Installation, Operation and Diagnostics
for your
Communication Interface Unit
MIU(Dial or Lease Line modem with) / 485 (RS485) ~
See MIUXXX for modem Technical Data
Edition: June 17, 2003
P/N: 0049-0002-010 rev A
Страница 1: ...nstallation Operation and Diagnostics for your Communication Interface Unit MIU Dial or Lease Line modem with 485 RS485 See MIUXXX for modem Technical Data Edition June 17 2003 P N 0049 0002 010 rev A...
Страница 2: ...T DESCRIPTION Page 1 3 SERIAL CONNECTOR SPECIFICATIONS Page 2 4 POWER SUPPLY SPECIFICATIONS Page 4 5 RS485 SPECIFICATIONS Page 5 6 ENVIRONMENTAL SPECIFICATIONS Page 6 7 APPROVALS Page 6 DRAWING STANDA...
Страница 3: ...S485 signal levels for both stand alone and embedded applications 2 PRODUCT DESCRIPTION The CIU provides Dial telephone communication capabilities for the industrial environment It can be operated sta...
Страница 4: ...gnal Levels RS 232 RS485 Configuration Connector P1 Connector Type 4 pin terminal header with 138 spacing Signal Levels RS485 3 2 MIU 485 LED LED Blinks every 4 seconds with AC DC power 3 3 MIU 485 LE...
Страница 5: ...d ON RS485 Received RX RX DC terminated with SB 2 Closed SB 1 Open OFF RS485 Received RX RX AC terminated with SB 2 Closed SB 2 Closed ON RS485 Received RX RX terminated SB 2 Open OFF RS485 Received R...
Страница 6: ...nnector Power Connector P3 MIU Connector Type 3 Pin screw type terminal Regulated Powe r Supply Range 48 0 to 220 Volts AC DC Standby Supply Currents 200uA Active Supply Currents 8mA to 40mA plus mode...
Страница 7: ...s RS485 RS422 standard covers line lengths up to 4000 feet For line lengths greater than 4000 feet a line repeater can be added MIUXXXX 485 can drive 4000 feet of 26AWG twisted pair cable at 200k bps...
Страница 8: ...ut damage or impairment ESD susceptibility Field connected circuits meet the requirements of IEC 801 2 for ESD withstand capability up to 10 KV EMI susceptibility Withstand 27 to 1000 MHz per IEC 801...
Страница 9: ...nection RJ11 Leased Line Port LED 1 Earth Digital Ground Jump pins if req d DB9 Data Port Power Connector Power In MIU 48 to 220VAC DC AC or DC non polarized Earth Gnd Power In MIU LV 9 to 36VDC Posit...
Страница 10: ...et Switches B 2 B 1DOWN OFF for all Slaves except UP ON on unit furthest from the Host Switch A 1 RTS CTS Delay UP 0 sec DOWN 7ms Switch A 2 DOWN TXD enables TX 5ms Select only A 2 or Switch A 3 DOWN...
Страница 11: ...set ready from MIUXXX 485 RTS 7 request to send to MIUXXX 485 CTS 8 clear to send from MIUXXX 485 RI 9 ring indication from MIUXXX 485 PGND shield protective ground __________________________________...
Страница 12: ...to Reset mode Switch two ON Switch one three and four are OFF MIU S3 external SW 2 Closed ON MIU is configured for DB9 interface to Modem interface connection SW 1 3 4 Open OFF Switch Three Setting SW...
Страница 13: ...disable no result codes return to terminal ring Connect XXX Q6 Normal mode speed buffering S0 1 Auto Answer active first ring modem will go OFF Hook and start answer sequence C1 Carrier Detect is alwa...
Страница 14: ...rity mode Not available for MIU9 6L C1 Carrier Detect is always true MIU LED will be ON all the time when Carrier Detect is ON D0 DTR is ignored K0 No flow control Note Q5 error detection and data com...
Страница 15: ...l not disable RxD MIU S3 external SW 1 Closed ON MIU is configured for RS485 Module RS485 RxD Output to Modem TxD input SW 2 3 4 Open OFF SA2 SA3 can be configures for TxD enable TxEn signal if there...
Страница 16: ...ntroller RS485 DIAGNOSTICS RS485 CONNECTION FAILURE To test RS485 module set switch SB 3 4 Closed ON to loopback data to the host modem This test is for RS485 2 wire and 4 wire configurations Connect...