- 6 - 

5.2

 

Casters (Optional Accessory)

5.2.1.1

 

Description 

The standard option for the Air Medic is rubber foot pads for 
stability. An optional accessory for the Air Medic is four swivel 
casters,  two  are  locking.  These  casters  add  increased 
portability and allow the unit to roll around in any direction.  

5.2.1.2

 

Installation Instructions 

To instal the casters, first place the unit on its side, be careful 
not  to  scratch  the  unit.  Remove  the  rubber  foot  pads  by 
unscrewing them from the threaded holes on the bottom of 
the unit.  

Take the supplied casters and align them with the holes in the 
corners on the bottom. Ensure the lockable casters are at the 
front of the unit for easy access. Screw the base of the caster 

to the base of the unit, with the spring washer placed between 
the screw head and the caster base.  

5.3

 

UVC Light (Optional Accessory)

5.3.1.1

 

Description 

An  optional  accessory  is  the  UVC  light.  This  is  a  fluorescent 
style bulb that emits what is known as UVC-GI light wavelength 
(UVC-Germicidal Irradiation, 254nm). This light is a very small 
wavelength  which  allows  it  to  penetrate  pathogens  and 
destroy the DNA rendering it inert.  

The light is positioned so that it shines on the full face of the 
HEPA  filter,  allowing  it  to  clean  filter  of  anything  that  gets 
caught to it and to lengthen the filter life.  

Direct exposure should be avoided as it may cause damage to 
skin and eyes.  

The UVC light is also supplied with a reflector to ensure that 
the  UVC  light  does  not  have  any  direct  exposure  on  the  fan 
assemblies. 

5.3.1.2

 

Installation Instructions 

First  remove  the  lower  and  upper  access  panel  and  then 
remove the HEPA filter.  

Take the light ballast and align the tabs with the holes on the 
right fan bulkhead, closest to the wall of the unit, and screw 
them down with the provided Philips head screws.  

Take supplied UVC mount assembly and align it with the four 
holes (two on each bulkhead) and with the end with the Bulb 
mounting bolts on the same side as the ballast. Screw assembly 
down with the provided Philips head screws. 

Mount  the  UVC  bulb,  by  inserting  the  cable  through  the 
mounting bracket. Align the blub base with the mounting bolts 
and tighten the supplied nuts. Do not over tighten the nuts.  

Connect the bulb to the ballast, and the ballast to the power 
supply using the supplied quick connects. Ensure they have a 
firm and properly sealed connection, and that the locks have 
fully engaged.  

5.3.1.3

 

Maintenance Interval 

The replacement frequency for the UVC bulb can be found in 
Table 1. 

5.3.1.4

 

Replacement Instructions  

To replace the UVC light, only the blub needs to be replaced. 
To do this, first remove the lower and upper access panel and 
then remove the HEPA filter.  

Disconnect  the  quick  connect  between  the  bulb  and  the 
ballast,  remove  the  nuts  holding  the  bulb  to  the  mounting 
bracket  and  remove  the  bulb  and  wire  from  the  mounting 
bracket.  

To  reinstall  the  new  bulb,  insert  the  cable  through  the 
mounting bracket. Align the bulb base with the mounting bolts 
and  tighten  the  supplied  nuts.  Do  not  over  tighten  the  nuts 
Reconnect the wiring quick connect between the bulb and the 
ballast.  Ensure  they  have  a  firm  and  properly  sealed 
connection, and that the locks have fully engaged.  

 

Содержание Air Medic TIF-06

Страница 1: ...IOM 2020 0 2360 Millrace Court Tel 905 670 3595 Mississauga Ontario Fax 905 670 3592 Canada L5N 1W2 Web Temspec com Air Medic Air Filtration Sterilization Unit TIF 06 Installation Operation Maintenance Manual ...

Страница 2: ...nel 3 4 4 Motor Access Panel 4 5 Air Medic Component Installation Maintenance and Replacement Instructions 4 5 1 Filters 4 5 1 1 Prefilter 4 5 1 2 HEPA Filter 5 5 1 3 Activated Carbon Filter Optional Accessory 5 5 2 Casters Optional Accessory 6 5 3 UVC Light Optional Accessory 6 5 4 Ionizer Optional Accessory 7 5 5 Fan Assembly 8 5 6 Differential Pressure Switch Optional Accessory 8 6 Warranty Inf...

