background image

Quick Start Guide for Equipment Touch and

LS-1628 Unit Controller, Standard 3.1.5 Program

Introduction

This start-up guide will guide you through the

necessary procedures to start-up the unit equipped

with an LS-1628 controller. Before turning on the

controller, be sure all wiring is completed and in

the proper location. All 

input

 connections (i.e. SAT

sensor) wire into the grey terminals located on the

bottom of the controller. All 

output

 connections

wire into the blue terminals located on top of the

controller. 

Refer to the wiring diagram included with

the unit for the connections specific to this unit.

If installing a zone or room sensor, wire to TB5

terminal blocks, these will be factory wired to the

controller’s Rnet port located on bottom-left of the

controller. 

Refer to the wiring diagram included with

the unit for the connections specific to this unit.

Figure 1: LS-1628 controller

Form Number: TPM54-SU2 (321) New Release

Issue Date: 2021-03-16

Содержание LS-1628

Страница 1: ...y terminals located on the bottom of the controller All output connections wire into the blue terminals located on top of the controller Refer to the wiring diagram included with the unit for the conn...

Страница 2: ...nostic The Standby screen shows the program name version number date of revision issue and the current operational condition mode of the unit i e UNOCCUPIED SCHEDULE is the initial condition Press the...

Страница 3: ...Tech settings Occupancy control SF min setting enable settings Admin Misc setup BAS ModStat config Admin Calibration Allows manual of sensor readings used for testing of unit and sensor calibration Ad...

Страница 4: ...l light when the current sensor closes for compressor 1 HPS1 and LPS1 should always have the light on FRZ1 will light when the DXLAT1 sensor is below 38 F Clg Mode will be on when OAT is above 55 F an...

Страница 5: ...occupancy control unit enable supply fan minimum run settings ZAT SAT reset on off emergency heat enable and many more Please refer to specific unit sequence of operation for specific run conditions...

Страница 6: ...d a zone sensor if needed The following four charts show all avaibable options for the four selectable drop down menus These options can be added to the unit or may have come from the factory Figure 1...

Страница 7: ...ents the current value the offset given This screen is used for testing purposes to enable an operational state or to calibrate a sensor reading Figure 16 Calibration screen Note The Calibration scree...

Страница 8: ...of the setpoint screens available from the Setpoints DB screen Figure 18 Cooling 1 setpoint These setpoints are all adjustable the sensor is NOT adjustable and is for information only Limits and safe...

Страница 9: ...by writing to manual occ control point occ enable 24 7 operation runs continuously unit does not have an unoccupied mode unless the occupancy enable is changed S S switch on off signal control could b...

Страница 10: ...recommend weekly schedules Leave the Date Range to NO Make sure to set the time to the hours for occupied schedule unless otherwise stated by customer 5 Click Save Schedule button on bottom of screen...

Страница 11: ...ekly view or daily Misc status screen The Misc Setup screen can be accessed by selecting the Misc Setup link from the Unit Status screen The Misc Setup screen includes navigating buttons for BAS setup...

Страница 12: ...t point by pressing the desired button A drop down menu will give you your choices 4 Press the button of your desired choice The select choice will appear on your button You may need to scroll by usin...

Страница 13: ...upied condition and place unit in occupied mode for a set period of time adjustable 30 minutes default 7 Manual Ovrd Select to manually force Occupied or Unoccupied Mode Figure 25 Occupancy control Se...

Страница 14: ...lures navigate to the Calibration screen by press the Setup link on the Home screen Now press the calibration link to display the Calibration screen Show all points Remember the unit will receive the...

Страница 15: ...points are for the modulation of the supply fan speed The supply fan will modulate to maintain the setpoint Default is 3900 cfm The SF setpoint may need to be adjusted check with your TAB contractor...

Страница 16: ...or the 10 minute countdown timer for the heating mode change over to cooling mode On the very bottom of the screen are links to other screens 6 Reheat HGRH screen The reheat displays that reheat is in...

Страница 17: ...re links to other screens 8 Dehumidification 1 screen The first line has the status of the OAT and the dehum lower limit setpoint see SOO The OAT must be above the lower limit setpoint and the OADP mu...

Страница 18: ...mer for the cooling mode change over to heating mode On the very bottom of the screen the type of heat is displayed You have completed the startup of the 100 Outside Air unit Before you leave make sur...

Страница 19: ...should be set to no The rotary switch on the controller located in the upper left corner need to be set to the proper protocol 1 MSTP 2 ARCnet contact the FMOC for correct BACnet Device Instance numbe...

Страница 20: ...ecords 3 low pressure start restart failure incidents within 1 hour compressor 1 is locked out and the controller will issue an alarm The compressor lock out can be reset in the EQ2 display pad or by...

Отзывы: