Temspec Air Medic TIF-06 Скачать руководство пользователя страница 10

- 8 - 

5.5

 

Fan Assembly

5.5.1.1

 

Description 

The  air  medic  comes  with  two  high  efficiency  backward 
inclined fans. These fans modulate their speed based on the 
input control signal which varies from 0-10VDC, based on the 
controls selected in the Fan Control section.  

All  controls  within  the  fans  are  internally  sealed  and  do  not 
need any maintenance.  

5.5.1.2

 

Replacement Instructions 

To replace a  fan, first  open the lower access panel and then 
remove  the  fan  cover.  Disconnect  the  quick  connect  to  the 
desired  fan.  Remove  the  screws  holding  the  fan  to  the 
bulkhead and then remove the fan through the opening.  

To install the new fan, insert into the opening and align the fan 
with the holes on the bulkhead. Ensure the fan in oriented in a 
way  that  the  fan  quick  connect  will  reach  the  unit  quick 
connect. Tighten all screws on the fan and then reconnect the 
quick  connect.  Ensure  they  have  a  firm  and  properly  sealed 
connection, and that the locks have fully engaged. 

 

5.6

 

Differential Pressure Switch (Optional Accessory)

5.6.1.1

 

Description  

An optional accessory is the differential pressure switch. This 
switch measures the pressure around the HEPA filter with the 

use  of  1/4”  tubing

  to  let  the operator  know  when  the  HEPA 

needs to be replaced. When the pressure differential around 
the HEPA rises above the recommended level the switch will 
close and it will light the amber indicator light on the unit face.  

5.6.1.2

 

Maintenance Interval 

The switch is fully sealed and does not need any maintenance 
itself.  

Every  year  it  is  recommended  to  inspect  pressure  switch 
tubing to ensure they are a not kinked or clogged. 

5.6.1.3

 

Replacement instructions 

To  replace  the  Differential  Pressure  Switch,  first  remove  the 
lower access panel, and then disconnect the tubing attached 
to  switch.  Unscrew  the  switch  from  the  bulkhead,  removing 
the Prefilter and Activated Carbon Filter on that side my allow 
for easier access. Once the device is loose, open the cap and 
disconnect  the  wiring  inside,  then  remove  them  from  the 
switch.  

Open the remove the cap from the new switch, adjust the dial 
to 2-inch WC, feed the wires into the switch and attach them 
to terminals 2&3. Attach the cap and mount the switch to the 
bulkhead, ensure the tube ports are pointed down. Reattach 
the tubes, with the tube going below the HEPA on port 1, and 
the tube going above the filter onto port 2.  

 

 

Содержание Air Medic TIF-06

Страница 1: ...IOM 2020 0 2360 Millrace Court Tel 905 670 3595 Mississauga Ontario Fax 905 670 3592 Canada L5N 1W2 Web Temspec com Air Medic Air Filtration Sterilization Unit TIF 06 Installation Operation Maintenance Manual ...

Страница 2: ...nel 3 4 4 Motor Access Panel 4 5 Air Medic Component Installation Maintenance and Replacement Instructions 4 5 1 Filters 4 5 1 1 Prefilter 4 5 1 2 HEPA Filter 5 5 1 3 Activated Carbon Filter Optional Accessory 5 5 2 Casters Optional Accessory 6 5 3 UVC Light Optional Accessory 6 5 4 Ionizer Optional Accessory 7 5 5 Fan Assembly 8 5 6 Differential Pressure Switch Optional Accessory 8 6 Warranty Inf...

Страница 3: ...e hot and could cause serious burns if not handled properly Please wait until the lamp has cooled to room temperature to remove from the unit WARNING UV Light Hazard Harmful to skin and eyes Can cause temporary or permanent loss of vision Never look at the lamp while illuminated To prevent exposure to ultraviolet light be sure the power is disconnected before servicing CAUTION Ionizer generates hi...

Страница 4: ... switched This pressure switch measures the air pressure around the HEPA filter and when it is too high the indicator light will come on to warn the user it should be changed This is only a warning indicator The unit will continue to work with it on but the airflow will be decreased due to the dirty filter 3 3 Fan Control The fan control is available in either variable speed or constant speed conf...

Страница 5: ...el is equipped with two cam latches that turn to lock in place to secure the panel and the optional lock mentioned above To open the lower access panel unlock the cam lock turn the cam latches to the unlocked position and then pull up and out When replacing the panel align the panel with the width of the unit and slide it down onto the hook at the bottom Make sure not to damage the power cable 4 3...

Страница 6: ...initial dust and dirt particles before they can get inside of the Air Medic similar to your HVAC equipment 5 1 1 2 Replacement Frequency The replacement frequency for the Prefilters can be found in Table 1 5 1 1 3 Replacement Instructions To replace the Prefilters when they are dirty they need to be removed To remove the Prefilters the lower access panel must be removed Lift out of the lower guide...

Страница 7: ...d then tighten the wingnuts 5 1 3 Activated Carbon Filter Optional Accessory 5 1 3 1 Description An optional accessory for the Air Medic is two 1 inch Activated Carbon Filters These filters make use of Activated Carbon to adsorb airborne particles to help with allergens and odours 5 1 3 2 Installation Instructions The Activated Carbon filters are installed on the intakes behind the Prefilters To i...

Страница 8: ...on the fan assemblies 5 3 1 2 Installation Instructions First remove the lower and upper access panel and then remove the HEPA filter Take the light ballast and align the tabs with the holes on the right fan bulkhead closest to the wall of the unit and screw them down with the provided Philips head screws Take supplied UVC mount assembly and align it with the four holes two on each bulkhead and wi...

Страница 9: ...ews Attach the ionizer quick connect to the 2 pin quick connect to the unit quick connect below the electrical cover Ensure they have a firm and properly sealed connection and that the locks have fully engaged 5 4 1 3 Maintenance Interval It is recommended that every six 6 months the ionizer being inspected for dust or dirt buildup on the brushes or indicator light If there is dust or dirt it shou...

Страница 10: ...l pressure switch This switch measures the pressure around the HEPA filter with the use of 1 4 tubing to let the operator know when the HEPA needs to be replaced When the pressure differential around the HEPA rises above the recommended level the switch will close and it will light the amber indicator light on the unit face 5 6 1 2 Maintenance Interval The switch is fully sealed and does not need ...

Страница 11: ...vated Carbon Filter 16 x 18 x 1 MERV 7 FPC 16118 1 year UVC Light 16 Watt EUL 01516 1 year Table 2 Unit Specifications TIF 06 TIF 08 Performance 450 CFM 600 CFM Purge Mode 450 CFM 800 CFM Purge Mode Electrical 120 VAC 2 6 FLA 6ft 2m Power cord 120 VAC 3 4 FLA 6ft 2m Power cord Fan Motor 250mm Backward Inclined Impeller fan with ECM 20 100 fan modulation 600C FM 1 2 TSP 285 s 300pa 280mm Backward I...

Страница 12: ...EMC 09004 CONSTANT SPEED FAN CONTROLLER EMC 09003 DOOR INTERLOCK SWITCH ESX 08000 DIFFERENTIAL PRESSURE SWITCH ESD 22000 CASTER WHEELS LOCKING WCX 51608 CASTER WHEELS WCX 51608 LIFT HANDLE VHX 01004 KEYED CAM LOCK NXL 01008 FAN BFE 025017 3 4IN FAN SCREW NSL 00306 IONIZER NUT NNX 21024A UVC THUMB NUT NNT 00202 CAM LOCK NXL 01010 3 4IN SCREW NSH 10206 1 2IN SCREW NSL 00304 CASTER LOCK WASHER NWX 21...

Отзывы: