Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 126254-4 A0.1
Page 4-43
5. For unprotected ribbon fiber, place all of exposed ribbon in flex tubing. The end of the flex
tubing should be pushed back to the IFC clamp.
6. Remove the tray and allow the tubing to hang out the front of the panel.
4.3.1.2 Installing & Routing Network Element Fiber
Network element fiber cable enters the panel at either the rear corner opposite the IFC or one of
the front corners.
1. Route the cable to a corner entrance of the LCX Fiber Splice Panel:
•
If network element leads are gathered in IFC, use a cable clamp at a rear corner, just as
you would for the IFC from a splice vault.
•
If using discrete fiber cables at a front corner entrance, use a cable management system
as illustrated in Figure 50.
You can route network element leads from the bottom up or top down at either a rear or
front corner of the splice panel.
Figure 49 - Installing an IFC for a LCX 1RU Panel
Pivoting Arc
12 - 24 x 1½ in. Screw Secures
Clamp Halves to Rack's Rear Flange
Rear Flange
24-Fiber IFC
Split Grommet
Provide enough slack to
allow tray to fully open