
SPG8000A User Manual
35
Operate Instrument with Two Power Supplies (Option
DPW Only)
The standard instrument has one Power Supply module installed. With Option
DPW, a second hot
-
swappable, redundant (backup) Power Supply module is
provided. When two Power Supply modules are installed in the instrument, one is
configured as the primary supply and the other is configured as the backup supply.
If that the primary supply fails, the backup supply automatically provides power
to maintain instrument operation. You can remove and replace a failed supply
without having to remove the instrument from operation. (See
hot-swap a Power Supply module
Power Supply Status
The status of the Power Supply modules can be viewed from the front or rear of
the instrument. On the front panel, the PWR1 and PWR2 indicators illuminate
using various colors to show the status of the Power Supply modules. The rear
panel of each Power Supply module has a STATUS LED that matches the status
shown on the PWR1 and PWR2 indicators. See
SPG8000A Installation and Safety
Instructions
for information about the power supply status indicators.
You can use the SYSTEM menu to perform a load test on the backup supply and
to view voltage levels in the instrument.
Temperature weighted
hours (TWH)
The instrument keeps track of the age of a Power Supply module by calculating the
temperature weighted hours (TWH). You can view the TWH of each installed
supply using the SYSTEM : DIAGNOSTICS menu.
TWH calculation method:
When the outside air temperature is at 25 °C or cooler,
the Power Supply module is expected to last 15 years. As the outside air
temperature rises to the maximum operating temperature of 50 °C, the expected
life of the supply decreases to 5 years. Every hour, the instrument measures the
outside temperature and changes
the temperature weighted hours count in
response t
o the measured
temperature.
When the TWH value reaches a value of 131,400, then the associated PWR1 or
PWR2
indicator
will
be set to
orange
to
indicate
that
the
supply
should
be
replaced.
Note
:
When two Power Supply modules are installed, the active supply runs
warmer than the backup supply. Therefore, the TWH of the active supply will
increase faster than the backup supply.
Содержание SPG8000A
Страница 53: ...SPG8000A User Manual 39 Figure 7 Removing a Power Supply module...
Страница 103: ...SPG8000A User Manual 89 Figure 22 SDI Overlay submenu...
Страница 182: ...168 SPG8000A User Manual Figure 61 AES button menu diagram...
Страница 190: ...176 SPG8000A User Manual Figure 73 EMBED button menu diagram...
Страница 194: ...180 SPG8000A User Manual Figure 77 DOLBY E CONFIG submenu diagram part 2...
Страница 197: ...SPG8000A User Manual 183 Figure 81 REF button menu diagram part 2...
Страница 200: ...186 SPG8000A User Manual Figure 84 SDI button menu diagram part 2...
Страница 211: ...SPG8000A User Manual 197 Figure 96 SDI ANC PAYLOAD submenu diagram part 2...
Страница 213: ...SPG8000A User Manual 199 Figure 97 STATUS button menu diagram part 1...
Страница 215: ...SPG8000A User Manual 201 Figure 99 SYSTEM button menu diagram part 1...
Страница 216: ...202 SPG8000A User Manual Figure 100 SYSTEM button menu diagram part 2...
Страница 222: ...208 SPG8000A User Manual PTP submenu Figure 104 shows the diagram for the PTP submenu Figure 104 PTP submenu...
Страница 223: ...SPG8000A User Manual 209 SNMP submenu Figure 105 shows the diagram for the SNMP submenu Figure 105 SNMP submenu diagram...
Страница 225: ...SPG8000A User Manual 211 Figure 107 SNMP TRAPS submenu diagram part 2...
Страница 226: ...212 SPG8000A User Manual GPI submenu Figure 108shows the diagram for the GPI submenu Figure 108 GPI submenu diagram...
Страница 240: ...226 SPG8000A User Manual Figure 123 PTP primary master menu diagram part 1...
Страница 241: ...SPG8000A User Manual 227 Figure 124 PTP primary master menu diagram part 2...
Страница 243: ...SPG8000A User Manual 229 Figure 126 PTP primary slave menu diagram part 2...