OLCT 80
GAS TRANSMITTER
USER MANUAL
44
NPO80GB
Revision F.1
3.10.1
Cal sensor
Calibrate the main sensor (adjust zero and sensitivity).
How to access
See Figure 31.
Tree structure
Figure 32: the
Calibration
menu. Press
ESC
repeatedly to return to the reading display.
Menu
Description
Calib. Gas
Configure the value of the calibration gas to be used.
Adjust.’0’’
•
Place the injection hood over the device and inject clean air from the bottle (flow rate of
30-60 l/h).
•
Wait for the reading to stabilize (at least 2 minutes).
•
Press Enter to confirm the zero.
Note: a CO2 sensor pack must always be zeroed using reconstituted air or nitrogen. Never use
ambient air as the zero since it naturally contains 300-500 ppm of CO
2
.
Содержание OLCT 80 d
Страница 1: ...NPO80GB Revision F 1 OLCT 80 GAS TRANSMITTER USER MANUAL...
Страница 10: ...OLCT 80 GAS TRANSMITTER USER MANUAL 4 NPO80GB Revision F 1...
Страница 56: ...OLCT 80 GAS TRANSMITTER USER MANUAL 50 NPO80GB Revision F 1...
Страница 78: ...OLCT 80 GAS TRANSMITTER USER MANUAL 72 NPO80GB Revision F 1...
Страница 80: ...OLCT 80 GAS TRANSMITTER USER MANUAL 74 NPO80GB Revision F 1...
Страница 86: ...OLCT 80 GAS TRANSMITTER USER MANUAL 80 NPO80GB Revision F 1...
Страница 92: ...OLCT 80 GAS TRANSMITTER USER MANUAL 86 NPO80GB Revision F 1 12 1 OLCT 80 without and with antenna...
Страница 93: ...OLCT 80 GAS TRANSMITTER USER MANUAL NPO80GB Revision F 1 87...
Страница 94: ...OLCT 80 GAS TRANSMITTER USER MANUAL 88 NPO80GB Revision F 1...
Страница 95: ...OLCT 80 GAS TRANSMITTER USER MANUAL NPO80GB Revision F 1 89 12 2 IR20 remote control of the OLCT 80...
Страница 96: ...OLCT 80 GAS TRANSMITTER USER MANUAL 90 NPO80GB Revision F 1...
Страница 104: ...OLCT 80 GAS TRANSMITTER USER MANUAL 98 NPO80GB Revision F 1...
Страница 115: ...OLCT 80 GAS TRANSMITTER USER MANUAL NPO80GB Revision F 1 109...