Страница 3: ...e hot and could cause serious burns if not handled properly Please wait until the lamp has cooled to room temperature to remove from the unit WARNING UV Light Hazard Harmful to skin and eyes Can cause temporary or permanent loss of vision Never look at the lamp while illuminated To prevent exposure to ultraviolet light be sure the power is disconnected before servicing CAUTION Ionizer generates hi...

Страница 4: ... switched This pressure switch measures the air pressure around the HEPA filter and when it is too high the indicator light will come on to warn the user it should be changed This is only a warning indicator The unit will continue to work with it on but the airflow will be decreased due to the dirty filter 3 3 Fan Control The fan control is available in either variable speed or constant speed conf...

Страница 5: ...el is equipped with two cam latches that turn to lock in place to secure the panel and the optional lock mentioned above To open the lower access panel unlock the cam lock turn the cam latches to the unlocked position and then pull up and out When replacing the panel align the panel with the width of the unit and slide it down onto the hook at the bottom Make sure not to damage the power cable 4 3...

Страница 6: ...initial dust and dirt particles before they can get inside of the Air Medic similar to your HVAC equipment 5 1 1 2 Replacement Frequency The replacement frequency for the Prefilters can be found in Table 1 5 1 1 3 Replacement Instructions To replace the Prefilters when they are dirty they need to be removed To remove the Prefilters the lower access panel must be removed Lift out of the lower guide...

Страница 7: ...d then tighten the wingnuts 5 1 3 Activated Carbon Filter Optional Accessory 5 1 3 1 Description An optional accessory for the Air Medic is two 1 inch Activated Carbon Filters These filters make use of Activated Carbon to adsorb airborne particles to help with allergens and odours 5 1 3 2 Installation Instructions The Activated Carbon filters are installed on the intakes behind the Prefilters To i...

Страница 8: ...on the fan assemblies 5 3 1 2 Installation Instructions First remove the lower and upper access panel and then remove the HEPA filter Take the light ballast and align the tabs with the holes on the right fan bulkhead closest to the wall of the unit and screw them down with the provided Philips head screws Take supplied UVC mount assembly and align it with the four holes two on each bulkhead and wi...

Страница 9: ...ews Attach the ionizer quick connect to the 2 pin quick connect to the unit quick connect below the electrical cover Ensure they have a firm and properly sealed connection and that the locks have fully engaged 5 4 1 3 Maintenance Interval It is recommended that every six 6 months the ionizer being inspected for dust or dirt buildup on the brushes or indicator light If there is dust or dirt it shou...

Страница 10: ...l pressure switch This switch measures the pressure around the HEPA filter with the use of 1 4 tubing to let the operator know when the HEPA needs to be replaced When the pressure differential around the HEPA rises above the recommended level the switch will close and it will light the amber indicator light on the unit face 5 6 1 2 Maintenance Interval The switch is fully sealed and does not need ...

Страница 11: ...vated Carbon Filter 16 x 18 x 1 MERV 7 FPC 16118 1 year UVC Light 16 Watt EUL 01516 1 year Table 2 Unit Specifications TIF 06 TIF 08 Performance 450 CFM 600 CFM Purge Mode 450 CFM 800 CFM Purge Mode Electrical 120 VAC 2 6 FLA 6ft 2m Power cord 120 VAC 3 4 FLA 6ft 2m Power cord Fan Motor 250mm Backward Inclined Impeller fan with ECM 20 100 fan modulation 600C FM 1 2 TSP 285 s 300pa 280mm Backward I...

Страница 12: ...EMC 09004 CONSTANT SPEED FAN CONTROLLER EMC 09003 DOOR INTERLOCK SWITCH ESX 08000 DIFFERENTIAL PRESSURE SWITCH ESD 22000 CASTER WHEELS LOCKING WCX 51608 CASTER WHEELS WCX 51608 LIFT HANDLE VHX 01004 KEYED CAM LOCK NXL 01008 FAN BFE 025017 3 4IN FAN SCREW NSL 00306 IONIZER NUT NNX 21024A UVC THUMB NUT NNT 00202 CAM LOCK NXL 01010 3 4IN SCREW NSH 10206 1 2IN SCREW NSL 00304 CASTER LOCK WASHER NWX 21...

Отзывы: