Pressing the “Start” button will start your web browser and display the Monitoring page of your 

TCG120 

controller. 

 

7.1.  Monitoring page

 

Monitoring  page  displays  the  current  I/O  state  of 

TCG120 

controller

The  page  has  4  sections  – 

“Sensors”, “Digital inputs”, “Analog inputs” and “Relays”. 

For every parameter (sensor, input, relay) there is a description of up to 20 characters. The default 

descriptions can be changed in “Setup-Input/Output” menu. 

The Monitoring page can be automatically refreshed on an interval of 0 to 254 seconds. Zero means 

no  automatic  refresh.  This  parameter  is  set  in  section  “Setup->System->Monitoring  page  automatic 
refresh”. By default it is 30 seconds. 

 

7.1.1. Sensors section

 

All  detected  1-Wire  sensors  are  shown  in  this  section.  Sensor  detection  is  made  either  after 

connecting  the  power  supply  or  by  “Scan  for  new  sensors”  button.  All  found  sensors  are  shown  in 
ascending  order  refer  their  unique  ID  number.  For  every  sensor  there  are  description,  value,  and  ID 
information. 

Teracom  temperature  sensors  readings  are  shown  in  the  Value  1  column.  TSH2xx 

temperature/humidity sensors have the 2nd parameter shown on the Value 2 column. 

It is possible to lock sensors in a specific position. To do this all sensors should be added one by one. 

After every addition new scan should be made and newly found sensor should be locked in its position. 
If all sensors are locked, removing one “in the middle” will not change the positions of following sensors 
after reset. This option is very useful when 

TCG120 

is used like a part of monitoring and control system 

managed either by SNMP or HTTP API commands. 

 

 

 

7.1.2. Digital inputs section

 

Digital  inputs  can  be  used  for  monitoring  the  state  of  discrete  devices  –  motion  sensor,  door 

contact, relay contact, alarm output etc. Both digital inputs are not galvanic isolated. 

Содержание TCG120

Страница 1: ......

Страница 2: ...and TSHxxx temperature humidity sensors SMS alarm alerts up to 5 numbers Email alarm alerts up to 5 email recipients SMTP with SSL support Single call control the relays can be controlled with a singl...

Страница 3: ...mum low level input voltage for digital inputs VDC 0 8 Maximum input voltage for digital inputs VDC 5 5 Supply voltage for 1 wire bus VDD VDC 5 0 0 2 Maximum output current for 1 wire bus VDD A 0 2 An...

Страница 4: ...ion 6 2 Connectors Attention Disconnect power supply before wiring The correct wiring procedure is as follows Make sure power is turned off Make wiring connections to the terminals Apply power It is r...

Страница 5: ...y contact mode digital inputs can be used to monitor the state of a discrete device door contact switch push button PIR detector etc Following picture illustrates how a dry contact switch can be conne...

Страница 6: ...esigned to connect several sensors over a short wiring It is not suitable for long distances or environments with EMC interference We recommend reading Maxim s 1 Wire tips at http www maxim ic com app...

Страница 7: ...ver mentioned wiring length We guarantee proper operation only with Teracom 1 Wire sensors 6 2 5 Relay connection The relay contacts are internally connected directly to the terminal connectors For al...

Страница 8: ...essage appears The following drivers will be installed Microchip composite device USB serial port driver If for some reason the USB serial port driver cannot be installed automatically it must be inst...

Страница 9: ...he power supply or by Scan for new sensors button All found sensors are shown in ascending order refer their unique ID number For every sensor there are description value and ID information Teracom te...

Страница 10: ...nic isolated One side of source is connected to Analog In and the other side is connected to GND pins For every analog input 3 variables Unit Multiplier and Offset can be set in Setup Input Output sec...

Страница 11: ...an be set in this section These descriptions will appear in the monitoring page XML data SMS and Email alerts For every analog input field Unit Multiplier and Offset parameters are available to conver...

Страница 12: ...on Setup Alarm conditions Following choices to assign parameter to relay are possible S S stands for Sensor 1 Wire The relay is activated from value measured from specified 1 Wire sensor and rules for...

Страница 13: ...section is used for parameterization of trigger and alert conditions for 1 Wire sensors analog and digital inputs 7 2 3 1 1 Wire sensors and analog inputs For every sensor two type of fields are pres...

Страница 14: ...SMS message with the measured value Email SMS the authorized recipients will receive SMS and email messages with the measured value All above settings are valid also for the analog inputs Example TCG1...

Страница 15: ...it reached 19 C it goes out of range trigger and alert conditions The relay is activated heater is switched on and e mail is sent The Max value is set far enough from the wanted temperature to avoid t...

Страница 16: ...mote server 1 HTTP POST request with XML data is sent to the remote server 2 the server responds with HTTP response message which contains set r1 1 command as a brief text in the message body 3 new HT...

Страница 17: ...able to process the commands which are sent from the remote server The valid commands are described below Command Description set r1 1 Turn Relay 1 ON set r1 0 Turn Relay 1 OFF set r2 1 Turn Relay 2...

Страница 18: ...t should be used IPaddress Port For example 209 81 9 7 123 The current system time is sent in the status xml file when Push mode is enabled 7 2 5 3 GPRS setup To set the GPRS connection it is necessar...

Страница 19: ...tension Press UPLOAD button The firmware will be uploaded and verified the Upload procedure taker around 6 minutes If the file is correct the following message will appear Upload Successful Please wai...

Страница 20: ...m or larger for wiring of digital and analog inputs and relay output of the device should be used To avoid electric shock and fire hazard do not expose this product to liquids rain or moisture Objects...

Страница 21: ...able after Controller Initialization the LEDs will display directly the next controller state Searching for GSM network Searching for GSM network SIG LED is OFF STA LED flashes flash length 200ms Conn...

Страница 22: ...02rc4 FwVer MnfInfo www teracom cc MnfInfo DeviceInfo S Appendix B S1 S1 S2 description Sensor1 description id FFFFFFFFFFFF id item1 value value unit unit alarm 0 alarm item1 item2 value value unit u...

Страница 23: ...sor4 description id FFFFFFFFFFFF id item1 value value unit unit alarm 0 alarm item1 item2 value value unit unit alarm 0 alarm item2 description Analog In1 description value 0 00 value unit VDC unit mu...

Страница 24: ...ter must be replaced by one space character SMS master number Syntax number mobile number in international format Rights Master Description this message is used to change the Master number Example mas...

Страница 25: ...ormat Rights Master Description this message is used to add up to 5 numbers to the Call list Example add call users 359885111111 359885222222 359885333333 359885444444 35988555555 Answer 359885111111...

Страница 26: ...values of relay are r1 r2 Rights Master Users Description this message is used to switch ON OFF the selected relay output Example 1 set r1 1 Answer R1 ON R2 OFF DI1 0 DI2 1 AI1 15 6VDC AI2 681 3kg S11...

Страница 27: ...e is used to send test SMS messagel to the authorized users Example test sms Answer SMS update URL Syntax URL is URL of the update cod file Rights Master Description this message is used to update the...

Отзывы: