Telguard TG-7FP Installation & Operating Guide
9
56052401 Rev A
Installation
Summary
The following are steps necessary to install the communicator properly.
NOTE: IF YOU DO NOT PROCEED IN THE ORDER AND MANNER PRESCRIBED, YOU MAY NOT
COMPLETE THE INSTALLATION IN THE TIME DESIRED.
These steps are summarized below and explained in detail in the remainder of this manual.
1.
Register for Telguard service
2.
Physically install the TG-7FP device
•
Mount the TG-7FP device in desired location
•
Complete all power-related wiring connections
3.
Determine antenna placement for best performance
•
Connect antenna
•
Measure Received Signal Strength (RSSI)
•
Consider other antenna options
4.
Connect to Panel DACT and Activate
5.
Connect supervisory trip outputs
6.
Connect trip input (optional)
7.
Connect Tamper Switch (required for burglary systems; optional for fire systems)
This installation approach provides the alarm installer with the easiest and fastest method of
properly installing a TG-7FP device. Please follow the instructions carefully and if you should need
assistance or have any questions, please call Telguard Technical Support at 1-800-229-2326
extension 9.
NOTE: Dealer Account Establishment and Telguard Registration must be complete prior to
Installation.
Step 1: Register the Telguard Communicator
Installation Tip: Register for Telguard service prior to leaving for the job site to avoid a second
trip.
The registration form may be completed online through our 24/7 dealer portal
The desired features and programmable options for any installation are selected during the
registration process. This includes STC strategy, Trip-Input enabling, and added value services like
HomeControl Flex and Standard Line Security.
UL/ULC Commercial Fire Sole Path Features
•
Link Supervision: When registering a TG-7FP device for commercial fire applications, use the
link supervision option in accordance with local requirements (5-minute supervision or
60-minute supervision in the U.S. or 180-second supervision in Canada).
•
End-to-End Acknowledgment feature: When enabled an RFC condition will occur when the
captured signal is not delivered to the Central Station as expected.