1. Stop relays SR1–2
2. PLd status LED (red)
NOTE: All safety-related parameters must be configured as follows in order to
comply with the appointed safety requirements:
n
The system must be configured in continuous radio mode
n
The stop relays must be switched off when the radio link is down
n
The radio link timeout must be set to a maximum of 500 ms
n
The login/logout function must be activated
n
The Custom ID setting must be deactivated, i.e. the receiver must always use
the unique transmitter ID code
3 .5 Interf ace
The radio system comprises one SRP/CS (as defined in EN ISO 13849-1:2015),
including the stop button (input), the stop relays (output) and the safety-related
logic maintening the stop function (logic).
The interfaces to the SRP/CS are the stop button (as controlled by the
operator) and the stop relays.
INPUT
LOGIC
OUTPUT
Transmitter's stop button
¢
Safety-related logic
¢
Receiver's stop relays
¢
: Interconnection
14
IM-PN-RX107-CERT-01pre4