10.

 

Installation 

This device must be installed by qualified personnel. 
This device must not be installed directly outdoors. 
Installation consists of mounting the device, connecting to an IP network, connecting inputs 

and outputs, providing power and configuring via a web browser.  

TCW181B-CM

 can be wall or flat, not flammable surface mounted, in a clean and dry location 

room. Ventilation is recommended for installations where ambient air temperature is expected to be 
high.  

Mount the device to a wall by using two plastic dowels 8x60mm (example Würth GmbH 0912 

802 002) and two dowel screws 6x70mm (example Würth GmbH 0157 06 70). Attach the screws to 
the surface vertically. See Appendix-A, fig. 1 for mechanical details. 

Maintain spacing from adjacent equipment. Allow 50 mm of space on all sides, as shown on 

fig.2 in Appendix A, this provides ventilation and electrical isolation

 

TCW181B-CM

 can be mounted to a standard (35mm by 7.55mm) DIN rail. Attach the 

controller to the DIN rail by hooking the hook on the back of the enclosure to the DIN rail and then 
snap the bottom hook into place.   

PCB only variant (

TCW181

) should be installed in not flammable box. See Appendix-A, fig. 1 

for mechanical details. Maintain spacing from adjacent equipment. Allow 50 mm of space on all sides, 
as shown on fig.2 in Appendix A. This provides ventilation and electrical isolation.  

 

11.

 

Configuration 

Please follow the steps below for proper installation : 

1.

 

Mount the controller in a dry and ventilated place. 

2.

 

Connect the Ethernet port to a 10/100MB Ethernet network. For direct connection to a PC 
use a “crossover” cable. 

3.

 

Connect the I/O pins of the controller according to the required application. 

4.

 

Connect the power supply. 

 

If the red LED blinks, the power supply is OK. By default 

TCW181B-CM 

comes with the following 

network settings: 

 

IP address: 

192.168.1.2,   

Subnet Mask:

 255.255.255.0, 

Default Gateway:

 192.168.1.1 

 

Communication  with 

TCW181B-CM

  can  be  established  by  assigning  a  temporary  IP  address  to 

the computer. This address should be in the same network (for example 192.168.1.3). To get access to 
the web interface, you should type 

http://192.168.1.2

 

 into the browser. 

 

 

If the network settings are correct, the “Login” page will appear.  
The web based interface allows configuration, monitoring and control. Recommended browser is 

Internet Explorer at 1024x768 resolutions. 

 

11.1

 

Login page 

After opening the “Login” page, authorization data must be entered (by default username=admin 

, password=admin). It is recommended to change the username and password to prevent unauthorized 
access to the controller. 

 

Содержание TCW181B-CM

Страница 1: ...ut is suitable for solving specific problems in various fields such as remote control process automation home automation and others 2 Features 10 Mb Ethernet connectivity Password protected web based configuration and control 1 digital input with logic level and dry contact modes 8 relays with NO and NC contacts SNMP v 1 support Sending SNMP Traps messages under certain conditions Sending E mail m...

Страница 2: ...NO COM NC of Relay7 Pin 10 11 12 NO COM NC of Relay8 Connector 2 Pin 1 2 3 NC COM NO of Relay4 Pin 4 5 6 NC COM NO of Relay3 Pin 7 8 9 NC COM NO of Relay2 Pin 10 11 12 NC COM NO of Relay1 Connector 3 Pin 1 Digital input DI Pin 2 Ground Pin 3 12VDC Connector 4 Power Ø2mm central positive Connector 5 Ethernet RJ45 Operating mode is selected by jumper DI on PCB closed for dry contact and open for log...

Страница 3: ...ler if recommended free spaces to adjacent devices are not ensured Joint part with external component shall have space for attachment removal of the cable after installation Teracom does not guarantee successful operation of the product if the product was used under conditions deviating from the product specifications To ensure that the device works correctly follow the steps below ensure that the...

Страница 4: ...for mechanical details Maintain spacing from adjacent equipment Allow 50 mm of space on all sides as shown on fig 2 in Appendix A This provides ventilation and electrical isolation 11 Configuration Please follow the steps below for proper installation 1 Mount the controller in a dry and ventilated place 2 Connect the Ethernet port to a 10 100MB Ethernet network For direct connection to a PC use a ...

Страница 5: ... to login the following message appears Someone s logged in The active session will be terminated automatically if the current user stays inactive for 2 minutes 11 2 Monitoring page After successful authorization the Monitoring page appears The Monitoring page provides information about the state of the relays and digital input ...

Страница 6: ...P address is static DNS these fields is mandatory if domain names are used instead of IP addresses By default DNS has the same Ip address as Default gateway Time Server and Time Zone these fields are not mandatory they are used when e mail must be sent Host Name up to 16 symbols it appears as a Subject in sent e mails MAC device MAC address The good practice is to change the default IP address of ...

Страница 7: ...ings for SNMP section are SNMP Configuration enable disable SNMP Read Write community performs client authentication Read Only community performs client authentication SNMP Traps enable disable SNMP trap messages IP address IP address of the receiving host Community string performs client authentication Trap Interval time interval in seconds for SNMP trap messages Max Traps number maximum number o...

Страница 8: ...put can mange e mail sending Following parameters must be set Mail to e mail address of recipient Subject e mail subject Message e mail body Important It is necessary to set SMTP server settings on Network Setup page to successfully send e mail messages In the example above if an event occurs closing contact the controller will send e mail message to info teracom cc with subject input alarm and bo...

Страница 9: ...Network Management Protocol This could be done using every SNMPv 1 compatible program Parameters that can be changed are grouped according to their functions in the tables below To obtain a valid OID number it is necessary to replace the x symbol with the 1 3 6 1 4 1 38783 To save the changes configurationSaved OID x 6 0 should be set to 1 13 1 Product OID Name Access Description Syntax x 1 1 0 na...

Страница 10: ...7 pulse state INTEGER 0 255 x 3 17 0 Pulse8 read write Relay 8 pulse state INTEGER 0 255 x 3 18 0 allOn read write Set all relays On INTEGER 0 255 x 3 19 0 allOff read write Set all relays Off INTEGER 0 255 x 3 20 0 allPulse read write Pulse all relays INTEGER 0 255 13 4 Network OID Name Access Description Syntax x 4 1 0 deviceIPAddress read write Device IP address IpAddress x 4 2 0 subnetMask rea...

Страница 11: ...SIZE 0 22 x 6 0 configurationSaved read write Configuration save status SAVED UNSAVED INTEGER SAVED 1 UNSAVED 0 x 7 0 restartDevice read write Restart Device INTEGER RESTART 1 CANCEL 0 14 XML and HTTP API commands XML is often preferred choice when it comes to M2M communication and system integration The monitored values are transmitted in status xml file that can be easily processed by software a...

Страница 12: ... Name Admin admin Password Admin admin IP Address 192 168 1 2 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 SNMPConfiguration disabled readCommunity public writeCommunity private 16 Firmware update TCW181B CM supports remote firmware update To update the device follow the steps below Download the TCW1XX_Update_Tool program from www teracom cc Download the latest firmware version file cod f...

Страница 13: ...TCW181B CM_R1 Page 13 Appendix A Fig 1 Fig 2 ...

Отзывы: