Appendix A

 

 

LED  indicators  are  intended  to  show  the  status  of  the  controller.  The  following  states  are 

displayed after the power supply is turned ON: 

Controller  initialization 

–  Both  LEDs  (SIG  and  STA)  turn  ON  for  1  second  every  time  when  the 

controller is initialized – after turning the power supply ON or after firmware update 

Error message 

– after Controller initialization both LEDs will turn OFF.  If there is an error message, 

STA  Led  will  start  to  flash.  The  number  of  flashes  (flash  length  –  1  second)  shows  different  error 
message: 

  

Master not set – STA LED flashes once; 

  

Hardware problem 

– 

STA LED flashes constantly. 

Is there is no error message available, after Controller Initialization the LEDs will display directly the next 
controller state - Searching for GSM network. 

Searching for GSM network 

– SIG LED is OFF, STA LED flashes (flash length – 200ms). 

Connected to GSM network 

– Once the controller is connected to the GSM network, SIG and STA 

LEDs will display the level of the GSM signal. STA LED will flash once every 2 seconds (flash length– 
200ms.) This indication ensures that 

TCG120 

is connected to the network. If STA LED flashes twice – this 

indicates that GPRS connection is established. Between the STA LED flashes, SIG LED will indicate the 
signal strength: 1 flash (200ms.) means that signal strength is between 0 and 20%, 2 flashes – 20 and 
40%, 3 flashes – 40 and 60%, 4 flashes – 60 and 80%. If SIG LED is solid ON– this indicates that the signal 
level is higher than 80%. 

The above described controller states are shown in the diagrams below: 

 

 

 

 
 

 

 

 

Содержание TCG120

Страница 1: ......

Страница 2: ...and TSHxxx temperature humidity sensors SMS alarm alerts up to 5 numbers Email alarm alerts up to 5 email recipients SMTP with SSL support Single call control the relays can be controlled with a singl...

Страница 3: ...mum low level input voltage for digital inputs VDC 0 8 Maximum input voltage for digital inputs VDC 5 5 Supply voltage for 1 wire bus VDD VDC 5 0 0 2 Maximum output current for 1 wire bus VDD A 0 2 An...

Страница 4: ...ion 6 2 Connectors Attention Disconnect power supply before wiring The correct wiring procedure is as follows Make sure power is turned off Make wiring connections to the terminals Apply power It is r...

Страница 5: ...y contact mode digital inputs can be used to monitor the state of a discrete device door contact switch push button PIR detector etc Following picture illustrates how a dry contact switch can be conne...

Страница 6: ...esigned to connect several sensors over a short wiring It is not suitable for long distances or environments with EMC interference We recommend reading Maxim s 1 Wire tips at http www maxim ic com app...

Страница 7: ...ver mentioned wiring length We guarantee proper operation only with Teracom 1 Wire sensors 6 2 5 Relay connection The relay contacts are internally connected directly to the terminal connectors For al...

Страница 8: ...essage appears The following drivers will be installed Microchip composite device USB serial port driver If for some reason the USB serial port driver cannot be installed automatically it must be inst...

Страница 9: ...he power supply or by Scan for new sensors button All found sensors are shown in ascending order refer their unique ID number For every sensor there are description value and ID information Teracom te...

Страница 10: ...nic isolated One side of source is connected to Analog In and the other side is connected to GND pins For every analog input 3 variables Unit Multiplier and Offset can be set in Setup Input Output sec...

Страница 11: ...an be set in this section These descriptions will appear in the monitoring page XML data SMS and Email alerts For every analog input field Unit Multiplier and Offset parameters are available to conver...

Страница 12: ...on Setup Alarm conditions Following choices to assign parameter to relay are possible S S stands for Sensor 1 Wire The relay is activated from value measured from specified 1 Wire sensor and rules for...

Страница 13: ...section is used for parameterization of trigger and alert conditions for 1 Wire sensors analog and digital inputs 7 2 3 1 1 Wire sensors and analog inputs For every sensor two type of fields are pres...

Страница 14: ...SMS message with the measured value Email SMS the authorized recipients will receive SMS and email messages with the measured value All above settings are valid also for the analog inputs Example TCG1...

Страница 15: ...it reached 19 C it goes out of range trigger and alert conditions The relay is activated heater is switched on and e mail is sent The Max value is set far enough from the wanted temperature to avoid t...

Страница 16: ...mote server 1 HTTP POST request with XML data is sent to the remote server 2 the server responds with HTTP response message which contains set r1 1 command as a brief text in the message body 3 new HT...

Страница 17: ...able to process the commands which are sent from the remote server The valid commands are described below Command Description set r1 1 Turn Relay 1 ON set r1 0 Turn Relay 1 OFF set r2 1 Turn Relay 2...

Страница 18: ...t should be used IPaddress Port For example 209 81 9 7 123 The current system time is sent in the status xml file when Push mode is enabled 7 2 5 3 GPRS setup To set the GPRS connection it is necessar...

Страница 19: ...tension Press UPLOAD button The firmware will be uploaded and verified the Upload procedure taker around 6 minutes If the file is correct the following message will appear Upload Successful Please wai...

Страница 20: ...m or larger for wiring of digital and analog inputs and relay output of the device should be used To avoid electric shock and fire hazard do not expose this product to liquids rain or moisture Objects...

Страница 21: ...able after Controller Initialization the LEDs will display directly the next controller state Searching for GSM network Searching for GSM network SIG LED is OFF STA LED flashes flash length 200ms Conn...

Страница 22: ...02rc4 FwVer MnfInfo www teracom cc MnfInfo DeviceInfo S Appendix B S1 S1 S2 description Sensor1 description id FFFFFFFFFFFF id item1 value value unit unit alarm 0 alarm item1 item2 value value unit u...

Страница 23: ...sor4 description id FFFFFFFFFFFF id item1 value value unit unit alarm 0 alarm item1 item2 value value unit unit alarm 0 alarm item2 description Analog In1 description value 0 00 value unit VDC unit mu...

Страница 24: ...ter must be replaced by one space character SMS master number Syntax number mobile number in international format Rights Master Description this message is used to change the Master number Example mas...

Страница 25: ...ormat Rights Master Description this message is used to add up to 5 numbers to the Call list Example add call users 359885111111 359885222222 359885333333 359885444444 35988555555 Answer 359885111111...

Страница 26: ...values of relay are r1 r2 Rights Master Users Description this message is used to switch ON OFF the selected relay output Example 1 set r1 1 Answer R1 ON R2 OFF DI1 0 DI2 1 AI1 15 6VDC AI2 681 3kg S11...

Страница 27: ...e is used to send test SMS messagel to the authorized users Example test sms Answer SMS update URL Syntax URL is URL of the update cod file Rights Master Description this message is used to update the...