TCW122B-WD_R2 ( Firmware version 2.xx )
Page 11
14.5
Setup -> SNMP
OID
Name
Access
Description
Syntax
x
.2.4.1.0
snmpConfiguration
read-write SNMP Configuration
INTEGER { disabled(0), enabled(1) }
x
.2.4.2.0
trapEnabled
read-write TRAP messages ENABLED/DISABLED
INTEGER { no(0), yes(1) }
x
.2.4.3.0
trapReceiverIPAddress
read-write TRAP receiver IP address
IpAddress
x
.2.4.4.0
trapCommunity
read-write TRAP community
String (SIZE (0..13))
x
.2.4.5.0
trapInterval
read-write TRAP messages interval
INTEGER (1..253)
x
.2.4.6.0
maxNumberOfTraps
read-write Maximum number SNMP traps
INTEGER (1..253)
14.6
Setup -> oneWireSensor1 -> temperature1
OID
Name
Access
Description
Syntax
x
.2.5.1.1.0
temperature1Min
read-write Temperature1 range (min. value)
INTEGER (-400..1250)
x
.2.5.1.2.0
temperature1Max
read-write Temperature1 range (max. value)
INTEGER (-400..1250)
x
.2.5.1.3.0
temperature1Hyst
read-write Hysteresis
INTEGER (0..1250)
14.7
Setup -> oneWireSensor1 -> humidity1
OID
Name
Access
Description
Syntax
x
.2.5.2.1.0
humidity1Min
read-write Humidity1 range (min. value)
INTEGER (0..1000)
x
.2.5.2.2.0
humidity1Max
read-write Humidity1 range (max. value)
INTEGER (0..1000)
x
.2.5.2.3.0
humidity1Hyst
read-write Hysteresis
INTEGER (0..1000)
14.8
Setup -> oneWireSensor2 -> temperature2
OID
Name
Access
Description
Syntax
x
.2.6.1.1.0
temperature2Min
read-write Temperature2 range (min. value)
INTEGER (-400..1250)
x
.2.6.1.2.0
temperature2Max
read-write Temperature2 range (max. value)
INTEGER (-400..1250)
x
.2.6.1.3.0
temperature2Hyst
read-write Hysteresis
INTEGER (0..1250)
14.9
Setup -> oneWireSensor2 -> humidity2
OID
Name
Access
Description
Syntax
x
.2.6.2.1.0
humidity2Min
read-write Humidity2 range (min. value)
INTEGER (0..1000)
x
.2.6.2.2.0
humidity2Max
read-write Humidity2 range (max. value)
INTEGER (0..1000)
x
.2.6.2.3.0
humidity2Hyst
read-write Hysteresis
INTEGER (0..1000)
14.10
Setup -> analogInput -> input1
OID
Name
Access
Description
Syntax
x
.2.7.1.1.0
voltage1Min
read-write Voltage1 alarm range (min. value)
INTEGER (0..1000)
x
.2.7.1.2.0
voltage1Max
read-write Voltage1 alarm range (max. value)
INTEGER (0..1000)
x
.2.7.1.3.0
voltage1Hyst
read-write Voltage1 hysteresis
INTEGER (0..1000)
14.11
Setup -> analogInput -> input2
OID
Name
Access
Description
Syntax
x
.2.7.2.1.0
voltage2Min
read-write Voltage2 alarm range (min. value)
INTEGER (0..1000)
x
.2.7.2.2.0
voltage2Max
read-write Voltage2 alarm range (max. value)
INTEGER (0..1000)
x
.2.7.2.3.0
voltage2Hyst
read-write Voltage2 hysteresis
INTEGER (0..1000)
14.12
Setup -> relay
OID
Name
Access
Description
Syntax
x
.2.9.1.0
relay1ControlledBy
read-write Relay1 control item
INTEGER { manual(0), watchdog1(1) }
x
.2.9.2.0
relay2ControlledBy
read-write Relay2 control item
INTEGER { manual(0), watchdog2(1) }
x
.2.9.3.0
relayPulseWidth
read-write Relay Pulse Width
INTEGER{ 1..253 }