Remote control application example
The controlled device is connected in series with the relay contacts. User can operate
TCW181B-CM
using either WEB browser or SNMP application. The relays can be managed
independently of each other.
The above example is included solely for illustrative purposes. Because of the many variables
and requirements associated with any particular installation, Teracom Ltd. cannot assume
responsibility or liability for actual use based on the example.
13.
Control and monitoring using SNMP
TCW181B-CM
can be configured and monitored through
SNMP (Simple Network
Management Protocol). This could be done using every SNMPv.1 compatible program.Parameters
that can be changed, are grouped according to their functions in the tables below. To obtain a valid
OID number it is necessary to replace the “x” symbol with the ”1.3.6.1.4.1.38783
”
. To save the
changes
configurationSaved
(OID
x
.6.0) should be set to "1".
13.1
Product
OID
Name
Access
Description
Syntax
x
.1.1.0
name
read-only Device name
String
x
.1.2.0
version
read-only Software version
String
x
.1.3.0
date
read-only Release date
String
13.2
SNMP Setup
OID
Name
Access
Description
Syntax
x
.2.1.0
trapEnabled
read-write TRAP messages enable/disable
INTEGER { Yes(1), No(0) }
x
.2.2.0
trapReceiverIPAddress
read-write TRAP messages receiver address
IpAddress
x
.2.3.0
trapCommunity
read-write TRAP community
String (SIZE (0..13))