TCG120 _R1.1 - March 2015
Page 17
If the checkbox “Connect on any alarm” is selected, the HTTP POST request will be send if any
alarm condition occurs. The “Key” field value is sent in the XML data and can be used for device
identification.
If “Process Answer” option is enabled, the
TCG120
controller will be able to process the
commands, which are sent from the remote server. The valid commands are described below:
Command
Description
set r1=1
Turn Relay 1 ON
set r1=0
Turn Relay 1 OFF
set r2=1
Turn Relay 2 ON
set r2=0
Turn Relay 2 OFF
set tg1=1
Toggle Relay 1 state
set pl1=1
Pulse Relay 1
set r1=1&r2=1
Turn both relays ON
set
r1=0&r2=0
Turn both relays OFF
set FIN
No pending command
Typical monitoring application is shown on the picture below:
The structure of
Status.xml
file is shown in
Appendix B.
Содержание TCG120
Страница 1: ......