TCW112-WD_R2 - June 2014
Page 10
9.
1-Wire Bus
1-Wire is a registered trademark of Maxim Integrated Products, Inc. It is designed to connect
several sensors over a short wiring. The bus carries power and a single data wire. It is not suitable for
long distances or environments with EMC interference. We strongly recommend to read Maxim’s 1-Wire
tips at
http://www.maxim-ic.com/app-notes/index.mvp/id/148
.
We recommend keeping the total wiring length under 60m, although functionality has been
achieved in longer distance. We cannot guarantee error-free operation over mentioned wiring length.
We guarantee proper operation only with our 1-Wire sensors series TST1XX and TSH2XX.
10.
Control and monitoring using SNMP
TCW112-WD
can be configured and monitored through SNMP (Simple Network Management
Protocol). This could be done using every SNMPv.1 compatible program. Parameters that can be
changed, are grouped according to their functions in the tables below. To obtain a valid OID number it is
necessary to replace “
x
” symbol with “
1.3.6.1.4.1.38783”
. To save the changes
configurationSaved
(OID
x.3.7.0) should be set to “1”.
10.1
Product
OID
Name
Access
Description
Syntax
x
.1.1.0
name
read-only Device name
String
x
.1.2.0
version
read-only Firmware version
String
x
.1.3.0
date
read-only Firmware release date
String
10.2
Setup -> network
network
OID
Name
Access
Description
Syntax
x
.2.1.1.0
deviceIPAddress
read-write Device IP address
IpAddress
x
.2.1.2.0
subnetMask
read-write Subnet Mask
IpAddress
x
.2.1.3.0
gateway
read-write Gateway IP address
IpAddress
x
.2.1.4.0
deviceMACAddress
read-write Device MAC address
OCTET STRING (SIZE(6))
x
.2.1.5.0
dhcpConfig
read-write DHCP configuration ON/OFF
INTEGER { off(0), on(1) }
x
.2.1.6.0
dns
read-write Domain Name Server Address
IpAddress
x
.2.1.7.0
hostName
read-write Host Name
String (SIZE (0..38))
10.3
Setup -> network -> VLAN
network -> VLAN
OID
Name
Access
Description
Syntax
x
.2.1.10.1.0 vlanStatus
read-write VLAN Status ENABLED/DISABLED
INTEGER { disabled(0), enabled(1) }
x
.2.1.10.2.0 vlanId
read-write VLAN ID (0-4095)
INTEGER (0..4095)
10.4
Setup -> network -> macFilter
network -> macFilter
OID
Name
Access
Description
Syntax
x
.2.1.11.1.0 filterMACAddress1
read-only
filter1 MAC address (Gateway)
OCTET STRING (SIZE(6))
x
.2.1.11.2.0 filterMACEnable1
read-write MAC filter 1 Enable ENABLED/DISABLED
INTEGER { disabled(0), enabled(1) }
x
.2.1.11.3.0
filterMACAddress2
read-write Filter2 MAC address
OCTET STRING (SIZE(6))
x
.2.1.11.4.0
filterMACEnable2
read-write MAC filter 2 Enable ENABLED/DISABLED
INTEGER { disabled(0), enabled(1) }
x
.2.1.11.5.0
filterMACAddress3
read-write Filter3 MAC address
OCTET STRING (SIZE(6))
x
.2.1.11.6.0
filterMACEnable3
read-write MAC filter 3 Enable ENABLED/DISABLED
INTEGER { disabled(0), enabled(1) }