T30 SERIES PID Controller
User's Manual
DIGITAL PID CONTROLLER
SERIES
T30
PID cont Timer
Hybrid
Страница 1: ...T30 SERIES PID Controller User s Manual DIGITAL PID CONTROLLER SERIES T30 PID controller Timer Hybrid ...
Страница 2: ...he up key while pressing the set key in any setting menu you can move to the corresponding upper menu and move to the desired menu immediately F u n c t i o n o f m e n u r e t u rn sEt n General Setting group ORG 1 Initial setting group iosE 2 Input output Setting group Enhance hot key between group menus ...
Страница 3: ...his manual The contents of the manual may be changed without notice The product is designed to be used installed on a control panel This manual is copyrighted and may not be copied in part or in whole without permission The manufacturer takes no responsibility for direct or indirect damages caused by careless operation or operation under unpredictable or risky environments Safety requirements are ...
Страница 4: ... Observe the rated voltage and specification It may cause a fire or shorten the controller s life Turn off the power during wiring and maintenance to avoid an electric shock Be careful that any of foreign materials do not inflow into the controller It may cause a fire or malfunction of the controller Do not touch the terminals when it is power on It may give an electric shock Do not give direct vi...
Страница 5: ...1 Setting mode 12 Alarm ALARM1 2 3 setting 13 Details explanation of primary function 1 Auto tuning AT function 2 Manipulated variable Mvn check mode 3 Alarm ALARM1 2 function 4 Retransmission output 5 Input function 6 Selection function for Hysteresis 7 SV1 2 set up control by external contact signal 8 Set value LOCK function 9 Error indication during operation 14 SOAK alam and Timer output 1 SOA...
Страница 6: ... SERIES 0 RELAY output 1 Alarm output 2 SCR 4 20mA SSR Voltage pulse 1 RET 4 20mA Retransmission output D I SV2 3 External input RELAY output 1 Alarm output 2 SCR 4 20mA SSR Voltage pulse 1 RET 4 20mA Retransmission output D I SV2 3 External input RELAY output 1 ALARM or MAIN SCR 4 20mA SSR Voltage pulse 1 RELAY output 1 Alarm output 2 SCR 4 20mA SSR Voltage pulse 1 No function Basic function S0x ...
Страница 7: ... 24V AC or DC 2 Example of model building 4 Power supply voltage 6 4 S 0 0 T34 S00 7 S 3 0 T37 S30 Ex T34 S00 Ex T37 S30 1 Size 48 W x 48 H x 77 D 1 Size 72 W x 72 H x 77 D 3 Optional function Basic function 3 Optional function DI SV1 2 RET 2 Control mode SINGLE 2 Control mode SINGLE 4 Supply voltage 100 240V AC 4 Supply voltage 100 240V AC ...
Страница 8: ...C mV DC 200 1370 199 9 999 9 200 1000 199 9 999 9 200 1000 199 9 999 9 199 9 400 0 0 1700 400 1800 0 1700 200 900 199 9 900 0 200 1300 199 9 400 0 0 2300 0 2400 199 9 500 0 200 500 199 9 640 0 200 640 0 100 mV DC 10 20 mV DC 1 5 V DC When using current input use the resistor 250 on input terminal Input type Input Setting Code Temperature range Remarks Accuracy Thermocouple T C RTD Current When usi...
Страница 9: ...default value at the point of manufacture SCR output of PID control 4 20mA current output Output setting number 2 This setting is used mainly with thyristor power regulator TPR modules and is capable of precision control Relay output of PID control Output setting number 3 This is the most cost efficient method of implementing PID control and is used mainly with magnetic switches electric switches ...
Страница 10: ... mm Dimensions 2 T33 96x48 mm Dimensions 3 T34 48x48 mm Dimensions 9 T32 T33 96x48 Panel cutouts Unit mm Unit mm 45 0 5 92 0 5 Min 30 Min 20 T34 48x48 Panel cutouts Min 17 Min 17 45 0 5 0 45 0 5 0 48 0 96 0 10 0 77 0 96 0 91 0 96 0 48 0 48 0 43 6 10 0 77 0 8 8 48 0 44 9 48 0 77 0 48 0 ...
Страница 11: ...LLER 4 T37 72x72 mm Dimensions 5 T39 96x96 mm Dimensions 10 Unit mm Unit mm T37 72x72 Panel cutouts Min 20 68 0 5 68 0 5 Min 30 T39 96x96 Panel cutouts Min 20 92 0 5 92 0 5 Min 30 72 0 9 0 77 0 72 0 67 0 72 0 96 0 77 0 96 0 91 0 10 0 96 0 ...
Страница 12: ...rd until it fits tightly to the panel and secure Bore a hole in the panel referring to the panel cutouts on the previous page Insert this device into the front of the panel Insert 2 brackets one each on the B K holes on the top and the bottom of the device Secure using screws on the two locations at top and bottom 11 figure 1 Top side figure 2 Bottom side figure 3 Fixing completion Hole of fixing ...
