MULTIFLAME DF-TV7
OPTICAL FLAME DETECTOR
OPERATING MANUAL
32
NOSP17662
Revision 03
6.3
Signal current loop
Status
“4-20”
[mA]
“0-22”
[mA]
TLU state
Line fault
0.0
0.0
Configuration fault
1.5
2.0
DEF
Hardware fault
1.5
2.0
DEF
Sensor fault (Optical self-test)
1.5/2.0/3.0
2.6
DEF
Start-up inhibit
1.5
3.4
Countdown
Permanent inhibit.
1.5
3.4
INH
Maintenance inhibit.
Default / (“Free mode”)
Previous value
/
(1.5)
Previous value
/
(3.4)
INH
Operation, No faults, No Alarm
4.0
4.0
No detection
No alarm
IR detection
(8.0)
(8.0)
(IR detection)
UV detection
(12.0)
(12.0)
(UV detection)
Pre alarm (Detection but still waiting for time
delay)
(16.0)
(16.0)
(Pre-alarm)
Confirmed Alarm
20.0
20.0
Alarm
Configured by TLU600 / TLH700
The maintenance inhibit can be set to “Frozen mode” (factory setting), or “Free mode”.
The standard detector alarm output is either No alarm = 4mA or Confirmed alarm = 20mA.
Pre-alarm states (8 / 12/ 16 mA) are available when the detector is in “expertise mode”.
Содержание Everywhereyoulook MultiFlame DF-TV7
Страница 20: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 14 NOSP17662 Revision 03...
Страница 34: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 28 NOSP17662 Revision 03...
Страница 56: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 50 NOSP17662 Revision 03...
Страница 59: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 53 10 Conformity certificate...
Страница 60: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 54 NOSP17662 Revision 03...
Страница 61: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 55...
Страница 62: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL 56 NOSP17662 Revision 03...
Страница 63: ...MULTIFLAME DF TV7 OPTICAL FLAME DETECTOR OPERATING MANUAL NOSP17662 Revision 03 57...