Содержание TCW260

Страница 1: ......

Страница 2: ...monitoring general for general monitoring and cumulative for energy volume etc monitoring The user can also arrange up to 24 independent alarms with 5 different user selectable states Every alarm can...

Страница 3: ...include Energy analysis and optimization Water consumption analysis Gas consumption optimization A building management system Industrial processes monitoring General SCADA systems 4 Specifications Ph...

Страница 4: ...Installation consists of mounting the device connecting to an IP network connecting inputs and outputs providing power and configuring via a web browser 6 1 Mounting TCW260 should be mounted in a clea...

Страница 5: ...negative GND Pin8 SGND Connector 4 Pin1 S04 SGND Connector 6 Pin1 D0 A Pin2 not connected Pin2 SGND Pin3 S04 Digital in 4 Pin3 D1 B Pin4 S03 SGND Connector 7 Pin1 Analog in 1 Pin5 not connected Pin2 S...

Страница 6: ...om the power supply The digital inputs of TCW260 in OPEN CLOSED mode can be used for monitoring of devices with dry contact outputs door contact switch push button PIR detector etc The following pictu...

Страница 7: ...dity current voltage transducers etc The following picture illustrates how a battery can be connected to the analog input of TCW260 in voltage mode The positive terminal is connected to Analog In and...

Страница 8: ...and Implementation Guide available on www modbus org It is mandatory to use 120ohms line terminators at both ends of the bus TCW260 incorporates one of the terminators and should be placed at one end...

Страница 9: ...e T Ethernet hub switch or router For configuration TCW260 may be connected directly to the Ethernet port on a computer The device support Auto MDIX and it is not necessary to use crossover cable stan...

Страница 10: ...ess 192 168 1 2 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 Communication with TCW260 can be established by assigning a temporary IP address to the computer For computers with Windows OS ass...

Страница 11: ...up begin with network settings Then the so called primary parameters MODBUS RTU sensors registers analog inputs and digital inputs are set up The channels are formed from already set up primary parame...

Страница 12: ...terval is 1 second 8 1 1 Channels This page displays the status of all monitored channels their values and alarm status The information is updated on the refresh interval 8 1 2 Alarms This page displa...

Страница 13: ...etc rather than the default gateway 8 2 2 Modbus sensors 8 2 2 1 Modbus RTU communication setup This section allows you to set the communication parameters of the RS 485 interface bit rate parity and...

Страница 14: ...ler expects an answer in response time out If the sensor does not respond for that time the controller addresses the next sensor If the same sensor does not respond in series 3 times the device assume...

Страница 15: ...inputs 8 2 3 1 Analog inputs TCW260 has 6 analog inputs All they are isolated from the power supply but use the same ground Every analog input can work in voltage 0 10V or current loop mode 0 20mA Fo...

Страница 16: ...ame ground Every digital input can work in OPEN CLOSE or COUNTER mode In COUNTER mode counting can be made on rising falling or both edges For the counter mode there is a possibility for setting up of...

Страница 17: ...o 24 alarms can be set up There is four types of alarms Warning Minor Major and Critical Only channels can be used to form the alarms The alarms are independent but can be assigned to a channel There...

Страница 18: ...larm Return notification option is available If this option is chosen there will be notification also when parameter returns in range For every alarm there is Notification delay parameter It is very u...

Страница 19: ...HTTP port for WEB access by default is 80 but it can be changed This is useful for some routers which don t support different outside inside ports for port forwarding HTTP API access authentication b...

Страница 20: ...e SNMP disabled Port 161 SNMPv3 disabled read community public write community private Security User Name teracom Security Level noAuthNoPriv Authentication Protocol none Authentication Password rc ut...

Страница 21: ...n User based Privacy Mechanism is based on the following Data Encryption Standard DES Advanced Encryption Standard AES None encryption For alarm notification an SNMP trap can be sent to up to 5 indepe...

Страница 22: ...is very useful when monitoring electricity water gas meters etc The log interval can be chosen from a drop down menu between 1 and 60 minutes The field Sync to the minute determines which minute of ev...

