TCW122B-WD_R2 ( Firmware version 2.xx )
Page 8
Authentication details for WEB access to
TCW122B-WD
can be set in the last section. Only one user is
supported.
11.5
SNMP Setup page
TCW122B-WD
supports SNMP v.1. This enables the device to be part of large monitoring and control
networks. The possible settings for “SNMP” section are:
SNMP Configuration
– enable/disable SNMP;
SNMP Port
– allows standard port changing;
Write/Read community
– performs client authentication;
SNMP Traps
–
enable/disable SNMP trap messages;
IP address
– IP address of the receiving host;
Community string
– performs client authentication;
Trap Interval
-
time interval in seconds for SNMP trap messages;
Max. Traps number
– maximum number of SNMP trap messages sent, if trap condition is
present.
SNMP traps are sent if:
event occurs (status change) on Digital Input 1 or Digital Input 2;
measured voltage on Analog Input 1 or Analog Input 2 goes outside the range;
measured temperature goes outside the range;
measured humidity goes outside the range;
restart condition.