Страница 13: ...www temcoline com DIGITAL PID CONTROLLER 4 Terminal arrangements and Wirings 1 T32 48x96 mm T33 96x48 mm 2 T34 48x48 mm 12 T32 T33 T34 Option 1 T34 S1x Option 3 T34 S3x OPTION T32 33 T3 2017 5 T5 N C ...
Страница 14: ... output mode Terminal OUT1 only for output selection no 1 2 SSR SCR output mode Terminal RET Retransmission 4 20mA or for power of sensor SPS DC 15V Terminal Power supply terminal Terminal Alarm1 output terminal Terminal Alarm2 output terminal Terminal The external D I input terminal may be used when DIS ON and the target value may be controlled SV1 SV2 Terminal Input terminals 13 OPTION Option 3 ...
Страница 15: ...Pt100 DIN Current input A 4 20mA DC Voltage input V 1 5V DC 10 20mV DC 0 100mV DC Rating 100 240V AC 50 60Hz voltage operating range 85 265V AC Option Rating 24VAC or DC voltage operating range 20 28V DC 1c 250V AC 3A resistance load electric lifespan 100 000 time proportional PID output or ON OFF output 4 20mA DC load impedance 600 resolution 1 4 600 PV process value SV set value MV manipulated v...
Страница 16: ...ey SV2 display lamp SV2 display lamp Set value Up key Alarm output lamp Alarm output lamp Function key Shift key Set value down key Set value up key Display the process value red color Flash every 0 5 second during auto tuning Display the set value codes and modes Lights when the control output is ON Lights when the SV2 is displayed Lights during the alarm is ON Use to shift the digits Use to decr...
Страница 17: ...LARM1 2 3 DI SV1 2 ALARM1 2 01 K Type 200 1370 02 K type 199 9 999 9 33 mV DC 0 100 mV 16 The default input and output values of the product at the point of manufacture are as follows Input K Type Code No 1 Output SSR Code No 1 0 RELAY ON OFF control 1 SSR VOLT PULSE PID control 2 SCR 4 20mA PID control 3 RELAY PID control When selecting SSR 1 SCR 2 output mode only for model T34 S00 no option ala...
Страница 18: ...에 해당되는 처음의 위치로 순간 이동됩니다 0 5초 이상 5 오토튜닝 단축 키 다이렉트 메뉴이동 및 진입 키 단축 키 지원 템코라인 T30은 사용자 편의를 위해서 단축 키 Hot Key 를 지원합니다 1 기본 설정메뉴 진입 키 2 AT 미 실행 시 입 출력 설정모드 진입 단축 키 3초 이상 3 초기설정모드 진입 단축 키 3초 이상 한번클릭 4 순간이동 키 로 임의의 설정메뉴 위치에서 SET 키를 누른상태에서 UP 키를 한번 클릭하면 현재의 메뉴에 해당되는 처음의 위치로 순간 이동됩니다 0 5초 이상 5 오토튜닝 단축 키 다이렉트 메뉴이동 및 진입 키 단축 키 지원 템코라인 T30은 사용자 편의를 위해서 단축 키 Hot Key 를 지원합니다 1 기본 설정메뉴 진입 키 2 AT 미 실행 시 입 출력 설정모드 진...
Страница 19: ...iable 0 100 at operating menu The method for input and output setting menu before auto tuning Press key more than 3 seconds Entering into input output setting menu Even if PID control output 1 2 3 is selected ON OFF control mode can also be used when P value is OFF 0 100 mV DC 10 20 mV DC 1 5 V DC 33 32 30 INPUT V DC mV DC CODE INPUT RTD TEMP RANGE 20 22 21 23 199 9 500 0 200 500 199 9 640 0 200 6...
Страница 20: ...N Return to the operating menu Will return automatically more than 3 sec After auto tuning has done of T30 series models to avoid any user s mistake input output setting menu is restricted automatically But you can change input output by following ways However unit will be returned to factory default when changed input type more than 3 sec Press more than 3 seconds at the inital set before running...
Страница 21: ...se refrain from operating the keys while auto tuning is in progress Enter to setting mode by key Set a desired value by key Store a value by key AT operation start 0 5 second AT stop by perforce 0 5 second 순간이동기능 초기설정 그룹 ORG 1 임의의 위치 설정 메뉴에서 SET키를 누른상태 에서 UP키를 누르면 해당되는 상위 그룹 메뉴로 순간이동하여 빠르게 원하는 메뉴로 이동할 수 있습니다 편리한 기능 순간이동 기능을 사용하면 설정속도가 최대 10배까지 빨라 집니다 Function of menu return Useful Features Use the...
Страница 22: ... Flow Chart Parameter structure To enter Input Output settings by IOSE on is valid for only time If you want to enter Input Output settings again you must turn on IOSE first If there is no Key action the IOSE will be OFF automatically in 50 seconds ...
Страница 23: ...LAY ON OFF control ON OFF control ALARM1 No 21selection Use retransmission and select PV or SV Use Alarm 2 Always PID control PID control PID control OFF 1 6000 sec OFF 1 6000 sec 5 0 105 0 1 1000 sec EUS 0 100 HALF NORMAL OFF 1 9999 sec TC RTD _IN H _IN L DCV IN _SL H _SL L But RET H RET L Set value 1 SV1 setting Set value 2 SV2 setting Set value of alarm 1 AL1 Set value of alarm 2 AL2 Selection ...
Страница 24: ...e only 0 3 1999 9999 But SL H SL L Decimal point positioning by _DPP OFF 1 21 LBA See alarm type REV Heating DIR Cooling I O setting entry switch IOSE Set highest input range _IN H Set lowest input range _IN L Set input digital filter value _FLT Input value correction _INS Input temperature unit selection Fixed Celsius Correcting upper limit Gain of input _ING Select the decimal point position in ...
Страница 25: ... OFF switch Retransmission type or SPS selection Set data protection 3 In Output setting mode The input output setting mode is a parameter for the first time use It s a hardware configuration so requires special user caution That is the configuration is determined by the type of equipment and it must be configured first all parameters are initialized according to the entered input type When the in...
Страница 26: ...he T30 series supports operation start stop function during inverter control 4 20mA to enable more stable control and solve the problems of lifetime and power saving of peripheral devices When the low limit alarm is used if the temperature before the power supply is lower than the set value unnecessary low limit alarm occurs until the normal control temperature is reached At this time when the hol...
Страница 27: ...pper Lower limit deviation with hold Upper Lower limit deviation in range Upper Lower limit deviation in range with hold CODE NO ALARM TYPE ALARM OUTPUT OPERATION 01 09 1 1 19 02 10 12 20 03 05 13 15 04 06 14 16 07 17 08 18 Low When temperature is falling When temperature is rising OFF ON ON Alarm setting value High ON Hysteresis OFF OFF Low High OFF OFF OFF ON ON ON Temperature When temperature i...
Страница 28: ...lamp flash every 0 5sec Do not use auto tuning under below Process Rapid control Process such as Flow input control Process which should not ON OFF output even a temporary Process which should not over load at control 2 Manipulated Variable Mvn check mode Refer to P18 19 I O Set Mode Operation mode Setting method In condition of Mvn ON Mvn display screen Present Mvn Out 85 AT operation start 0 5 s...
Страница 29: ...imes of integral times Control loop break alarm consists to alert you Control loop break by detect Variation during setting time when P I D calculations On time period of output is 0 or 100 ⅰ When P I D calculations stays 100 more than LBA setting time Break alarm will be turned on if calculations is not increase more than 2 In positive action will turned on if calculations does not fall more than...
Страница 30: ...Power supply for external sensor Scale setting can on retransfer output se Cause of activation LBA will activate below condition ⅰ Abnormalities of the control target Heater break No supply voltage Wrong wiring etc ⅱ Abnormalities of the sensor Disconnection short circuit of sensor ⅲ Abnormalities of the handling tools Splice relay wrong wiring etc ⅳ Abnormalities of Output circuit Spliced relay i...
Страница 31: ...The user may set ranges units and decimal point position as desired This can be used not only for temperatures but also for a number of other measurements including humidity pressure and weight 3 Correcting upper limit of input vlaue _ING 4 Setting decimal point position _DPP and free scale high and low limits SL H SL L Use only in voltage input current 4 20mA mode This can accurately correct the ...
Страница 32: ...D value with the other Please use a non voltage contact relays switches for direct input If a non contact device such as a semiconductor are used please operate within the ranges ON 1K OFF 100K ON SV1 Select OPEN SHORT SV2 Select Use SV1 2 by external contact _dis ON SV Action External terminal status Block external contact signal Can select under inside menu only OFF T30 series can select Hystere...
Страница 33: ...e refer to input group setting or overcooling SYS E SYSTEM setting error or Memory damage request for repair RJC E RJC Sensor damage or PCB burn request for repair EEP E EEPROM damage request for repair COM E Communication ERROR request for repair AT E Auto Tuning Error Checking heater break or controller 1 Alarm type setting When the alarm 2 Alarm2 is set to timer output the digit shift key and e...
Страница 34: ... OFF Start Stop or D I 1 5 sec Run Timer 1 45 0 00 ON Run Timer 1 45 0 00 ON Timer 1 45 0 00 1 min 45 s ON Timer 1 45 0 00 ON OFF ON ON AL2 OFF Reset S W or D I 1 5 sec ON Timer 1 45 0 00 OFF 70 sec ON OFF ON ON AL2 OFF 선택코드 21 정접 경보설정 선택코드 22 역접 Timer output Time Set T1 Alarm 2 Timer output Time Set T2 Alarm 2 Timer output On Off Time Set T4 Alarm 2 Timer output T5 Alarm 2 Stop Start Not valid No...
Страница 35: ...TEMCOLINE Co Ltd Misung Bldg 217 1 Gurojungang ro Guro gu Seoul 08216 Korea Tel 82 2 3667 5521 Fax 82 2 2632 5549 E Mail sales temcoline com www temcoline com Rev 301701 01 ...