Страница 23: ...Post The HTTPS is over TLS 1 0 TLS 1 1 and TLS 1 2 with RSA as a key exchange agreement and authentication The XML JSON file contains the current status of all monitored parameters and extra system in...

Страница 24: ...e following DNS services DynDNS No IP and DNS O Matric With dynamic DNS TCW260 can be accessed from the Internet having only a dynamic public IP address 8 3 6 MODBUS TCW260 supports MODBUS TCP IP The...

Страница 25: ...TCW260_R1 11 October 2022 Page 25 8 3 7 MQTT Device supports MQTT 3 1 1 This page is for the MQTT settings 8 3 7 1 MQTT General setup 8 3 7 2 MQTT Channels topic...

Страница 26: ...TCW260_R1 11 October 2022 Page 26 8 3 7 3 MQTT Alarms topic...

Страница 27: ...ces This is very useful for multiplying similar settings to a batch of controllers 8 4 3 FW update The TCW260 can be updated via a WEB interface To update the device follow the steps below Go to www t...

Страница 28: ...2 1 1 1 2 0 mbSenDescription read write Sensor description DisplayString 6 2 2 1 1 1 3 0 mbSenMult read write Sensor multiplier x1000 in Integer format Integer32 6 2 2 1 1 1 4 0 mbSenOffset read writ...

Страница 29: ...none 0 multiplication 1 division 2 sum 3 subtract 4 6 3 1 1 1 6 0 chParam2 read write Channel parameter 2 INTEGER none 0 one 1 null 2 s01 3 s02 4 s03 5 s04 6 s05 7 s06 8 s07 9 s08 10 s09 11 s10 12 s1...

Страница 30: ...2 v03 3 v04 4 v05 5 v06 6 v07 7 v08 8 v09 9 v10 10 v11 11 v12 12 v13 13 v14 14 v15 15 v16 16 v17 17 v18 18 v19 19 v20 20 v21 21 v22 22 v23 23 v24 24 6 3 2 1 1 10 0 alCond2Operand read write Alarm con...

Страница 31: ...TTPS Post to upload XML JSON file to a dedicated server This functionality is very useful if the controller is behind the router without a public IP address or the user don t have access to router con...

Страница 32: ...t is as follows http device ip address status xml http device ip address status json See sections 8 2 4 XML file structure and 8 2 5 JSON file structure for details of files HTTP Get can be sent at an...

Страница 33: ...xxx HTTP Post key xxx is up to 17 characters mdata x Data format JSON Plain text for MQTT Publish 0 JSON 1 Plain text mmode x Publish protocol where x is 0 for unsecure and 1 for TLS SSL muser xxxx U...

Страница 34: ...tion Humidity description value 51 323 value valuebin unit RH unit alarmbin 1 alarmbin alarm Normal alarm selch 4 selch CH2 CH3 type 2 type description Digital Input 1 description value OPEN value val...

Страница 35: ...h CH9 CH10 type 0 type description V10 description value value valuebin unit alarmbin 0 alarmbin alarm selch 0 selch CH10 CH11 type 0 type description V11 description value value valuebin unit alarmbi...

Страница 36: ...alarm selch 0 selch CH17 CH18 type 0 type description V18 description value value valuebin unit alarmbin 0 alarmbin alarm selch 0 selch CH18 CH19 type 0 type description V19 description value value v...

Страница 37: ...armbin 1 alarmbin alarm Normal alarm assign 5 assign AL2 AL3 description AL03 description alarmbin 1 alarmbin alarm Normal alarm assign 6 assign AL3 AL4 description AL04 DI1 description alarmbin 1 ala...

Страница 38: ...mbin alarm assign 0 assign AL14 AL15 description AL15 description alarmbin 0 alarmbin alarm assign 0 assign AL15 AL16 description AL16 description alarmbin 0 alarmbin alarm assign 0 assign AL16 AL17 d...

Страница 39: ...Key PostPeriod 300 PostPeriod HTTPPost MQTT Period 300 Period MQTT Sys hwerr HighAlarmbin 4 HighAlarmbin HighAlarm Minor HighAlarm Sys Time Date 15 05 2019 Date Time 10 32 44 Time Time Monitor Where...

Страница 40: ...valuebin unit C alarmbin 4 alarm Minor selch 3 CH2 type 0 description Humidity value 52 490 valuebin unit RH alarmbin 1 alarm Normal selch 4 CH3 type 2 description Digital Input 1 value OPEN valuebin...

Страница 41: ...09 value valuebin unit alarmbin 0 alarm selch 0 CH10 type 0 description V10 value valuebin unit alarmbin 0 alarm selch 0 CH11 type 0 description V11 value valuebin unit alarmbin 0 alarm selch 0 CH12 t...

Страница 42: ...ription V17 value valuebin unit alarmbin 0 alarm selch 0 CH18 type 0 description V18 value valuebin unit alarmbin 0 alarm selch 0 CH19 type 0 description V19 value valuebin unit alarmbin 0 alarm selch...

Страница 43: ...rm Minor assign 1 AL2 description AL02 alarmbin aa 1 alarm Normal assign 5 AL3 description AL03 alarmbin aa 2 alarm Normal assign 6 AL4 description AL04 DI1 alarmbin aa 3 alarm Normal assign 3 AL5 des...

Страница 44: ...assign 0 AL14 description AL14 alarmbin aa 13 alarm assign 0 AL15 description AL15 alarmbin aa 14 alarm assign 0 AL16 description AL16 alarmbin aa 15 alarm assign 0 AL17 description AL17 alarmbin aa 1...

Страница 45: ...sory computer with a remote terminal unit RTU in supervisory control and data acquisition SCADA systems 9 3 1 Codes and answers 9 3 1 1 Read Discrete Inputs FC 02 Request This command is requesting th...

Страница 46: ...of registers requested read 8 registers each 2 bytes 16 bytes Response 03 10 54 65 6D 70 65 72 61 74 75 72 65 00 00 00 00 00 03 The Function Code 3 read Analog Output Holding Registers 10 The number...

Страница 47: ...Function Code 16 10 hex 477C Starting Address of the firsrt register 477C hex 18300 0002 Quantity of registers 04 Byte count 0003 The value to be write 3 s01 in first register address 18300 0004 The v...

Страница 48: ...t 1 4 high level name R W 03 06 16 12200 16 bytes UTF 8 Digital input 1 4 mode R W 03 06 16 12300 16 bit unsign int openclosed 0 risingEdge 1 fallingEdge 2 bothEdges 3 Digital input 1 4 close to open...

Страница 49: ...16 bit unsign int none 0 multiplication 1 division 2 sum 3 subtract 4 Channel 1 to 24 parameter 2 R W 03 06 16 18500 16 bit unsign int none 0 s01 3 s02 4 s03 5 s04 6 s05 7 s06 8 s07 9 s08 10 s09 11 s1...

Страница 50: ...v19 19 v20 20 v21 21 v22 22 v23 23 v24 24 Alarm 1 to 24 condition 1 operand R W 03 06 16 20300 16 bit unsign int larger 0 less 1 Alarm 1 to 24 condition 1 limit R W 03 06 16 20400 32 bit float Alarm 1...

Страница 51: ...yes 1 Alarm 1 to 24 action 1 R W 03 06 16 21700 16 bit unsign int none 0 trapcond1 1 trapcond2 2 trapcond1and2 3 postiostate 4 mqttpublish 6 Alarm 1 to 24 action 2 R W 03 06 16 21800 16 bit unsign in...

Страница 52: ...s always header All rows including the header start with record ID and time stamp The structure of one row a record of the log is as follows ID Time Type of record Channels values units Channels state...

Страница 53: ...ght open simple and designed so as to be easy to implement MQTT is used in a wide variety of industries such as automotive manufacturing telecommunications oil gas and etc More about MQTT can be read...

Страница 54: ...ons 14 Safety This device must not be used for medical life saving purposes or for any purpose where its failure could cause serious injury or the loss of life To reduce the risk of fire only flexible...

Страница 55: ...operation If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Teracom Ltd be responsible or liable for ind...

Страница 56: ...TCW260_R1 11 October 2022 Page 56 Appendix A Fig 1 Fig 2...