background image

8

Discharge

- Building Regulations:

Discharge pipes must be installed in accordance with the latest edition of the Building Regulations.  

Discharge Pipes

The discharge pipe (D1) from the vessel up to and including the tundish is generally supplied by
the manufacturer of the hot water storage system (see paragraph 3.5). Where otherwise, the
installation should include the discharge pipe(s) (D1) from the safety device(s). In either case the
tundish should be vertical, located in the same space as the unvented hot water storage system
and be fitted as close as possible and within 500mm of the safety device e.g. the temperature relief
valve.
The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk 
to persons in the vicinity of the discharge, be of metal and:

a.

be at least one pipe size larger than the normal outlet size of the safety device unless its total
equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e. discharge pipes
between 9m and 18m equivalent resistance length should be at least two sizes larger than the
nominal outlet size of the safety device, between 18 and 27m at least 3 sizes larger, and so on.
Bends must be taken into account in calculating the flow resistance. Refer to Diagram 1, Table
1 and the worked example. An alternative approach for sizing discharge pipes would be to
follow BS 6700: 1987 

Specification for design installation, testing and maintenance of

services supplying water for domestic use within buildings and their curtilages, Appendix E,
section E2 and table 21.

b.

have a vertical section of pipe at least 300mm long, below the tundish before any elbows or
bends in the pipework.

c.

be installed with a continuous fall.

d.

have discharges visible at both the tundish and the final point of discharge but where this is not
possible or is practically difficult there should be clear visibility at one or other of these
locations. Examples of acceptable discharge arrangements are:

i.

ideally below a fixed grating and above the water seal in a trapped gully.

ii.

downward discharges at low level; i.e. up to 100mm above external surfaces such as car parks,
hard standings, grassed areas etc. are acceptable providing that where children may play or
otherwise come into contact with discharges a wire cage or similar guard is positioned to
prevent contact, whilst maintaining visibility.

iii.

discharges at high level; e.g. into a metal hopper and metal down pipe with the end of the
discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high
temperature discharges of water and 3 m from any plastics guttering system that would
collect such discharges (tundish visible).

iv.

where a single pipe serves a number of discharges, such as in blocks of flats, the number served
should be limited to not more than 6 systems so that any installation discharging can be traced
reasonably easily. The single common discharge pipe should be at least one pipe size larger
than the largest individual discharge pipe (D2) to be connected. If unvented hot water storage
systems are installed where discharges from safety devices may not beapparent i.e. in 
dwellings occupied by blind, infirm or disabled people, consideration should be given to the
installation of an electronically operated device to warn when discharge takes place.

Note:

The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic
rainwater goods may be damaged by such discharges.

NEW TORNADO/TEMPEST 25336  19/4/05  12:25 PM  Page 15

Содержание Tempest Stainless

Страница 1: ...TER MANUFACTURERS ASSOCIATION Tel 01952 257963 Fax 01952 253452 Furrows Business Park Haybridge Road Wellington Telford Shropshire TF1 2FE www telford group com NEW TORNADO TEMPEST 25336 19 4 05 12 25 PM Page 1 ...

Страница 2: ...PRODUCTS STAINLESS Tornado Tempest Stainless Installation Guide NEW TORNADO TEMPEST 25336 19 4 05 12 25 PM Page 2 ...

Страница 3: ...ING TO INSTALLER This installation is subject to building regulation approval notify Local Authority of intention to install Use only manufacturer s recommended replacement parts Installed by Name Address Tel No Completion Date Water Supply Pressure Max 12 Bar Min 1 5Bar Electric Immersion Heaters 14 3kW 230V AC Operating Pressure 3 BAR Expansion Vessel charge Pressure 3 BAR Expansion relief valve...

Страница 4: ...d First Annual Service Third Annual Service Fourth Annual Service Fifth Annual Service Sixth Annual Service Seventh Annual Service Eighth Annual Service Ninth Annual Service Tenth Annual Service PRODUCTS STAINLESS NEW TORNADO TEMPEST 25336 19 4 05 12 25 PM Page 4 ...

Страница 5: ... clear debris If discharge does not stop replace expansion relief valve Check setting and operation of cylinder thermostat 55 65o C Replace if necessary Check mixer taps and shower valve and fit check valves or area pressure controls if required Alternatively supply cold water to mixer tap or shower valves from balanced supply position on inlet control set Recharge or replace Water fails to heat N...

Страница 6: ...3 Tornado Stainless Tempest Stainless NEW TORNADO TEMPEST 25336 19 4 05 12 25 PM Page 6 ...

Страница 7: ...st Stainless mains pressure systems require an annual safety check by a competent person Failure to carry out this safety check may invalidate the warranty Use only approved DZR brass compression fittings for cylinder connections STEP 2 Measure the area in which you plan to install the Tornado and Tempest Stainless and ensure that the floor can support the weight of the cylinder when full Heat up ...

Страница 8: ...13 PIPE WORK LOGIC LAYOUTS S PLAN SYSTEM CYLINDER VALVE HEATING VALVE NEW TORNADO TEMPEST 25336 19 4 05 12 25 PM Page 8 ...

Страница 9: ...DER VALVE 8 2 10 9 GRY B N GRY B 2 10 5 9 N HEATING VALVE THE BOX NUMBERS INDICATE THE POSITION ON WIRE CENTRE COLOUR CODES BROWN BR ORANGE ORG GREY GRY BLUE N NEUT EARTHS ARE NOT DRAWN INSTALL AS NECESSARY NOTE THE CONTROLS PROVIDED MUST BE USED ONE IMMERSION HEATER REQUIRES A 16 AMP SUPPLY TWO IMMERSION HEATERS REQUIRE A 32 AMP SUPPLY FAILURE TO INSTALL WILL INVALIDATE GUARANTEE DRAWING SHOWS S ...

Страница 10: ... valve which reduces the pressure to 3 0 bar this is factory set and should not be adjusted and then through the expansion valve factory pre set to 5 0 bar The Inlet Control Group also includes a single check valve and filter NB Upon commissioning if the incoming pressure is less than 3 0 bar the expansion vessel pressure should be adjusted to 0 2 bar less than the incoming water pressure Ensure t...

Страница 11: ...ial part of the safety requirements for indirect mains pressure cylinders and should be installed on the primary flow to the cylinder with port B embossed on side of valve body to the cylinder The valve will open and close on receiving a signal from the cylinder thermostat No further control is required for the hot water in a two zone valve system This valve must also be used in a flow share Y Pla...

Страница 12: ...ater control valves cylinder thermostat and energy cut out valves are guaranteed for two years from the date of manufacture This guarantee is only available in the United Kingdom of Great Britain and Northern Ireland Claims made against our Lifetime Guarantee must be supported with evidence of purchase and the product serial number along with a copy of the completed Benchmark Log Book Your Statuto...

Страница 13: ...en fitted to the cylinder ensuring that the threads are sealed appropriately Checking for back pressure Back pressure from a faulty or uncontrolled mixer valve or appliance will cause the cylinder to over pressurise and may result in water being discharged from the expansion valves To check for back pressure follow the steps below Turn off cold water supply to cylinder whilst leaving cold supply t...

Страница 14: ...ll the unit until water runs continuously from all of the open taps Open the service valve fully and close all hot taps Check for leaks Heat the water to 60o C Once the desired temperature has been reached the cylinder should be isolated and drained to flush out any flux solder introduced during the installation process The filter in the inlet control set should be removed cleaned and re fitted se...

Страница 15: ...ipework c be installed with a continuous fall d have discharges visible at both the tundish and the final point of discharge but where this is not possible or is practically difficult there should be clear visibility at one or other of these locations Examples of acceptable discharge arrangements are i ideally below a fixed grating and above the water seal in a trapped gully ii downward discharges...

Страница 16: ...18m up to 27m Resistance created by each elbow or bend 0 8m 1 0m 1 4m 1 0m 1 4m 1 7m 1 4m 1 7m 2 3m see 3 5 3 9 3 9 a and Diagram 1 Worked Example The example below is for a G1 2 temperature relief valve with a discharge pipe D2 having 4 no elbows and length of 7m from the tundish to the point of discharge From Table 1 Maximum resistance allowed for a straight length of 22mm copper discharge pipe ...

Отзывы: