probe jacks CAT5e ports the Control Mode DIP Switch and the MODBUS Address DIP Switch Bank EC Motor Control Card Operating Temperature 0 40 C Open frame PCB with standoffs Panel mounted 12 24V DC Power Supply or network power Two non directional CAT5e RJ45 connections for ne...

Страница 3: ... Bank S1 SWITCH 1 ON SWITCH 2 OFF Network Control Mode DIP Switch Bank S1 SWITCH 1 OFF SWITCH 2 ON Closed Loop Feedback Network Control Mode DIP Switch Bank S1 SWITCH 1 ON SWITCH 2 ON Example Addresses in Network Mode MODBUS Address Value 1 DIP Switch Bank S2 SWITCH 1 ON MODBUS Address Value 21 DIP Switch Bank S2 SWITCHES 1 3 5 ON NOTE Address zero should not be used as it is reserved for global c...

Страница 4: ...Alone Operation Power Source Ratings Supply Transformer Voltage Rating 12 24V AC Supply Transformer Power Rating 2 VA Regulated DC Supply Voltage Rating 14 30V DC Regulated DC Supply Power Rating 2 W Extended Accessory Output Currents for Stated Input Voltage Condition Input Voltage Accessory Current DC mA2 Suggested AC DC Source Power Rating 5V 10V V RFU VA 14V DC Regulated 300 300 500 20 20 30 3...

Страница 5: ...parately For Terra s Policy and Procedures for Returning Goods see Terra s Internet site www TerraUniversal com Generally customers can improve the chance of collecting on a freight claim by following these procedures 1 formally requesting that the carrier inspect the shipment immediately upon suspecting damage or shortage to verify condition 2 notifying the carrier upon discovery of concealed dam...

Отзывы: