Blizzard Enclosure User Manual 

 

page 27 

STATUS DISPLAY 

View current status information, using the arrow keys to scroll through: 

a)

 

Humidity – relative humidity in % 

b)

 

Firmware version 

c)

 

Lamp Hours elapsed 

d)

 

Current being drawn by projector/light fixture, in amps 

e)

 

PCB temperature 

f)

 

Air temperature, in degrees C or F (note that sensor is placed in the exhaust 

airflow in Tornado enclosures and may be higher than the temperature being 

‘seen’ by the fixture body or electronics) 

RESET LAMP HOURS 

The lamp hour counter needs to be reset each time you change the lamp in the 

fixture/projector. Make this a part of your maintenance instructions. 

HUMIDITY SET 

The humidity level above which the heater kicks in to remove humidity from 

incoming air (default 80%, permissible range 50-90%). 

SET FAN OVERRUN 

The fan will continue to run for a time after the internal fixture has gone to standby. This 

facility allows the heat built up in the fixture to dissipate before the DEC3.2 resumes 

normal maintenance of the enclosure. 

(default 5 minutes, permissible range 0-15 minutes) 

SET TEMP RANGES 

Set three temperature trigger points for Bottom, Top and Cutoff temperatures. 

TEMP BOTTOM 

The desired lower temperature limit for normal operation  

(default 10°C, permissible range 0-10°C).   

TEMP TOP 

The desired upper temperature limit for normal operation  

(default 40°C, permissible range 35-45°C).  

When the DEC3.2 sees air above this temperature, but below the additional Cutoff 

temperature (see below), it indicates a temperature error. This is not dangerous. 

TEMP CUTOFF 

The desired upper temperature ABOVE the TOP TEMP setting, at which the lamp relay is 

forced to open, isolating the fixture/projector power.  

(default 15°C, permissible range 0-15°C).  

To avoid nuisance tripping, set this variable to the maximum, and monitor actual 

temperatures in your normal operating conditions. If your actual temperatures are 

Содержание Blizzard DEC3.2

Страница 1: ...ll Fan only Blizzard Enclosures Includes supplement covering DEC3 control enclosures manufactured prior to September 2011 In the interest of continuous product improvement the information in this docu...

Страница 2: ...tch Force cooled 230V are in Compliance with the following standards or specifications according to the EMC Directive 89 336 EEC EN55015 EN61000 3 4 EN61000 3 5 EN61000 4 2 EN61000 4 3 EN61000 4 4 pr...

Страница 3: ...led 230V 6566 US Blizzard X Stretch Force cooled 230V Have been tested and approved to standards UL 508 electrical and UL 50 environmental as NEMA 3R enclosures for use in the United States and Canada...

Страница 4: ...d Warnings 2 1 Tools and Equipment 2 2 Mounting the Enclosure 2 3 Base up or Base down Operation 2 4 Mounting the Projector 2 5 Wiring 3 Wiring for Fan Only Versions 3 2 DEC3 2 Versions Wiring and Con...

Страница 5: ...00 Baby Blizzard Force cooled 6505 Baby Blizzard Force cooled Low noise 6510 Baby Blizzard DEC 3 2 6515 Baby Blizzard DEC3 2 Low noise 6550 Blizzard DEC3 2 Enclosure Control 6555 Blizzard Stretch DEC3...

Страница 6: ...Enclosure User Manual page 6 1 1 Dimensions and Weight Baby Blizzard Enclosure Weight 29lb 13kg 1 2 Maximum Projector Dimensions and Power Maximum Projector Power Standard Versions 700W Low Noise Vers...

Страница 7: ...ontrol 120V 49 124cm 51 130cm 16 41cm 12 30cm 42 107cm 26 66cm 106lb 48kg 6556 IN Blizzard X Stretch DEC3 Enclosure Control 230V 49 124cm 51 130cm 16 41cm 12 30cm 42 107cm 26 66cm 106lb 48kg 6560 US B...

Страница 8: ...has been shut off to all supply lines to the enclosure including the one powering the projector Do not open the enclosure in wet weather 2 2 Tools and Equipment To install the enclosure you will need...

Страница 9: ...losure 4900 MB Stainless Steel Unistrut channel nut bolt and washer Four required per enclosure 4900 MC Stainless Steel Unistrut channel nut bolt and pipe clamp for pipes 1 5 38mm to 2 50mm OD Four re...

Страница 10: ...the projector to be used supports this feature usually referred to as Ceiling Mount mode before commencing installation Air vents for Base up operation When the Blizzard is used base up remove the fr...

Страница 11: ...eld before proceeding further Note You can still adjust the projector pan and tilt by loosening the projector clamp adjusting the projector feet then re tightening the projector clamp to hold the proj...

Страница 12: ...t to the FAN terminals inside the enclosure passing the fan cable through the rubber grommet in the side of the electrical cover 4 Attach one end of the hose to the hose adapter plate using one of the...

Страница 13: ...ints suitable for flexible conduit fittings US size international 20mm Note the locations of the cable entry fittings on the rear panel 3 All junction boxes must be installed in accordance with local...

Страница 14: ...below Feed the projector power cable through the grommeted hole in the electrical cover and terminate as shown in the wiring diagrams below Replace the electrical cover taking care not to pinch any of...

Страница 15: ...System DEC3TM Your enclosure has DEC3 control if you see a control panel on the rear surface like this IMPORTANT Blizzard enclosures manufactured from September 2011 ship with DEC3 2 control described...

Страница 16: ...vice Management if desired Unless otherwise specified this version of the user guide refers to DEC3 2 units fitted with software version 0 1 xxx or later So what does DEC3 2 actually DO The DEC3 2 Eng...

Страница 17: ...ans to change the enclosure air every 30 seconds or so We call this pulse mode and it is the key to preventing damaging condensation inside your equipment If the temperature rises above the top set li...

Страница 18: ...control of the Lamp Relay using a single DMX slot at the address configured as the DEC3 2 DMX start address A DMX slot value level 75 will cause the fixture to be powered and less than 25 will disconn...

Страница 19: ...Range 0 15 C Default 15 C This is a setting above the Top Set temperature that determines the temperature at which the lamp relay is opened cutting off power from the fixture projector User may reduc...

Страница 20: ...t Lamp Hours Default 0000 DEC3 2 counts the hours your projector fixture lamp is on and can report it both on the user interface display and over RDM Remember to reset to 0 when changing lamps This is...

Страница 21: ...minations Pinout 1 Ground 2 Data 3 Data The picture shows the 4 DMX connections on the controller The incoming DMX feed should always be wired to DMX IN 1 If the enclosed projector shares the DMX sign...

Страница 22: ...TANT Tempest enclosures are supplied for either 120VAC 50 60Hz or 208 240VAC 50 60Hz operation Tempest Lighting is not liable for damage or failure to operate correctly due to connection to an inappro...

Страница 23: ...tral Split Feed Operation Split Feed allows you to run the projector light fixture independently of the enclosure The enclosure must be powered 24 7 DEC3 2 normally ships from the factory with circuit...

Страница 24: ...X Personality RDM Mode Device Type Device Label Software Version RDM is an effective and powerful tool for commissioning and monitoring an installation particularly in large systems For further guidan...

Страница 25: ...re as part of the condensation prevention strategy The fan comes on for a few seconds approximately every 30 seconds ON Green Fan is running due to lamp being on or internal temperature exceeding top...

Страница 26: ...ENU SET DMX ADDRESS in Monitor DMX or Service modes Select a DMX starting address in the range 001 to 510 1 Lamp Relay In Service Mode an addition two slots are available 2 Fan Relay 3 Heater Relay No...

Страница 27: ...he internal fixture has gone to standby This facility allows the heat built up in the fixture to dissipate before the DEC3 2 resumes normal maintenance of the enclosure default 5 minutes permissible r...

Страница 28: ...is displayed will depend on the RDM interface used The following screen shots were taken running the GetSet program in Windows 7 and connecting to a DEC3 2 controller using a RDM TRI MK1 interface bot...

Страница 29: ...Tempest enclosures and all other RDM devices you plan to use on the same network Firmware Upgrade over RDM DEC3 2 firmware is now field upgradeable using RDM A field upgrade requires a JESE RDM TRI MK...

Страница 30: ...y of the user to ensure that the fan is running at all times when the projector lamp is on Unless the enclosure or projector is undergoing routine maintenance the enclosure should be closed and secure...

Страница 31: ...ed to it the fan will start to turn Make sure that your hands are clear of the fan before applying power to the enclosure Only authorized personnel should perform maintenance on the enclosure or proje...

Страница 32: ...hose to clean the case Window As Needed Clean using a proprietary glass cleaning solution or a mild detergent and wipe dry Use only soft lint free cloths for glass cleaning Never use an abrasive clea...

Страница 33: ...sure and check for obstructions Turn power back on to see if fan will start spinning If fan does not turn then enclosure is not receiving power Turn off all power and check wiring If the wiring is cor...

Страница 34: ...aragraph A above ii to any Goods that have been subject to misuse abnormal service or handling or altered or modified in design or construction iii to any Goods repaired or serviced by any person othe...

Страница 35: ...respond quickly to your needs Step 2 If your dealer is unable to answer your questions please contact our Sales Office Tempest Lighting Inc 13110 Saticoy Street North Hollywood CA 91605 USA Tel 1 818...

Страница 36: ...orm on the next page and sending it to the Tempest Lighting factory within 30 days of installation entitles you to the warranty cover specified in this manual It also enables us to notify you in case...

Страница 37: ...a Tempest Representative has not inspected the installation please send photos showing installation Model Number Serial Number Padlock Key Number Dealer Sold By Name Location Date Purchased Contracto...

Страница 38: ...light fixture to be enclosed Customers wishing to provide independent electrical feeds to the enclosure and the projector fixture must follow the instructions below Feeder Connections Common Feed Fee...

Страница 39: ...d at the same supply voltage 3 1 DMX Connections DMX refers to USITT DMX512 a commonly used control protocol in the entertainment industry running over RS485 Consult USITT DMX installation guidelines...

Страница 40: ...prevent condensation particularly overnight dew formation inside the equipment housed Condensation is fatal to electronic equipment particularly in polluted areas or saline environments where it brin...

Страница 41: ...inate condensation and runs the fans to change the enclosure air every 30 seconds or so We call this pulse mode and it is the key to preventing damaging condensation inside your equipment If the tempe...

Страница 42: ...the user is responsible for maintaining a DMX input with the slot as selected as the DMX START ADDRESS on the DEC3 high This slot level must be set greater than 50 at all times when the internal fixtu...

Страница 43: ...fer only basic guidance on RDM utilization DEC3 Control Parameters DEC3 will run out of the box with its default parameter settings which equate to the fixed settings of its predecessor DECs 1 and 2 T...

Страница 44: ...ge 001 510 Default 001 Sets the DMX address for the lamp relay control In the DMX RDM service mode the subsequent two DMX slots control fan and heater respectively Lamp Hours Default 0000 DEC3 counts...

Страница 45: ...same as DMX IN DMX Line Terminations DMX cable runs must be terminated at the far end of the cable run with a termination resistor as detailed in the DMX standard This is particularly important for sa...

Страница 46: ...te Device Management is an ANSI standard that adds bidirectional discovery and status monitoring to a standard DMX network connection No additional wiring is required for RDM operation DEC3 s RDM impl...

Страница 47: ...few seconds approximately every 30 seconds ON RED Indicates fan is running due to lamp being on or internal temperature exceeding top limit Lamp Relay ON RED Indicates lamp relay closed and power is...

Страница 48: ...running because of Overtemp the DMX input cannot turn them off and so on The DMX SET menu can be ignored if the DEC3 is in Standalone or DMX RDM Mode 1 RDM Monitor mode SET LAMP HOURS TO 0 The lamp ho...

Страница 49: ...y reduce the cutoff temperature margin In hot climates it may be advisable to set both TOP TEMP and CUTOFF TEMP as high as possible BOTTOM TEMP The desired lower temperature limit for normal operation...

Отзывы: