Table of light sources:
Model code Max. wattage
LBT
marking
Nominal
voltage
Luminous flux
Lamp
holder
Temp.
class
(gas
)
T
0 MAX
(dust)
OSRAM type
PHILIPS type
Another
supplier
T
a
=40°C T
a
=40°C
PLFM
100 - .
100 W
A
230V
1340 lm
E27
T4
130°C
-
GE Lighting -
Rough Service
GLS - Clear
116 W Osram
105 W Philips
A ECO
230 V
2135 lm Osram
1980 lm Philips
E27
T4
130°C
Halogen Classic
A ECO
EcoClassic A -
shape
-
100 W
QT
230 V
1800 lm Osram
E27
T4
130°C
Halolux Ceram
Eco
-
-
PLFM
100/1 - .
100 W
LME
230 V,
50 Hz
1100 lm
E27
T3
155°C
-
ML Mixed Light
lamps
-
PLFM
100/2 - .
22 W Osram
23 W Philips
TC-SB
230 V,
50 Hz
1440 lm
E27
T6
80°C
Osram Deluxe-
Intelligent
Longlife
Master PL -
Electronic
-
PLFM
100/3 - .
12 W Osram
13 W Philips
LED
230 V,
50 Hz
810 lm Osram
1055 lm Philips
E27
T6
80°C
Parathorm Ledotron
Classic A
Master LED bulb
-
PLFM
20 LED - .
20 W
LED
modul
230 V,
50 Hz
1300 lm
-
T6
80°C
-
-
Vossloh LED
LR 42
PLFM
FLASH - .
5 W
XENON
10–100 V DC
4J/90Hz
-
T6
80°C
-
-
RS Components
– Miniature
Xenon beacons
110 V AC
230 V AC
PLFM
70 HSE - .
70 W
HSE
230 V,
50 Hz
5900 lm Osram
5600 lm Philips
E27
T4
130°C
Vialox NAV-E
70W/I
SON 70W I E27
CO 1CT
-
50W
HSE
230 V, 50 Hz
3600 lm Osram
3500 lm Osram
E27
T4
130°C
Vialox NAV-E
50W/I
SON 50W I E27
CO 1CT
-
PLFM
LUXOMAT 10
-
.
-
-
12 V AC/DC
-
-
T6
85°C
-
-
Doepke DASY
010
24 V AC/DC
230 V AC
PLFM
LUXOMAT 16
- .
-
-
230 V AC
-
-
T6
85°C
-
-
Doepke DASY
016
7. MOUNTING
AND INSTALLATION
Mounting of the lamp:
- With vertical suspension on the bolt with ring bolt
head M8 witch is twisted in the housing and further
blocked from self-loosening
- Mounting on the tube 2” and blocking it with two M10
screws
Before opening the housing, unscrewing the assembly of the protective glass, mechanical release should be carried
out by unscrewing the blocking screws M4x14 ISO 4027 in the framework of the glass. Removing the lamps is only
allowed in the not energized state. Not energized state must be ensured by switching of the master switch. It is
recommended only to install light sources listed in the table of light sources.
Electrical connection is made by connecting the power cable to the terminal connection terminals L - phase
conductor, N - neutral, PE - protective earth. For direct entry of cable, electrical connection is made by connecting
the power cable to the plug.