NSVM, NSVMN

 

  

  5      

 

 

 

 

 

7.2 Others (Only for NSVM, NSVMN 25L, 25, 32 series)

 

Ø

 

For these pumps, it is advisable to open the bypass 
valve during start-up. The bypass valve connects 
the suction and discharge sides of the            
pump, thus making the filling procedure easier. 
When the operation is stable, the bypass valve can 
be closed. 

Ø

 

If the pumped liquids contains air, it is advisable to 
leave the bypass valve open if the operating pressure 
is lower than 85.32 PSI. If the operating pressure constantly 
exceeds 85.32 PSI, the bypass valve must be closed. 
Otherwise the material at the opening will be worn because 
of the high liquid velocity. 

 

 

 

 

Содержание NSVM 25 Series

Страница 1: ...Installation Operating Manual VERTICAL MULTI STAGE CENTRIFUGAL PUMP NSVM NSVMN...

Страница 2: ......

Страница 3: ...and applications 3 Applications NSVM NSVMN series in line pumps booster pumps are designed for a wide range of applications in various industries for water treatment water boosting water supply coolin...

Страница 4: ...H ft 0 500 1 000 1 500 2 000 2 500 3 000 KH ft 0 1 804 3 608 5 412 7 216 9 02 10 824 Hst Safety margin minimum 2 ft head NPSHA NPSHR Pump running will be fine NPSHA NPSHR The pump will be dry running...

Страница 5: ...pump follow the installation examples in order to avoid damaging the pump Pos Description 1 Pipe support Support piping system properly to avoid stresses on connections 2 On off valves Install on off...

Страница 6: ...d well insulated Overload protection should be provided To connect proceed as shown on the inside of the terminal board cover The terminal box can be turned to four positions Check the direction of ro...

Страница 7: ...hus making the filling procedure easier When the operation is stable the bypass valve can be closed If the pumped liquids contains air it is advisable to leave the bypass valve open if the operating p...

Страница 8: ...s operating limits Check the operating conditions of the pump b The control panel is situated in an excessively heated area or is exposed to direct sunlight Protect the control panel from heat sources...

Страница 9: ...ove the operating conditions of the pump suction conditions head flow resistance liquid temperature viscosity etc b Make sure that pump and motor shafts are properly aligned Adjust the pump and or mot...

Страница 10: ...NSVM NSVMN 8...

Страница 11: ...NSVM NSVMN 9...

Страница 12: ...NSVM NSVMN 10...

Страница 13: ...NSVM NSVMN 11 NSVM N 25L 25 32 Coupling adjustments...

Страница 14: ...NSVM NSVMN 12 NSVM N 40 50 50B Coupling adjustments...

Страница 15: ......

Страница 16: ...TED Room 1001 10 F Olympia Plaza 255 King s Road North Point Hong Kong Tel 852 2571 0282 Fax 852 2571 0619 E mail sales teralasia com TERAL INC Head O ce 230 Moriwaki Miyuki cho Fukuyama city Hiroshim...

Отзывы: