TCW122B-WD_R2 ( Firmware version 2.xx )
Page 2
3.
Technical parameters
Supply voltage, VDC
12±2
Maximum current consumption (with both relays ON), mA
200
Weight, g
110
Dimensions, mm
107 x 72 x 32
Operating temperature, °C
0 to +40
Maximum humidity in 0 to 31°C range, %RH
80
Maximum humidity at 40°C (linear slope between 31-40°C), %RH
50
Minimum high level input voltage for digital inputs, VDC
+2.5
Maximum low level input voltage for digital inputs, VDC
+0.8
Maximum input voltage for digital inputs, VDC
+5.5
Supply voltage for 1-wire bus (
VDD
), VDC
5.3 ± 0.2
Maximum output current for 1-wire bus (
VDD
), A
0.2
Analog input 1 range, VDC
0 to +60
Analog input 2 range, VDC
0 to +60
Maximum switchable current for relay contacts, А
3
Maximum switchable voltage for relay contacts, VAC/VDC
30/24
4.
Connectors
Inputs and outputs locations are shown below:
Connector 1
– Power - central positive
Connector 2, Pin1 -
Digital input 1 (
Din1
)*
Connector 2, Pin2 -
Digital input 2 (
Din2
)*
Connector 2, Pin3 -
Ground
Connector 2, Pin4 -
Analog input 1 (
Ain1
)
Connector 2, Pin5 -
Analog input 2 (
Ain2
)
Connector 2, Pin6 -
Ground
Connector 2, Pin7 –
1-Wire data
Connector 2, Pin8 –
1-Wire power supply
Connector 3
– Ethernet - RJ45
Connector 4, Pin1
– NC Relay1
Connector 4, Pin2
– COM Relay1
Connector 4, Pin3
– NO Relay1
Connector 5, Pin1
– NC Relay2
Connector 5, Pin1
– COM Relay2
Connector 5, Pin1
– NO Relay2
* Operating mode is selected by jumper DI1/DI2 -
closed for “dry contact” and open for “logic
level”. By default jumpers are closed.
5.
LED indicators
The following indicators show the status of the controller:
Relay1
/
Relay2
(green) – these LEDs are illuminated whenever the corresponding relay is
activated (the NO contact is closed and the NC contact is open);
Sts
(red) – flashes when the main program of controller is executed;
Log
(yellow) – indicates that somebody is logged via WEB interface;